UL 2034 CRD-2015 UL Standard for Safety Single and Multiple Station Carbon Monoxide Alarms - Section Paragraph Reference New 3 26 Revised 38 1 3 38 2 2 38 2 3 39 1 1 39 1 2 40 1 4.pdf
《UL 2034 CRD-2015 UL Standard for Safety Single and Multiple Station Carbon Monoxide Alarms - Section Paragraph Reference New 3 26 Revised 38 1 3 38 2 2 38 2 3 39 1 1 39 1 2 40 1 4.pdf》由会员分享,可在线阅读,更多相关《UL 2034 CRD-2015 UL Standard for Safety Single and Multiple Station Carbon Monoxide Alarms - Section Paragraph Reference New 3 26 Revised 38 1 3 38 2 2 38 2 3 39 1 1 39 1 2 40 1 4.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): CZHF, CZHF2Standard Number: UL 2034Standard Title: Standard for Single and Multiple Station Carbon Monoxide AlarmsEdition Date: February 28, 2008Edition Numb
3、er: 3Section / Paragraph Reference: New 3.26, Revised 38.1.3, 38.2.2, 38.2.3, 39.1.1,39.1.2, 40.1, 40.5, 46.1.1, 47.1, 47.2, 49.1.2, 49.4.1, 54.1, 55.1, 58.1, 65.1, 71.1, 72.1,73.1, 74.1, 75.3.1, 75.4.1, 75.8.1.f, 83.1.l, 84.1.fSubject: Define pre-alarm and establish requirements for products (alarm
4、s andaccessories) that employ a pre-alarm signal.DECISION:New Section 3.263.26 Pre-alarm An optional signal above 30 ppm of CO, unique from the trouble and alarm signal,intended to provide an early notification of the detection of carbon monoxide prior to an alarm signal.When the pre-alarm signal oc
5、curs, the carbon monoxide alarm shall emit the unique pre-alarm signal atthe indicating carbon monoxide alarm and may also send the pre-alarm signal to a wirelesscommunication remote accessory device. The pre-alarm signal is an optional signal that whenimplemented does not prohibit the normal operat
6、ion of the carbon monoxide alarm. When rapid levels ofcarbon monoxide are detected as specified in UL 2034, the alarm signal shall take precedence over thepre-alarm signal.Revised Section 38.1.3, 38.2.2 and 38.2.3 (Section 38 Electrical Supervision Test)38.1.3 If an audible trouble signal is require
7、d to indicate a fault condition, it shall be produced every 30 -60 seconds 10 percent for a minimum of seven consecutive days. The trouble signal shall be distinctivefrom the alarm signal and, if provided, pre-alarm signal.38.2.2 Neither loss nor restoration of power shall cause an alarm signal unde
8、r either momentary orextended (at least 1/2 hour) power outage conditions. Momentary energization of the alarm circuit(maximum of 1 second), and energization of the trouble circuit (maximum of 2 minutes), is not consideredan alarm signal. A gradual increase to 110 percent of rated voltage or reducti
9、on to 0 volts from ratedvoltage at a rate of not greater than 5 volts per minute shall not result in energization of the alarm (orpre-alarm) signal for more than 1 second.38.2.3 Loss of power to a single unit of a multiple station alarm configuration, while energized in thestandby condition, shall n
10、ot result in a false alarm (or pre-alarm) and shall not prevent the operation of theremaining units for alarm.Revised Section 39.1 (Section 39 Sensitivity Test)UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL39.1.1 A carbon monoxide alarm shal
11、l operate (alarm signal) at or below the test points specified in PartA of Table 39.1 when using the test equipment described in 39.2.1. These test points are based on plottedlimits for the 10 percent COHb curve Figure 39.1. If the alarm employs a variable sensitivity setting, testmeasurements are t
12、o be made at maximum and minimum settings. For this test, three carbon monoxideconcentrations (70, 150, and 400 ppm) are to be used as specified in Part A of Table 39.1.39.1.2 A carbon monoxide alarm shall not operate (alarm signal) below the test points specified in Part Bof Table 39.1, when using
