《DIN EN 1397-2015 Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance German version EN 1397 2015《热交换器 液压间风扇线圈装置 性能确定的试验方法 德文版本EN 1397-.pdf》由会员分享,可在线阅读,更多相关《DIN EN 1397-2015 Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance German version EN 1397 2015《热交换器 液压间风扇线圈装置 性能确定的试验方法 德文版本EN 1397-.pdf(29页珍藏版)》请在麦多课文档分享上搜索。
1、 One or more corrigenda exist with corrections to this document. These can be searched online and ordered free of charge at www.beuth.de November 2015 English price group 14No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth
2、 Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 27.060.30!%G=“2365726www.din.deDIN EN 1397Heat exchangers Hydronic room fan coil units Test procedures for establishing the performance;English version EN 1397:2015,English translation of DIN EN
3、 1397:2015-11Wrmebertrager WasserLuftVentilatorkonvektoren Prfverfahren zur Leistungsfeststellung;Englische Fassung EN 1397:2015,Englische bersetzung von DIN EN 1397:2015-11changeurs thermiques Ventiloconvecteurs eau Procdures dessai pour la dtermination des performances;Version anglaise EN 1397:201
4、5,Traduction anglaise de DIN EN 1397:2015-11SupersedesDIN EN 1397:199905www.beuth.deDTranslation by DIN-Sprachendienst.In case of doubt, the German-language original shall be considered authoritative.Document comprises 28 pages 10.15 DIN EN 1397:2015-11 2 A comma is used as the decimal marker. Natio
5、nal foreword This document (EN 1397:2015) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units” (Secretariat: AENOR, Spain). The responsible German body involved in its preparation was DIN-Normenausschuss Kltetechnik (DIN Standards Committee Refrigeration Techno
6、logy), Working Committee NA 044-00-11 AA Klte-Apparate. Amendments This standard differs from DIN EN 1397:1999-05 as follows: a) the field of application has been revised to include ducted units 20 kPa) Air dry bulb temperature C 0,2 K dew point temperature C 0,3 K static pressure difference Pa 3 Pa
7、 (p 100 Pa) 3 % (p 100 Pa) Others brine concentration % 2 % atmospheric pressure kPa 0.5 kPa fan speed min-1 1 % mass kg 0.5 % Electrical quantities electric power W 1 % or at least 1 W voltage V 0,5 % current A 0,5 % electrical energy Wh 1 % The heating, the total cooling and latent capacities obta
8、ined from measurements on the liquid side shall be determined with a maximum uncertainty of measurement of 5 % independent of the individual uncertainties of measurement including uncertainties of the properties of fluids. 7.8 Test duration It is necessary to record all the meaningful data continuou
9、sly. In case of recording instruments which operate on a cyclic basis, the sequence shall be adjusted such that a complete recording is effectuated at least once every 30 s. The data shall be measured in steady state operation. The duration of the measurement shall not be less than 30 min. DIN EN 13
10、97:2015-11 EN 1397:2015 (E) 16 7.9 Data to be recorded The data to be recorded for the air flow and capacity tests are given in Table 9. The table identifies the general information required but is not intended to limit the data to be obtained. These data shall be the mean values taken over the data
11、 recording period. Table 9 Data to be recorded Symbol Unit Atmospheric pressure PatmkPa Voltage - V Frequency - Hz Speed control setting of the fan speed - - Rotational speed of the fan n2min-1 Total electric power input PelecW Air inlet dry bulb temperature tAC Air inlet wet bulb temperature tAwC A
12、ir inlet dew point temperature tAdpC External static pressure, where applicable pAPa Mass flow rate of condensate (air side) qmWq/s Inlet liquid temperature tL1C Outlet liquid temperature tL2C Liquid mass flow rate qmLg/s Brine concentration, where applicable - % vol Specific heat capacity of liquid
13、 at tL1cpL1kJ/(kg.K) Specific heat capacity of liquid at tL2cpL2kJ/(kg.K) Specific enthalpy of liquid at at tL1hL1kJ/kg Specific enthalpy of liquid at tL2hL2kJ/kg Liquid side pressure drop pLkPa Total cooling capacity PC W Latent cooling capacity Plat W Sensible cooling capacity PsensW Heating capac
14、ity PH W DIN EN 1397:2015-11 EN 1397:2015 (E) 17 8 Performance tests 8.1 General The sweat test and the condensate disposal test may be executed simultaneously. 8.2 Test conditions The standard conditions for the sweet test and air side condensate disposal test are given in Table 10. Table 10 Standa
15、rd conditions for sweat test and air side condensate disposal test Unit Value Air side conditions air inlet temperature dry bulb C 27 wet bulb C 24 Liquid side conditions Inlet temperature C 6 Outlet temperature C 10 Nominal voltage and frequency shall be used. The fan speed settings shall be as fol
16、lows: for condensate disposal test: minimum; for sweat test: minimum. No external resistance shall be added at the air inlet and outlet of the unit. 8.3 Sweat test Checks shall be made to ascertain whether there is any condensation of water on the casing and water dripping from or being blown off th
17、e fan coil unit. For the sweat test, the grilles, dampers, etc., shall be set to allow for the maximum cooling power. The fan speed shall be at the minimum setting. The specified standard temperature conditions shall be maintained within 1 K. After reaching the specified temperature conditions, the
18、unit shall be operated continuously for a period of four hours. NOTE Visual check can be documented by suitable instruments (e.g. pictures). 8.4 Condensate disposal test Checks shall be made to ascertain whether there is constant disposal of condensed water and no water is dripping from or being blo
19、wn off the fan coil unit. For the condensate disposal test, the grilles, dampers, etc., shall be set to allow for the maximum cooling power. The fan speed shall be at the minimum setting. DIN EN 1397:2015-11 EN 1397:2015 (E) 18 The specified standard temperature conditions shall be maintained within
20、 1 K. After reaching the specified temperature conditions, the unit shall be operated continuously for a period of four hours. NOTE Visual check can be documented by suitable instruments (e.g. pictures). 9 Test report 9.1 General information The test report shall at least contain: a) date; b) test i
21、nstitute; c) test location; d) test supervisor; e) test object designation; 1) type; 2) serial number; 3) name of the manufacturer; f) reference to this European Standard. 9.2 Additional information Additional information given on the rating plate shall be noted and any other information relevant to
22、 the tests. 9.3 Test results Test results shall include: type of configuration of the unit, according to Annex A; settings of the unit : wiring or control signal for fan speed setting, position of dampers and flaps, etc.; standard and application rating conditions, and all relevant data according to
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DINEN13972015HEATEXCHANGERSHYDRONICROOMFANCOILUNITSTESTPROCEDURESFORESTABLISHINGTHEPERFORMANCEGERMANVERSIONEN13972015

链接地址:http://www.mydoc123.com/p-666824.html