1、03-10 23 36 00 - 1 SECTION 23 36 00 AIR TERMINAL UNITS SPEC WRITER NOTE: 1. Delete between/-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraph. 2. References to pressure in this section are gage pressure unless otherwise n
2、oted. PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Edit each of the following paragraphs as necessary to agree with products being used. Air terminal units, air flow control valves. 1.2 RELATED WORK A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS: Seismic rest
3、raints for equipment. B. Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION: General mechanical requirements and items, which are common to more than one section of Division 23. C. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT: Noise requirements. D. Se
4、ction 23 31 00, HVAC DUCTS AND CASINGS: Ducts and flexible connectors. E. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Valve operators. F. Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC: Flow rates adjusting and balancing. G. Section 23 82 16, AIR COILS: Heating and Coolin
5、g Coils pressure ratings. 1.3 QUALITY ASSURANCE Refer to Paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data:
6、 1. Air Terminal Units: Submit test data. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-10 23 36 00 - 2 2. Air flow control valves. SPEC WRITER NOTE: Samples are generally not required as submittals. However, for large installations, samples can
7、 be requested in consultation with the Resident Engineer and Medical Center. Use paragraph C below for compliance. C. Samples: Provide one typical air terminal unit for approval by the Resident Engineer. This unit will be returned to the Contractor after all similar units have been shipped and deeme
8、d acceptable at the job site. D. Certificates: 1. Compliance with paragraph, QUALITY ASSURANCE. 2. Compliance with specified standards. E. Operation and Maintenance Manuals: Submit in accordance with paragraph, INSTRUCTIONS, in Section 01 00 00, GENERAL REQUIREMENTS. 1.5 APPLICABLE PUBLICATIONS A. T
9、he publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. Air Conditioning and Refrigeration Institute (AHRI)/(ARI): 880-08 . Air Terminals Addendum to ARI 888-98 incorporated into standard p
10、osted 15th December 2002 C. National Fire Protection Association (NFPA): 90A-09 . Standard for the Installation of Air Conditioning and Ventilating Systems D. Underwriters Laboratories, Inc. (UL): 181-08 . Standard for Factory-Made Air Ducts and Air Connectors E. American Society for Testing and Mat
11、erials (ASTM): C 665-06 . Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing 1.6 GUARANTY In accordance with the GENERAL CONDITIONS PART 2 - PRODUCTS DESIGNERS NOTE: See HVAC Design Manual Appendix 7-A Table 7-A1 for high humidit
12、y areas. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-10 23 36 00 - 3 2.1 GENERAL A. Coils: 1. /Surgical Suite AHU: Provide copper fins and copper coils for all hot water reheat coils serving surgical suite/. 2. /All Air-Handling Units: Provide
13、 aluminum fins and copper coils for all hot water reheat coils/. 3. Water Heating Coils: a. ARI certified, continuous plate or spiral fin type, leak tested at 2070 kPa (300 PSI). b. Capacity: As indicated, based on scheduled entering water temperature. c. Headers: Copper or Brass. d. Fins: Aluminum,
14、 maximum 315 fins per meter (8 fins per inch). e. Tubes: Copper, arrange for counter-flow of heating water. f. Water Flow Rate: Minimum 0.032 Liters/second (0.5 GPM). g. Provide vent and drain connection at high and low point, respectively of each coil. h. Coils shall be guaranteed to drain. 4. Elec
15、tric Heating Coils: a. ARI certified, spiral fin type. b. Capacity: As indicated, based on scheduled data. c. Coil: Enclosed copper tube, aluminum finned element of coiled nickel-chrome resistance wire centered in tubes and embedded in refractory material. Exposed helical coil of nickel-chrome resis
16、tance wire with refractory ceramic support bushings will not be allowed. B. Labeling: Control box shall be clearly marked with an identification label that lists such information as nominal CFM, maximum and minimum factory-set airflow limits, coil type and coil connection orientation, where applicab
17、le. C. Factory calibrate air terminal units to air flow rate indicated. All settings including maximum and minimum air flow shall be field adjustable. D. Dampers with internal air volume control: See section 23 31 00 HVAC DUCTS and CASINGS. E. Terminal Sound Attenuators: See Section 23 31 00 (HVAC D
18、UCTS AND CASINGS). Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-03-10 23 36 00 - 4 2.2 AIR TERMINAL UNITS (BOXES) A. General: Factory built, pressure independent units, factory set-field adjustable air flow rate, suitable for single duct applicati
19、ons. Use of dual-duct air terminal units is not permitted. Clearly show on each unit the unit number and factory set air volumes corresponding to the contract drawings. Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC work assumes factory set air volumes. Coordinate flow controller seque
20、nce and damper operation details with the drawings and Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. All air terminal units shall be brand new products of the same manufacturer. DESIGNERS NOTE: All boxes for the new construction and major renovation shall be DDC controlled. Use non-DDC b
21、oxes for minor replacement projects, where the existing air-handling units are not DDC controlled. B. Capacity and Performance: The Maximum Capacity of a single terminal unit shall not exceed 566 Liters/second (1,200 CFM) with the exception of operating rooms and Cystoscopy rooms, which shall be ser
22、ved by a single air terminal unit at a maximum of 1,250 Liters/second (3,000 CFM). C. Sound Power Levels: SPEC WRITER NOTE: Coordinate selection of the air terminal units with the acoustic analysis to be performed by the designer. For each terminal unit size, use maximum allowable radiated and trans
23、mitted sound power levels, in all octave bands, based on the maximum inlet static pressure and air volume for each size. Acoustic performance of the air terminal units shall be based on the design noise levels for the spaces stipulated in Section 23 05 41 (Noise and Vibration Control for HVAC Piping
24、 and Equipment). Equipment schedule () shall show the sound power levels in all octave bands. Terminal sound attenuators shall be provided, as required, to meet the intent of the design. D. Casing: Unit casing shall be constructed of galvanized steel no lighter than 0.85 mm (22 Gauge). Air terminal
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2336002010AIRTERMINALUNITSPDF