13、the test equipment described in 39.2.1. If the alarm employs a variablesensitivity setting, test measurements are to be made at maximum and minimum settings. For this test, atleast two carbon monoxide concentrations (70 and 30 ppm) are to be used as specified in Part B of Table39.1. It is not prohib
14、ited for a pre-alarm signal to occur prior to the exposure time specified for the testpoints outlined in Table 39.1 provided the gas concentration is in excess of 30 ppm carbon monoxide39.1.3 A single station carbon monoxide alarm employing a secondary power supply shall operate withinthe limits spe
15、cified in 39.1.1 when operating from the secondary power supply.Revised Section 40.1 and 40.5 (Section 40 Selectivity Test)40.1 The alarm (or pre-alarm) shall not sound when an alarm is exposed sequentially, as described in 40.3- 40.6, to the concentrations of gases and vapors shown in Table 40.1. T
16、hese substances are intendedto represent air contaminants found in the vicinity of an installed alarm.40.5 Allow the alarm to remain in the chamber for 2 hours. During this time the alarm (or pre-alarm) shallnot sound.Revised Section 42.1 (Stability Test)42.1 There shall not be false alarms (or pre-
17、alarms) of an alarm set at the maximum sensitivity settingwhen two representative samples are placed in the test chamber as specified in 39.2.1. Two additionalsamples are to be tested as described in 42.2. Momentary energization of the alarm (maximum of 1second) does not constitute a false alarm (or
18、 pre-alarm) during this test. Alarms are to be conditioned fornot less than 48 hours under the ambient conditions specified in 39.2.1.Revised Section 46.1 (Section 46 Variable Ambient Temperature Test)46.1.1 An alarm shall operate for its intended signaling performance and there shall be no false al
19、arms(or pre-alarms) during the exposures when tested at ambient temperatures of 0C and 49C (32F and120F) at a relative humidity as indicated below. Two alarms, one at maximum and one at minimumsensitivity, are to be maintained at both ambient temperatures for at least 3 hours so that thermalequilibr
20、ium is reached. The units then are to be tested for sensitivity while connected to a source of supplythat is in accordance with 35.3.1.Revised Section 47.1 and 47.2 (Section 47 Humidity Test)47.1 High humidity (non-condensing)47.1.1 Two alarms, one at maximum and one at minimum sensitivity, shall op
21、erate for their intendedsignaling performance and there shall be no false alarms (or pre-alarms) during the exposure whenexposed for 168 hours to air having a relative humidity of 95 4 percent at a temperature of 52 3C (1255F) while energized from a source of supply in accordance with 35.3.1.47.2 Lo
22、w humiditySTANDARD NUMBER: UL 2034 -2-UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL47.2.1 Two alarms, one at maximum and one at minimum sensitivity, shall operate for their intendedsignaling performance and there shall be no false alarms (o
23、r pre-alarms) during the exposure whenexposed for 168 hours to air having a relative humidity of 10 3 percent at a temperature of 22 3C (725F) while energized from a source of supply in accordance with 35.3.1.Revised Section 49.1.2 and 49.4.1 (Section 49 Transient Tests)49.1.2 Different alarms are t
24、o be used for each of the four tests in 49.1.1. The alarms shall not false alarm(or pre-alarm) for more than 1 second. Alarms using a primary battery as a power supply are to besubjected to the extraneous transients test only. If an alarm is intended for multiple-station connection, thetransient tes
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL2034CRD2015ULSTANDARDFORSAFETYSINGLEANDMULTIPLESTATIONCARBONMONOXIDEALARMSSECTIONPARAGRAPHREFERENCENEW326REVISED381338223823391139124014PDF

链接地址:http://www.mydoc123.com/p-1067777.html