《ASTM D4245-2008 Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable 90&176C Dry 75&176C Wet Operation《工作温度为90℃干 75℃湿的电线和电缆的耐臭氧热塑性合成橡胶绝缘.pdf》由会员分享,可在线阅读,更多相关《ASTM D4245-2008 Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable 90&176C Dry 75&176C Wet Operation《工作温度为90℃干 75℃湿的电线和电缆的耐臭氧热塑性合成橡胶绝缘.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 4245 08An American National StandardStandard Specification forOzone-Resistant Thermoplastic Elastomer Insulation ForWire and Cable, 90 C Dry/75 C Wet Operation1This standard is issued under the fixed designation D 4245; the number immediately following the designation indicates the ye
2、ar oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification covers an ozone-resistant insulati
3、ngcompound for electrical wire and cables 14 AWG and larger.This compound consists substantially of a thermoplastic elas-tomer.1.2 This type of insulation is suitable for continuous opera-tion at conductor temperatures not exceeding 90 C in drylocations and 75 C in wet locations. Operating voltages
4、arenot to exceed 2000 V. The minimum installation temperatureis 40 C.1.3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 In many inst
5、ances the insulation material cannot betested unless it has been formed around a conductor or cable.Therefore, tests are done on insulated wire or cable in thisdocument solely to determine the relevant property of theinsulation material and not to test the conductor or completedcable.2. Referenced D
6、ocuments2.1 ASTM Standards:2D 470 Test Methods for Crosslinked Insulations and Jacketsfor Wire and CableD 1711 Terminology Relating to Electrical InsulationD 2633 Test Methods for Thermoplastic Insulations andJackets for Wire and Cable3. Terminology3.1 Definitions: For definitions of terms used in t
7、his speci-fication refer to Terminology D 1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging, nexposure of materials to air at 121 C for168 h.4. Physical Properties4.1 Requirements for physical properties are listed in Table1.4.2 Thickness of InsulationTable 1A (Conductor Sizes,Insu
8、lation Thicknesses, and AC Test Voltages for RubberInsulations) of Test Methods D 470 lists the minimum averagethickness for the insulation. The required minimum thicknessis 90 % of the specified average thickness.5. Electrical Requirements5.1 Order of TestingPerform the ac voltage withstand test,in
9、sulation resistance, and dc voltage withstand test in that orderwhen any of these tests are specified. The sequence of othertesting is not specified.5.2 AC Voltage Withstand TestUnless otherwise specified,omit this test if the dc voltage withstand test described in 5.4 isto be performed. Test each i
10、nsulated conductor for 5 min at theac withstand voltage given in Table 1A (Conductor Sizes,Insulation Thicknesses, and AC Test Voltages for RubberInsulations) of Test Methods D 470 under the columns labeled“Ozone-Resisting Insulation.”5.3 Insulation Resistance5.3.1 The insulated conductor shall have
11、 an insulationresistance value of at least that corresponding to a constant of10 000 at 60 F (15.6 C).5.3.2 If the water temperature at the time measurement wasmade differs from 60 F (15.6 C), correct the insulationresistance to 60 F. Table 2, (Temperature Correction Factorsfor Insulation Resistance
12、 at 60 F), of Test Methods D 470,contains the correction factors. Use the procedure given in TestMethods D 470 to determine the 1 F coefficient for the1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility
13、 ofSubcommittee D09.18 on Solid Insulations, Non-Metallic Shieldings and Coveringsfor Electrical and Telecommunication Wires and Cables.Current edition approved Nov. 1, 2008. Published December 2008. Originallyapproved in 1983. Last previous edition approved in 2002 as D 4245 02.2For referenced ASTM
14、 standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD42452008STANDARDSPECIFICATIONFOROZONERESISTANTTHERMOPLASTICELASTOMERINSULATIONFORWIREANDCABLE90176CDRY75176CWETOPERATION

链接地址:http://www.mydoc123.com/p-516627.html