1、05-11 23 52 39 - 1 SECTION 23 52 39 FIRE-TUBE BOILERS SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraph. Deleted paragraphs should be labeled “omitted”. 2. References to pressure are
2、 gage pressure unless otherwise noted. 3. Contract drawings must include (as applicable) the VA National CAD Standards listed below: SD235239-01 Fire Tube Boiler SD235239-02 Access Platform Arrangement For Fire Tube Boiler SD235239-03 Natural Gas and Liquefied Petroleum Gas Burner and Igniter Fuel S
3、tandard Piping Diagram SD235239-04 No. 2, 5 unit with highest set point shall be manual reset. 2. Bellows actuated sealed snap-acting switch or mercury switch with adjustable set point and adjustable differential pressure (automatic reset unit); switch position indicator. 3. Rated for 1375 kPa (200
4、psi) minimum emergency pressure. 4. Set pressure range: To 150 percent of required set pressure. 5. Provide indicators with graduated scales for set point and differential pressure. 6. Mounting: Connect to water column piping. There shall be no valves between cutoff and boiler shell. Provide siphons
5、 at each switch to protect bellows from high temperature. 7. Set Points: a. Automatic Reset Unit: Refer to boiler schedule shown on the drawings. If not shown, set at 35 kPa (5 psi) below the set pressure of the manual reset unit. b. Manual Reset Unit: 35 kPa (5 psi) below lowest safety valve set pr
6、essure. Subtractive differential not to exceed 70 kPa (10 psi). 8. Refer to Section 23 09 11, INSTRUMENTATION and CONTROL FOR BOILER PLANT for the operation of the cutouts. 2.3 BURNER AND FUEL TRAINS: SPEC WRITER NOTE: Delete low NOx requirements unless required by air emissions authorities. Provide
7、d by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 23 52 39 - 15 A. Burner Type: Combination natural gas and fuel oil, packaged, forced draft, modulating firing /, variable speed forced draft fan/. / Design for low NOx emissions. / 1. Gas Burner: Ring ty
8、pe with multiple ports or spuds. 2. Oil Burner: Gun type, inside mix, low pressure air atomizing. 3. Igniter (Pilot): Interrupted, electrically ignited, natural gas and propane. B. Service: 1. Continuous operation at all firing rates on each fuel listed under Article, PROJECT CONDITIONS of Part 1. D
9、esign the entire burner and fuel train system for application to the specific boiler furnished and for service at the available fuel pressures. 2. Igniter (Pilot) Fuels: Normal fuel will be natural gas. Propane will be used if there is an interruption in natural gas service. 3. Main Fuels: After boi
10、lers are accepted for operation, choice of fuels will be based on cost and availability. C. Performance: 1. Igniter (pilot) flame on natural gas and propane shall form close to the point of ignition and shall be stable. Ignite both the gas and oil burner with single igniter. 2. Main flame on gas and
11、 oil fuels shall ignite at lowest firing rate. 3. Main flame characteristics at all firing rates: a. Flame retained at the burner. b. Flame stable with no blowoff from the burner or flashback into the burner. No pulsations. c. No deposits of unburned fuel or carbon at any location. d. No carryover o
12、f flame beyond the end of the first pass (furnace tube). 4. Operation: a. Minimum turndown / 10/1 / 8/1 /. b. Operate at all loads on any one fuel without any manual changes to burners, fuel trains or fuel pressures, atomizing media trains or pressures. c. Excess Air in Flue Gases with Oxygen Trim a
13、t Null Position: Boiler Steam Output, Percent of Maximum Percent Excess Air Allowable Range Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 23 52 39 - 16 Required Capacity Below 25 15 minimum 25 39 15 35 40 100 15 25 d. Performance at any load
14、point shall be repeatable after increasing or decreasing the firing rate. Repeatability plus or minus five percent excess air, at 25 percent and higher boiler loading except excess air must remain within ranges specified above. SPEC WRITER NOTE: Oxygen trim control should be specified on boilers tha
15、t have parallel positioning combustion controls. /e. Oxygen trim control set at maximum position shall not blow out the fire at any load point. At minimum position, the combustion shall not go below stoichiometric./ f. Noise and Vibration: Refer to Section 23 05 51, NOISE and VIBRATION CONTROL FOR B
16、OILER PLANT for requirements on forced draft fan and oil atomization system. Burners shall operate without pulsation. SPEC WRITER NOTE: Engineer must review local emissions rules and revise the following paragraphs as necessary. 5. Flue Gas Emissions Limits: a. Carbon Monoxide: Shall not exceed 200
17、PPM. b. Smoke: On natural gas and No. 2 oil shall not be visible and shall not exceed No. 1 on the Bacharach smoke scale. SPEC WRITER NOTE: Delete NOx requirements except where required by local air emissions authorities. Insert local NOx emissions limits if applicable. If local emissions rules expr
18、ess the requirement in a different way, revise the subparagraph to conform. c. NOx: _ ppm maximum, corrected to 3 percent oxygen, dry basis on natural gas /and low nitrogen No. 2 fuel oil/. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-11 23 52
19、39 - 17 D. Construction: 1. Burner Access (Main Burner and Igniter): Arrange fuel valve and piping trains, controls and other devices so that they do not interfere with the removal and replacement of burner parts. 2. Arrangement of Fuel Valve and Piping Trains: All devices shall be accessible for ma
20、intenance or replacement without removal of other devices. Do not attach any piping or devices to boiler casings. 3. Coatings: Provide surface preparation, heat resistant prime and finish coats using standard color of boiler manufacturer. Refer to Section 09 91 00, PAINTING. 4. Combustion Air System
21、 and Flue Gas Recirculation (FGR) System (if provided): a. Air flow rates controlled by forced draft fan inlet or outlet dampers /and variable speed drive/. b. Symmetrical, balanced distribution of combustion air into the burner. c. Provide induced type flue gas recirculation (FGR) system if FGR is
22、necessary to achieve specified NOx limits. All FGR ductwork shall comply with Section 23 51 00, BREECHINGS, CHIMNEYS, and STACKS. d. Forced Draft Fan: Airfoil or backwardly inclined wheel, electric motor driven. Design for required excess air and for static pressure that is based on losses from fan
23、inlet to stack or chimney outlet, including economizer (if provided), at jobsite altitude. Fan shall have no resonant frequencies at all operating speeds. e. Motor: TEFC or open drip proof, non-overloading under all fan operating conditions, design for 40 C ambient, premium efficiency type. Motors f
24、or variable speed service shall be rated inverter-ready. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. f. Damper: Design to provide accurate control of excess air with minimum hysteresis. On variable speed systems, the damper shall control only at lower firing rates.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2352392011FIRETUBEBOILERSPDF