1、04-11 23 64 00 - 1 SECTION 23 64 00 PACKAGED WATER CHILLERS SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. / Centrifugal/ Rotary-Screw/ Centr
2、ifugal or Rotary-Screw/ Scroll/ Absorption/ water-cooled chillers, complete with accessories. B. / Rotary-Screw/ Scroll/ Rotary-Screw or Scroll/ air-cooled chillers complete with accessories. 1.2 RELATED WORK A. Section 00 72 00, GENERAL CONDITIONS. B. Section 01 00 00, GENERAL REQUIREMENTS. C. Sect
3、ion 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. D. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. E. Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. F. Section 23 21 23, HYDRONIC PUMPS. G. Section 23 05 41, NOISE and VIBRATION CONTROL FOR
4、 HVAC PIPING and EQUIPMENT. H. Section 23 23 00, REFRIGERANT PIPING. I. Section 23 21 13, HYDRONIC PIPING. J. Section 23 31 00, HVAC DUCTS and CASINGS K. Section 11 41 21, WALK-IN COOLERS and FREEZERS. L. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC and STEAM GENERATION EQUIPMENT. M. Sectio
5、n 26 29 11, LOW-VOLTAGE MOTOR STARTERS. N. Section 23 81 00, DECENTRALIZED UNITARY HVAC EQUIPMENT. O. Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS P. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checklists, and training. 1.3 DEFINITION A.
6、 Engineering Control Center (ECC): The centralized control point for the intelligent control network. The ECC comprises of personal computer and connected devices to form a single workstation. B. BACNET: Building Automation Control Network Protocol, ASHRAE Standard 135. Provided by IHSNot for Resale
7、No reproduction or networking permitted without license from IHS-,-,-04-11 23 64 00 - 2 C. Ethernet: A trademark for a system for exchanging messages between computers on a local area network using coaxial, fiber optic, or twisted-pair cables. D. FTT-10: Echelon Transmitter-Free Topology Transceiver
8、. SPEC WRITER NOTE: SCBA (Self-Contained Breathing Apparatus) is defined below. Since SCBA is no longer required by ASHRAE 15, verify with the VAMC if SCBA(S) are required for this facility. Delete all references if not required. /E. SCBA: Self-Contained Breathing Apparatus./ 1.4 QUALITY ASSURANCE A
9、. Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION, and comply with the following. B. Refer to PART 3 herein after and Section 01 00 00, GENERAL REQUIREMENTS for test performance. C. Comply with AHRI requirements for testing and certificat
10、ion of the chillers. SPEC WRITER NOTE: Verify the compressor/motor warranty with the manufacturers of the equipment being specified and edit the following accordingly. D. Refer to paragraph, WARRANTY, Section 00 72 00, GENERAL CONDITIONS, except as noted below: 1. Provide a 5-year motor, /transmissi
11、on,/ and compressor warranty to include materials, parts and labor. E. Refer to OSHA 29 CFR 1910.95(a) and (b) for Occupational Noise Exposure Standard /F. Refer to 42 CFRPublic Health, Part 84, “Approval of Respiratory Protective Devices,“ Subpart H“Self-Contained Breathing Apparatus,“ 1998./ G. Re
12、fer to ASHRAE Standard 15, Safety Standard for Refrigeration System, for refrigerant vapor detectors and monitor. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designat
13、ion only. B. Air Conditioning, Heating and Refrigeration Institute (AHRI): 370-01Sound Rating of Large Outdoor Refrigerating and Air-Conditioning Equipment Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-04-11 23 64 00 - 3 495-1999 (R2002)Refrigerant
14、 Liquid Receivers 550/590-03Standard for Water Chilling Packages Using the Vapor Compression Cycle 560-00Absorption Water Chilling and Water Heating Packages 575-94Methods for Measuring Machinery Sound within Equipment Space C. American Society of Heating, Refrigerating, and Air-Conditioning Enginee
15、rs (ASHRAE): ANSI/ASHRASE-15-2007Safety Standard for Mechanical Refrigeration Systems GDL 3-1996Guidelines for Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems D. American Society of Mechanical Engineers (ASME): 2007 .ASME Boiler and Pressure
16、Vessel Code, Section VIII, “Pressure Vessels - Division 1“ E. American Society of Testing Materials (ASTM): C 534/ C 534M-2008Preformed, Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular Form C 612-04Mineral-fiber Block and Board Thermal Insulation F. National Electrical Manufact
17、uring Association (NEMA): 250-2008Enclosures for Electrical Equipment (1000 Volts Maximum) G. National Fire Protection Association (NFPA): 70-2008.National Electrical Code H. Underwriters Laboratories, Inc. (UL): 1995-2005. Heating and Cooling Equipment 1.6 SUBMITTALS A. Submit in accordance with Sp
18、ecification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. SPEC WRITER NOTE: There could be more than one type of chillers required for the project. Edit paragraph B and associated subparagraphs to suit project requirements in the chiller selection. B. Manufacturers Literature and Data.
19、 1. / Centrifugal / rotary-screw / scroll / absorption / water chillers, including motor starters, control panels, and vibration isolators, and remote condenser data shall include the following: a. Rated capacity. Provided by IHSNot for ResaleNo reproduction or networking permitted without license f
20、rom IHS-,-,-04-11 23 64 00 - 4 b. Pressure drop. c. Efficiency at full load and part load WITHOUT applying any tolerance indicated in the AHRI 550/590/Standard. d. Refrigerant e. Fan performance (Air-Cooled Chillers only.) f. Accessories. g. Installation instructions. h. Start up procedures. i. Wiri
21、ng diagrams, including factor-installed and field-installed wiring. j. Sound/Noise data report. Manufacturer shall provide sound ratings. Noise warning labels shall be posted on equipment. /k. Self-contained breathing apparatus (SCBA)./ l. Refrigerant vapor detectors and monitors. C. Maintenance and
22、 operating manuals for each piece of equipment in accordance with Section 01 00 00, GENERAL REQUIREMENTS. D. Run test report for all chillers. E. Product Certificate: Signed by chiller manufacturer certifying that chillers furnished comply with AHRI requirements. The test report shall include calibr
23、ated curves, calibration records, and data sheets for the instrumentation used in factory tests. SPEC WRITER NOTE: Show seismic restraints for Refrigeration Equipment in accordance with the latest VA Handbook H-18-8, “Seismic Design Requirements“. Delete the following paragraph if the chiller(s) is
24、located outside the seismic zone. /F. Provide seismic restraints for refrigeration equipment to withstand seismic forces. / SPEC WRITER NOTE: Chillers shall be selected on a project specific basis. In general, chillers should be selected within the following ranges: - Centrifugal(water-cooled): 200-
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2364002011PACKAGEDWATERCHILLERSPDF