ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 27-2012 AIR-HEATING COILS.pdf
《ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 27-2012 AIR-HEATING COILS.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 27-2012 AIR-HEATING COILS.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、27.1CHAPTER 27AIR-HEATING COILSCoil Construction and Design. 27.1Coil Selection 27.3Installation Guidelines 27.4Coil Maintenance 27.5IR-HEATING coils are used to heat air under forced con-Avection. The total coil surface may consist of a single coilsection or several coil sections assembled into a b
2、ank. The coilsdescribed in this chapter apply primarily to comfort heating and airconditioning using steam, hot water, refrigerant vapor heat reclaim(including heat pumps), and electricity. The choice between thevarious methods of heating depends greatly on the cost of the vari-ous available energy
3、sources. For instance, in areas where electricpower is cheaply available and heating requirements are limited,heat pumps are a very viable option. With available power andhigher heat requirements, electric heat is used. If electric power isconsiderably expensive, steam or hot water generated using g
4、as-fired sources is used in larger buildings and district cooling. Insmaller buildings, heat is supplied using gas furnaces, which arecovered in Chapters 33 and 34. Water and steam heating are alsowidely used where process waste heat is available.COIL CONSTRUCTION AND DESIGNExtended-surface coils co
5、nsist of a primary and a secondaryheat-transfer surface. The primary surface is the external surface ofthe tubes, generally consisting of rows of round tubes or pipes thatmay be staggered or parallel (in-line) with respect to the airflow.Flattened tubes or tubes with other nonround internal passagew
6、aysare sometimes used. The inside of the tube is usually smooth andplain, but some coil designs feature various forms of internal fins orturbulence promoters (either fabricated and then inserted, or ex-truded) to enhance fluid coil performance. The secondary surface isthe fins external surface, whic
7、h consists of thin metal plates or a spi-ral ribbon uniformly spaced or wound along the length of the primarysurface. The intimate contact with the primary surface provides goodheat transfer. Air-heating fluid and steam coils are generally availablewith different circuit arrangements and combination
8、s that offer vary-ing numbers of parallel water flow passes in the tube core.Copper and aluminum are the materials most commonly used forextended-surface coils. Tubing made of steel or various copperalloys is used in applications where corrosive forces might attackthe coils from inside or outside. T
9、he most common combination forlow-pressure applications is aluminum fins on copper tubes. Low-pressure steam coils are usually designed to operate up to 50 psig.Higher-strength tube materials such as red brass, admiralty brass, orcupronickel assembled by brazed construction are usable up to366F wate
10、r or 150 psig saturated steam. Higher operating condi-tions call for electric welded stainless steel construction, designedto meet Section II and Section VIII requirements of the ASMEBoiler and Pressure Vessel Code.Customarily, the coil casing consists of a top and bottom channel(also known as baffl
11、es or side sheets), two end supports (also knownas end plates or tube sheets), and, on longer coils, intermediate sup-ports (also known as center supports or tube sheets). Designs vary,but most are mounted on ducts or built-up systems. Most often,casing material is spangled zinc-coated (galvanized)
12、steel with aminimum coating designation of G90-U. Some corrosive air condi-tions may require stainless steel casings or corrosive-resistant coat-ing, such as a baked phenolic applied by the manufacturer to theentire coil surface. Steam coil casings should be designed to accom-modate thermal expansio
13、n of the tube core during operation (a float-ing core arrangement).Common core tube diameters vary from 5/16 up to 1 in. outsidediameter (OD) and fin spacings from 4 to 18 fins per inch. Fluidheating coils have a tube spacing from 3/4 to 1 3/4 in. and tube diam-eters from 5/16 to 5/8 in. OD. Steam c
14、oils have tube spacing from1 1/4 to 3 in. and tube diameters from 0.5 to 1 in. OD. The mostcommon arrangements are one- or two-row steam coils and two- tofour-row hot-water coils. Fins should be spaced according to theapplication requirements, with particular attention given to anysevere duty condit
15、ions, such as inlet temperatures and contaminantsin the airstream.Tube wall thickness and the required use of alloys other than(standard) copper are determined primarily by the coils specifiedmaximum allowable working pressure (MAWP) requirements. Asecondary consideration is expected coil service li
16、fe. Fin type,header, and connection construction also play a large part in thisdetermination. All applicable local job site codes and nationalsafety standards should be followed in the design and application ofheating coils.Flow direction can strongly affect heat transfer surface perfor-mance. In ai
17、r-heating coils with only one row of tubes, the air flowsat right angles to the heating medium. Such a cross-flow arrange-ment is common in steam heating coils. The steam temperature inthe tubes remains uniform, and the mean temperature difference isthe same regardless of the direction of flow relat
18、ive to the air. Thesteam supply connection is located either in the center or at the topof the inlet header. The steam condensate outlet (return connection)is always at the lowest point in the return header. When coils have two or more tube rows in the direction of airflow,such as hot-water coils, t
19、he heating medium in the tubes may be cir-cuited in various parallel-flow and counterflow arrangements. Coun-terflow is the arrangement most preferred to obtain the highestpossible mean temperature difference, which determines the heattransfer of the coil. The greater this temperature difference, th
20、egreater the coils heat transfer capacity. In multirow coils circuitedfor counterflow, water enters the tube row on the leaving air side ofthe coil.Steam CoilsSteam coils are generally classified, similarly to boilers, by oper-ating pressure: low (15 psi) or high (15 psi). However, variousorganizati
21、ons use other pressure classification schemes with differingdivisions e.g., low (15 psi), medium (15 to 100 psi), or high(100 psi). Steam coils can also be categorized by operating limits ofthe tube materials:Standard steam 150 psi 366F copper tubeHigh-pressure 236 psi 400F special materialsteam e.g
22、., cupronickel (CuNi)The preparation of this chapter is assigned to TC 8.4, Air-to-RefrigerantHeat Transfer Equipment.27.2 2012 ASHRAE HandbookHVAC Systems and Equipment Although these operating conditions are allowed by code, longexposures to them will shorten coil tube life. Leaks are less likelyw
23、hen the coil tube core has thicker walls of higher-strength materi-als. Operational experience suggests preferred limits for continuous-duty steam coils (tube OD ranging from 5/8 to 1 in.) in commercialand institutional applications, as shown in Table 1.Steam coils also can be categorized by type as
24、 basic steam,steam-distributing, or face-and-bypass.Basic steam coils generally have smooth tubes with fins on theair side. The steam supply connection is at one end and the tubes arepitched toward the condensate return, which is usually at the oppo-site end. For horizontal airflow, the tubes can be
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACSYSTEMSANDEQUIPMENTIPCH272012AIRHEATINGCOILSPDF

链接地址:http://www.mydoc123.com/p-455051.html