1、Designation: C 1283 07Standard Practice forInstalling Clay Flue Lining1This standard is issued under the fixed designation C 1283; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses i
2、ndicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the minimum requirements forinstalling clay flue lining for residential concrete or masonrychimneys.1.2 The values stated in inch-pound
3、units are to be regardedas the standard. The values stated in parentheses are forinformational purposes only.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety
4、 and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C24 Test Method for Pyrometric Cone Equivalent (PCE) ofFireclay and High Alumina Refractory MaterialsC27 Classification of Fireclay and High-Alumina Refrac-tory Br
5、ickC55 Specification for Concrete Building BrickC90 Specification for Loadbearing Concrete MasonryUnitsC99 Test Method for Modulus of Rupture of DimensionStoneC 129 Specification for Nonloadbearing Concrete MasonryUnitsC 170 Test Method for Compressive Strength of DimensionStoneC 199 Test Method for
6、 Pier Test for Refractory MortarsC 216 Specification for Facing Brick (Solid Masonry UnitsMade from Clay or Shale)C 270 Specification for Mortar for Unit MasonryC 315 Specification for Clay Flue LinersC 652 Specification for Hollow Brick (Hollow MasonryUnits Made From Clay or Shale)C 896 Terminology
7、 Relating to Clay ProductsC 1184 Specification for Structural Silicone Sealants3. Terminology3.1 GeneralTerminology C 896 should be used for clari-fication of definitions in this practice.3.2 Definitions of Terms Specific to This Standard:3.2.1 chimney connectortubular unit or pipe used toconvey pro
8、ducts of combustion from a heating or cookingappliance to the chimney.3.2.2 fluepassageway within a chimney through whichproducts of combustion are conveyed.3.2.3 flue linermanufactured tubular nonloadbearing firedclay unit, normally used for conveying hot gases in chimneys.3.2.4 masonry chimneyvert
9、ical structure constructed ofbrick, concrete, concrete masonry units, or stone, whichcontains one or more flues, and conveys products of combus-tion from a heat source or cooking appliance.3.2.5 smoke chambersection of a fireplace above thethroat and below the flue, which is an area of transition fr
10、omthe shape of the throat to the shape of the flue.3.2.6 thimblemanufactured tubular nonloadbearing firedclay unit normally used to connect the chimney connector froman appliance through the wall of the chimney to the flue.4. Footings and Foundations4.1 Footings for masonry chimneys shall be constru
11、cted ofconcrete or solid masonry at least 12 in. (305 mm) thick, andit shall extend at least 6 in. (150 mm) beyond the face of thefoundation or support wall on all sides. Footings shall befounded below frost depth on natural undisturbed earth orengineered fill. In areas not subjected to freezing, fo
12、otings shallbe founded at least 12 in. (305 mm) below finished grade.4.2 The foundation shall be placed, with respect to adjacentstructures existing or anticipated, to minimize the possibility ofdamage by construction operations or by transmission ofadditional loads to the supporting soils.4.3 Concr
13、ete footings and foundations shall conform tolocal building codes.1This practice is under the jurisdiction of ASTM Committee C04 on VitrifiedClay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods ofTest and Specifications.Current edition approved April 1, 2007. Published April
14、2007. Originallyapproved in 1994. Last previous edition approved in 2006 as C 1283 06.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary
15、 page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.3.1 In the absence of a local building code, concrete witha minimum 28 day compressive strength of 3000 psi (21 MPa)shall be used.4.4 Where a chimney or firep
16、lace is added to the outside ofthe exterior wall of an existing structure, the following shallapply:4.4.1 The new footing shall be installed at the same level orbelow the existing footing, provided the level is below the frostline and the new footing is placed on soil with adequate bearingcapability
17、.4.4.2 The existing drainage provision shall not be ob-structed.5. Chimney Construction5.1 Materials:5.1.1 Flue Linings Specification C 315.5.1.2 Refractory MortarTest Method C24(cone 10) andTest Method C 199 (medium duty).5.1.3 Concrete Block Specification C90or SpecificationC 129.5.1.4 BrickSpecif
18、ication C55 or Specification C 216,Grade SW.5.1.5 MortarSpecification C 270.5.1.6 FirebrickClassification C27.5.1.7 Natural Stone Test Method C 170 or Test MethodC99.5.2 The chimney consists of a flue liner and the chimneywall. When used to vent a fireplace, the chimney is constructeddirectly on the
19、 smoke chamber.5.3 The flue lining shall start from a point not less than 8 in.(205 mm) below the entrance of the lowest chimney connector.5.4 Flue liners shall be installed, each flue liner carefullybedded on the previous one, using refractory mortar. All jointsof flue liners shall be116 in. (1.6 m
20、m) to18 in. (3.2 mm) thick,and struck flush so as to produce a straight, smooth, fullyaligned flue. Liners shall be placed in such a manner as tominimize ledges or steps within the flue passageway.5.5 Flue liners shall be surrounded by masonry on all sidesbut shall not be bonded to the surrounding m
21、asonry. The flueliner shall contact the chimney wall only as necessary forsupport and alignment in order to permit the flue liner toexpand and contract freely. The separation of the flue linerfrom the surrounding concrete or masonry shall not exceed thewall thickness of the flue liner. Where seismic
22、 reinforcingrequires the space between the flue liner and the chimney wallto be grouted solid, the flue shall be wrapped with ceramic fiberpaper capable of withstanding temperatures of 2100F toprevent the flue liner from bonding to the chimney walls.5.6 The flue lining shall extend the entire height
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC12832007STANDARDPRACTICEFORINSTALLINGCLAYFLUELINING 安装 粘土 烟道 衬里 标准 实施 规程 PDF

链接地址:http://www.mydoc123.com/p-464069.html