ASTM D4388-2013 Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes《非金属半导电性及电绝缘橡胶带的标准规格》.pdf
《ASTM D4388-2013 Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes《非金属半导电性及电绝缘橡胶带的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM D4388-2013 Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes《非金属半导电性及电绝缘橡胶带的标准规格》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D4388 13 An American National StandardStandard Specification forNonmetallic Semi-Conducting and Electrically InsulatingRubber Tapes1This standard is issued under the fixed designation D4388; the number immediately following the designation indicates the year oforiginal adoption or, in t
2、he case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope*1.
3、1 This specification covers nonmetallic semi-conductingand electrical insulating tapes designed for the splicing andrepair of electrical wire and cables operating at voltages up to325 kV, phase to phase.1.2 The SI values are the standard. The values stated ininch-pound units given in parentheses are
4、 for informationpurposes only.2. Referenced Documents2.1 ASTM Standards:2D1711 Terminology Relating to Electrical InsulationD4325 Test Methods for Nonmetallic Semi-Conducting andElectrically Insulating Rubber Tapes3. Terminology3.1 DefinitionsUse Terminology D1711 for definitions ofterms used in the
5、se test methods and associated with electricalor electronic insulation materials.4. Classification4.1 Types:4.1.1 Type IAlow voltage rubber insulating tape designedfor use on wires and cables operating up to 2000 V phase tophase in dry locations with conductor temperatures up to 80 C(176 F) for cont
6、inuous operation, up to 95 C (203 F) foremergency overload conditions, and up to 150 C (302 F) forshort-circuit conditions. For outdoor use, protect the tape fromozone attack and ultraviolet radiation by the use of a suitableoverwrap. Apply the tape to the wire or cable within anambient temperature
7、range of 10 and 40 C (14 and 104 F).4.1.2 Type IIA medium voltage, ozone-resistant, rubberinsulating tape designed for use with wires and cables operat-ing up to 35 000 V phase to phase in either wet or drylocations with conductor temperatures up to 90 C (194 F) forcontinuous operation, up to 130 C
8、(266 F) for emergencyoverload conditions, and up to 250 C (482 F) for short-circuitconditions when installed in accordance with the manufactur-ers instruction. For wet or dry outdoor use, protect the tapefrom ultraviolet radiation by the use of a suitable overwrap.Apply the tape to the wire or cable
9、 within an ambienttemperature range of 10 and 40 C (14 and 104 F).4.1.3 Type IIIA high voltage, ozone-resistant, rubber in-sulating tape designed for use with wires and cables operatingup to 138 000 V phase to phase in either wet or dry locationswith conductor temperatures up to 90 C (194 F) for con
10、tinu-ous operation, up to 130 C (266 F) for emergency overloadconditions, and up to 250 C (482 F) for short-circuitconditions when installed in accordance with the manufactur-ers instructions. This tape is suitable for wet or dry outdooruse. Apply the tape to the wire or cable within an ambienttempe
11、rature range of 10 and 40 C (14 and 104 F).4.1.4 Type IVA nonmetallic semi-conducting tape de-signed for shielding various portions of joints and terminationsin electrical wires and cables operating at any voltage underwet or dry conditions with conductor temperatures up to 90 C(194 F) for continuou
12、s operation, or up to 130 C (266 F) foremergency overload conditions. This tape is suitable for wet ordry outdoor use. Apply the tape to the wire or cable within anambient temperature range of 10 and 40 C (14 and 104 F).4.1.5 Type VA higher voltage, ozone-resistant, rubberinsulating tape designed fo
13、r use with wires and cables operat-ing up to 325 000 V phase to phase in either wet or drylocations with conductor temperatures up to 90 C (194 F) forcontinuous operation, up to 130 C (266 F) for emergencyoverload, and up to 250 C (482 F) short-circuit conditionswhen installed in accordance with the
14、 manufacturers instruc-tions. This tape is suitable for wet or dry outdoor use.Apply the1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D09.07 on Flexible and Rigid Insulating Materia
15、ls.Current edition approved Nov. 1, 2013. Published December 2013. Originallyapproved in 1984. Last previous edition approved in 2008 as D4388 08. DOI:10.1520/D4388-13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual
16、 Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1tape to the wi
17、re or cable within an ambient temperature of 10and 40 C (14 and 104 F).5. Physical Properties5.1 The tape shall consist of a non-crosslinked or partiallycrosslinked rubber nonmetallic semi-conducting or insulatingcompound. The compound shall be well, evenly, and smoothlyprocessed, cut to the specifi
18、ed widths, and tightly wound inrolls with a separator between layers. Where a non-removableseparator is used, the separator will be considered an integralpart of the tape.5.2 The separator shall be parchment paper, glazed orplastic sheeting, or any suitable material interposed betweenadjacent layers
19、. The removable or non-removable separatorshall not interfere with the use of the roll during application.Where a removable separator is used, the separator shall bereadily removable from the rubber insulation without tearing ordamaging the tape insulation. The outside end of the roll shallbe secure
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD43882013STANDARDSPECIFICATIONFORNONMETALLICSEMICONDUCTINGANDELECTRICALLYINSULATINGRUBBERTAPES 非金属

链接地址:http://www.mydoc123.com/p-516940.html