1、Comments, suggestions, or questions on this document should be addressed to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC 20376-5160 or emailed to CommandStandardsnavy.mil, with the subject line “Document Comment”. Since contact
2、information can change, you may want to verify the currency of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 6320 INCH-POUND MIL-PRF-32226 25 October 2006 PERFORMANCE SPECIFICATION FLAME DETECTOR, ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS) Th
3、is specification is approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers the performance requirements for flame detectors (see 6.8.5), which are components of an overall Advanced Fire and Smoke Sensor System (AFSSS) for use on n
4、aval ships. These flame detectors may be of commercial-off-the-shelf (COTS) design, but must be rugged (see 6.8.12) enough to meet all of the requirements of this performance specification and the rigors of Navy shipboard service. Performance requirements for the other associated AFSSS components (e
5、.g., ionization (see 6.8.8) and photoelectric (see 6.8.10) smoke sensors (see 6.8.15), heat sensors (see 6.8.7), Flame Detector Zone Modules (FDZM) (see 6.8.6), Switch Closure Zone Modules (SCZM) (see 6.8.16), isolators (see 6.8.9), and alarm panel (see 6.8.2) are contained in their respective AFSSS
6、 specifications. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While
7、 every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this specification, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards,
8、 and handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-S-901 - Shock Tests,
9、 H.I. (High Impact); Shipboard Machinery, Equipment and Systems, Requirements for MIL-E-2036 - Enclosures for Electric and Electronic Equipment MIL-PRF-16884 - Fuel, Naval Distillate MIL-DTL-24643 - Cables and Cords, Electric, Low Smoke, for Shipboard Use General Specifications for Provided by IHSNo
10、t for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32226 DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1 - Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II Internally Excited) MIL-STD-461 - Requirements for the Control of Electromag
11、netic Interference Characteristics of Subsystems and Equipment (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 No
12、n-Government publications. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. FACTORY MUTUAL RESEARCH CORPORATION (FMRC) ANSI/FM 3260 - American National Stand
13、ard for Radiant Energy-Sensing Fire Detectors for Automatic Fire Alarm Signaling (Copies of this document are available from Factory Mutual Research Corporation, 1151 Boston-Providence Turnpike, Norwood, MA 02062 or online at .) NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 72 - National Fire Ala
14、rm Code (Copies of this document are available from National Fire Protection Association, One Batterymarch Park, Quincy, MA 02269 or online at http:/www.nfpa.org/.) 2.4 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this
15、 document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2 and 6.3), a sample shall be subjected to first article inspection in accordance with 4.2
16、. 3.2 Design requirements. 3.2.1 Design, materials, and manufacturing processes. The contractor shall select the materials, but the materials shall meet all of the interface, operational, and performance requirements specified herein. 3.2.2 Recycled, recovered, or environmentally preferable material
17、s. Recycled, recovered, or environmentally preferable materials should be used to the maximum extent possible, provided that the material meets or exceeds the operational and maintenance requirements, and promotes economically advantageous life cycle costs. 3.3 Configuration. The overall flame detec
18、tor shall consist of the appropriate electronics and viewing lens(es) housed in an appropriate enclosure. The flame detector shall also have appropriate mounting hardware that allows for mounting to the ship as well as adjustments for aligning the flame detectors orientation after mounting (see 3.3.
19、4 and 3.7.2). The term, “flame detector,” as used in this specification, refers to the overall flame detector consisting of the enclosed flame detector and its mounting and line-of-sight adjusting hardware. Flame detectors shall operate properly in both overhead (vertical) or bulkhead (horizontal) m
20、ounted positions. Flame detectors shall operate properly when oriented/aimed in any direction. 3.3.1 Interchangeability. The AFSSS flame detector shall have a unique model number and shall be physically identical and interchangeable with all other AFSSS flame detectors from the same manufacturer. 2
21、Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32226 3.3.2 Flame detector principle of operation. Flame detectors shall be the discriminating type that requires radiation of two or more different frequencies (e.g., one in the ultraviolet ran
22、ge and one in the infrared range, or two or three in the infrared range, etc.) before an alarm is generated, in order to minimize false alarms (see 6.8.4) from non-fire sources and nuisance alarms from welding or other light-emitting operations. In addition, flame detectors shall have a flicker disc
23、rimination (characteristic of the natural flicker frequency of a fire) to further prevent false or nuisance alarms from non-fire sources. Flame detectors shall be restorable after alarm, but only after a reset (see 6.8.11) at the alarm panel is manually executed and the detector is no longer viewing
24、 the radiation from the fire (i.e., flame detector alarms shall latch at the alarm panel). 3.3.3 Individual addressability and LED. Either the flame detector or the FDZM shall have an adjustable mechanical device or dipswitch that shall be easily set to allow each flame detector to be individually i
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILPRF322262006FLAMEDETECTORADVANCEDFIREANDSMOKESENSORSYSTEMAFSSS 高级 敏感 元件 系统 火焰 探测器 PDF

链接地址:http://www.mydoc123.com/p-981012.html