1、Designation: F 710 05Standard Practice forPreparing Concrete Floors to Receive Resilient Flooring1This standard is issued under the fixed designation F 710; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision.
2、 A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the determination of the acceptabil-ity of a concrete floor for the installation of resilient flooring.1.2 Thi
3、s practice includes suggestions for the constructionof a concrete floor to ensure its acceptability for installation ofresilient flooring.1.3 This practice does not cover the adequacy of theconcrete floor to perform its structural requirements.1.4 This practice covers the necessary preparation of co
4、n-crete floors prior to the installation of resilient flooring.1.5 This practice does not supersede in any manner theresilient flooring or adhesive manufacturers written instruc-tions. Consult the individual manufacturer for specific recom-mendations.1.6 This standard does not purport to address all
5、 of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. See 5.1, 7.1.1, and7.1.2 for specific warning statements.1.7 Th
6、e values stated in inch-pound units are to be regardedas standard. The values in parentheses are mathematicalconversions to SI units and are provided for information only.2. Referenced Documents2.1 ASTM Standards:2C 109/C 109M Test Method for Compressive Strength ofHydraulic Cement MortarsC 309 Spec
7、ification for Liquid Membrane-Forming Com-pounds for Curing ConcreteC 472 Test Method for Compressive Strength of GypsumCementD 4259 Practice for Abrading ConcreteE 1155 Test Method for Determining FF/FL (Floor Flatnessand Floor Levelness)E 1486 Test Method for Determining Floor Tolerances Us-ing Wa
8、viness, Wheel Path, and Levelness CriteriaE 1745 Specification for Plastic Water Vapor RetardersUsed In Contact With Soil or Granular Fill Under ConcreteSlabsF 141 Terminology Relating to Resilient Floor CoveringsF 1869 Test Method for Measuring Moisture Vapor Emis-sion Rate of Concrete Subfloor Usi
9、ng Anhydrous CalciumChlorideF 2170 Test Method for Determining Relative Humidity inConcrete Floor Slabs Using In Situ ProbesNOTE 1Specifications and test methods for cements and other relatedmaterials are found in ASTM Volume 04.01. Specifications and testmethods for concretes and related materials
10、are found in ASTM Volume04.02.2.2 ACI Guides:3302.1R Guide for Concrete Floor and Slab Construction117R Standard Tolerances for Concrete Construction andMaterials2.3 Resilient Floor Covering Institute (RFCI):4Recommended Work Practices for the Removal of ResilientFloor Coverings2.4 Other Standards:M
11、ASTERSPEC Guide Spec Section 03300, “Cast-In-Place Concrete”5SPECTEXT Guide Spec Section 03346, “Concrete FloorFinishing”63. Terminology3.1 Definitions For definitions of terms used in thispractice, see Terminology F 141.4. General Guidelines4.1 Concrete floors to receive resilient flooring shall be
12、permanently dry, clean, smooth, and structurally sound. Theyshall be free of dust, solvent, paint, wax, oil, grease, residual1This practice is under the jurisdiction of ASTM Committee F06 on ResilientFloor Coverings and is the direct responsibility of Subcommittee F06.40 onPractices.Current edition
13、approved Feb. 1, 2005. Published March 2005. Originallyapproved in 1981. Last previous edition approved in 2003 as F 710 03.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, r
14、efer to the standards Document Summary page onthe ASTM website.3Available from American Concrete Institute, 19150 Redford Station, Detroit,MI 48219.4Resilient Floor Covering Institute, 966 Hungerford Drive, Rockville, MD20850.5Available from MASTERSPEC, AIA Master Systems, King Street Station, 225Re
15、inekers Lane, Suite 215, Alexandria, VA 22314-2875.6Available from SPECTEXT, National Institute of Building Sciences, 1090Vermont Avenue, NW, Suite 700, Washington, DC 20005-4905.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.adhesi
16、ve, adhesive removers, curing, sealing, hardening, orparting compounds, alkaline salts, excessive carbonation orlaitence, mold, mildew, and other foreign materials that mightprevent adhesive bond.4.2 Surface cracks, grooves, depressions, control joints orother non-moving joints, and other irregulari
17、ties shall be filledor smoothed with latex patching or underlayment compoundrecommended by the resilient flooring manufacturer for fillingor smoothing, or both. Patching or underlayment compoundshall be moisture-, mildew-, and alkali-resistant, and, forcommercial installations, shall provide a minim
18、um of 3000 psicompressive strength after 28 days, when tested in accordancewith Test Method C 109 or Test Method C 472, whichever isappropriate.4.2.1 Joints such as expansion joints, isolation joints, orother moving joints in concrete slabs shall not be filled withpatching compound or covered with r
19、esilient flooring. Consultthe resilient flooring manufacturer regarding the use of anexpansion joint covering system.4.3 The surface of the floor shall be cleaned of all loosematerial by scraping, brushing, vacuuming, or other methods,or a combination thereof, as recommended by the resilientflooring
20、 manufacturer, immediately before commencing instal-lation of resilient flooring.4.4 Many resilient floorings may not be installed overconcrete when residual asphalt adhesive residue is present.Consult the resilient flooring manufacturers written recom-mendations concerning use of resilient flooring
21、 products inthese situations.4.5 Concrete floors shall be smooth to prevent irregularities,roughness, or other defects from telegraphing through the newresilient flooring. The surface of concrete floors shall be flat towithin the equivalent of316 in. (3.9 mm) in 10 ft, as describedin ACI 117R, or as
22、 measured by the method described in TestMethod E 1155 or any industry-recognized method specified.See X1.7 for more information regarding flatness measurementmethods.5. Testing Procedures5.1 Concrete floors to receive resilient flooring shall be freeof sealers, coatings, finishes, dirt, film-formin
23、g curing com-pounds, or other substances which may affect the rate ofmoisture dissipation from the concrete or the adhesion ofresilient flooring to the concrete. Non-chemical methods forremoval, such as abrasive cleaning or bead-blasting, includingmethods described in Practice D 4259 may be used on
24、existingslabs with deleterious residues to achieve an appropriate statefor testing. Cleaning shall take place a minimum of 24 h beforetesting. WarningHydraulic cement used in concrete con-struction may contain trace amounts of free crystalline silica.Prolonged exposure to airborne free crystalline s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF7102005STANDARDPRACTICEFORPREPARINGCONCRETEFLOORSTORECEIVERESILIENTFLOORING 弹性 地板 铺设 混凝土 楼板 准备 标准

链接地址:http://www.mydoc123.com/p-537133.html