1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJuly 17, 20171UL 199JOutline of Investigation for Fire Testing of Specific Application Sprinklersfor Use on WindowsIssue No. 2July 17, 2017Summary of TopicsThis Second Issue of the Outline of Inv
2、estigation for Fire Testing ofSpecific Application Sprinklers for Use on Windows, UL 199J, is beingissued to provide clarification as to the fire test method used to evaluatespecific application sprinklers for use on windows.ULs Outlines of Investigation are copyrighted by UL. Neither a printed nore
3、lectronic copy of an Outline of Investigation should be altered in any way. All ofULs Outlines of Investigation and all copyrights, ownerships, and rights regardingthose Outlines of Investigation shall remain the sole and exclusive property of UL.COPYRIGHT 2017 UL LLCUL COPYRIGHTED MATERIAL NOT AUTH
4、ORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJULY 17, 2017UL 199J2No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 Scope .42 Components 43 Units of Measurement .54 Undated Re
5、ferences 5PERFORMANCE5 Fire Tests for Sprinklers Used to Protect Heat Strengthened, Tempered Glazing Materials withInstructions to Keep Combustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface.56 Fire Tests for Sprinklers Used with a Fire Rated Glazing Material without a Limitation for
6、 KeepingCombustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface .56.1 General .56.2 Test Arrangement 66.3 Test method .8JULY 17, 2017 UL 199J 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 Scope1.1 These requirem
7、ents cover the fire testing of specific application sprinklers for use on non-operablewindows when the sprinklers are installed in accordance with the manufacturers instructions and theStandard for the Installation of Sprinkler Systems, NFPA 13.1.2 Sprinklers investigated in accordance with this Out
8、line shall also comply with the applicablerequirements in the Standard for Automatic Sprinklers for Fire-Protection Service, UL 199, not includingthe fire and water distribution tests.1.3 The requirements described herein are intended to investigate the ability of the sprinklers to providewater on t
9、he surface of a window to limit the transmission of heat from a fire to the glazing material andmaintain the integrity of the window.1.4 These sprinklers have not been investigated for use as a substitute for fire protection rated glazingmaterials investigated in accordance with ANSI/UL 9, Fire Test
10、s of Window Assemblies.2 Components2.1 Except as indicated in 2.2, a component of a product covered by this Outline shall comply with therequirements for that component.2.2 A component is not required to comply with a specific requirement that:a) Involves a feature or characteristic not required in
11、the application of the component in theproduct covered by this Outline, orb) Is superseded by a requirement in this Outline.2.3 A component shall be used in accordance with its rating established for the intended conditions ofuse.2.4 Specific components are incomplete in construction features or res
12、tricted in performance capabilities.Such components are intended for use only under limited conditions, such as temperatures not exceedingspecified limits, and shall be used only under those specific conditions.JULY 17, 2017UL 199J4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDI
13、STRIBUTION WITHOUT PERMISSION FROM UL3 Units of Measurement3.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory orapproximate information.4 Undated References4.1 Any undated reference to a code or standard appearing in the requirements of this Outline shal
14、l beinterpreted as referring to the latest edition of that code or standard.PERFORMANCE5 Fire Tests for Sprinklers Used to Protect Heat Strengthened, Tempered Glazing Materials withInstructions to Keep Combustibles at Least 2 inches (50.8 mm) Away from the Glazing Surface5.1 Sprinklers intended to p
15、rotect heat strengthened, tempered glazing materials with instructions to keepcombustibles at least 2 inches (50.8 mm) away from glazing surface shall be tested in accordance withULC/ORD-C263.1-99, Sprinkler Protected Window Systems using the minimum glazing thicknessspecified in the manufacturers i
16、nstallation instructions.Exception: A gas burner arrangement that is different from the arrangement described inULC/ORD-C263.1-99 shall be permitted to be used to achieve the required temperatures within the room.6 Fire Tests for Sprinklers Used with a Fire Rated Glazing Material without a Limitatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT199J2017ULOUTLINEOFINVESTIGATIONFORFIRETESTINGOFSPECIFICAPPLICATIONSPRINKLERSISSUE2PDF

链接地址:http://www.mydoc123.com/p-1069213.html