ASTM C1136-2009 Standard Specification for Flexible Low Permeance Vapor Retarders for Thermal Insulation《隔热用柔性、低渗透蒸气阻化剂的标准规范》.pdf
《ASTM C1136-2009 Standard Specification for Flexible Low Permeance Vapor Retarders for Thermal Insulation《隔热用柔性、低渗透蒸气阻化剂的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1136-2009 Standard Specification for Flexible Low Permeance Vapor Retarders for Thermal Insulation《隔热用柔性、低渗透蒸气阻化剂的标准规范》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1136 09Standard Specification forFlexible, Low Permeance Vapor Retarders for ThermalInsulation1This standard is issued under the fixed designation C1136; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of las
2、t revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers vapor retarder
3、s for thermalinsulation, specifically, flexible materials with permeance of0.10 perm or lower and surface burning characteristics of 25flame spread/50 smoke or lower. These materials are intendedfor use at surface temperatures of 20 to 150F (29 to 66C).It does not cover mastics or barrier coatings a
4、pplied in liquidform, nor materials intended for use as weather barriers.1.2 This is a material specification and does not imply thatan installed system using these materials will provide thephysical properties specified in Section 6.1.3 This specification provides physical requirements forvapor ret
5、arders. Practice C755 provides assistance in solvingproblems related to moisture vapor transmission through ther-mal insulation materials.1.4 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided
6、 for information onlyand are not considered standard.1.5 The following precautionary caveat pertains to the testmethods portion only, Section 10, of this specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of th
7、e userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC755 Practice for Selection of Water Vapor Retarders forThermal
8、 InsulationD774/D774M Test Method for Bursting Strength of PaperC1258 Test Method for Elevated Temperature and Humid-ity Resistance of Vapor Retarders for InsulationC1263 Test Method for Thermal Integrity of Flexible WaterVapor RetardersC1338 Test Method for Determining Fungi Resistance ofInsulation
9、 Materials and FacingsD828 Test Method for Tensile Properties of Paper andPaperboard Using Constant-Rate-of-Elongation Appara-tus3D882 Test Method for Tensile Properties of Thin PlasticSheetingD1204 Test Method for Linear Dimensional Changes ofNonrigid Thermoplastic Sheeting or Film at ElevatedTempe
10、ratureE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE96/E96M Test Methods for Water Vapor Transmission ofMaterials2.2 TAPPI Standards:T461 Flame Resistance of Treated Paper and Paperboard3. Terminology3.1 DefinitionsDefinitions in Terminology C168 apply toterms used in this
11、 specification.4. Classification4.1 Classification of vapor retarders is based on vaporretardance and strength properties, as listed in Table 1.5. Materials and Manufacture5.1 It is possible to construct vapor retarders from anynumber of various films, foils, cloths, papers, and reinforce-ments, alo
12、ne or in combination, to achieve required perfor-mance.1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.33 onInsulation Finishes and Moisture.Current edition approved Nov. 1, 2009. Published December 2009. O
13、riginallyapproved in 1990. Last previous edition approved in 2008 as C113608. DOI:10.1520/C1136-09.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Doc
14、ument Summary page onthe ASTM website.3Withdrawn. The last approved version of this historical standard is referencedon www.astm.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.6. Physical Properties6.1 Maximum permeance for a sp
15、ecific type vapor retardershall be as shown in Table 1 when tested in accordance with10.1.6.2 All vapor retarders shall demonstrate a flame spread of25 or less and smoke developed of 50 or less when testing thefinish side (the side opposite that contacting the insulation) inaccordance with 10.2.6.3
16、Minimum tensile strength for a specific type vaporretarder shall be as shown in Table 1 when tested in accordancewith 10.3.6.4 Maximum dimensional change for a specific type vaporretarder shall be as shown in Table 1, when tested in accor-dance with 10.4.6.5 All type vapor retarders shall not sustai
17、n growth of fungiwhen tested in accordance with 10.5.6.6 All type vapor retarders shall not crack or delaminate attemperatures from 20 to 150F (29 to 66C) when tested inaccordance with 10.6.6.7 Minimum burst strength for a specific type vaporretarder shall be as shown in Table 1 when tested in accor
18、dancewith 10.7.6.8 Vapor retarders containing paper or paper products shallnot demonstrate an increase in char length of more than 20 %when tested in accordance with 10.8.6.9 All type vapor retarders shall not corrode or delaminate,nor demonstrate, after exposure, a permeance greater than themaximum
19、 allowable for the type being tested, when tested inaccordance with 10.9.7. Dimensions, Mass, and Permissible Variations7.1 Dimensions for roll or sheeted materials shall be asspecified by the purchaser.7.2 Tolerance for roll materials shall be 618 in. (63 mm) onwidth and +5, 0 % on length.7.3 Toler
20、ance for sheeted materials shall be 618 in. (63mm) on length and width.8. Workmanship, Finish and Appearance8.1 There shall be no defects in materials or workmanshipthat will affect the required performance of the vapor retarder.8.2 There shall be no defects that adversely affect theappearance of th
21、e vapor retarder.8.3 There shall be no defects that would affect ability of userto process material.9. Significance and Use9.1 Entrapment of water in thermal insulation caused bycondensation of water vapor that has penetrated into theinsulation is detrimental to the thermal resistance of theinsulati
22、on. For this reason, in certain installations wheretemperature and moisture conditions have the potential tocreate a vapor driving force toward the insulation, a deterrentto the passage of such vapor into the installed insulation needsto be provided. This is the primary function of the vaporretarder
23、.9.2 In addition to the function stated in 9.1, a vapor retarderhas the potential to provide physical protection and addedstrength to the insulation system.9.3 This specification is used to specify material by physicalproperty requirements that address the above prerequisites. Thedesigner of an insu
24、lation system, after determining the degreeof protection needed for the insulation, can use this specifica-tion to specify the appropriate type of vapor retarder when oneis required.10. Test Methods10.1 Water Vapor PermeanceTest water vapor permeancein accordance with Test Methods E96/E96M, Procedur
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC11362009STANDARDSPECIFICATIONFORFLEXIBLELOWPERMEANCEVAPORRETARDERSFORTHERMALINSULATION 隔热 柔性 渗透

链接地址:http://www.mydoc123.com/p-463498.html