ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf
《ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf》由会员分享,可在线阅读,更多相关《ASHRAE 170 INT 2-2014 Ventilation of Health Care Facilities.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、 Page 1 of 3 2014 ASHRAE. All Rights reserved. Interpretation IC 170-2013-2 of ANSI/ASHRAE/ASHE Standard 170-2013 Ventilation of Health Care Facilities Date Approved: July 1, 2014 Request from: Travis English (Travis.R.Englishkp.org), Kaiser Permanente, 1800 Harrision Street, Oakland, CA 94612. Refe
2、rence: This request for interpretation refers to the requirements in ANSI/ASHRAE/ASHE Standard 170-2013, Section 7.1.a.2, regarding providing for comfort. Background: Standard 170 (S170) 7.1.a.2 states that the criteria in Table 7.1 are intended to “provide for comfort”. In ASHRAEs standards, comfor
3、t is also covered by ASHRAE Standard 55- Thermal Comfort for Human Occupancy (S55). The methodologies of the two are notably different. S70 prescribes air temperature, air flow, and relative humidity ranges. S55 predicts comfort by using multiple variables (including but not limited to air temperate
4、, speed and humidity) and comparing combinations of variables to known human comfort responses. Using the S55 methodology: For typical occupant types, assuming compliant air speed and a zero degree difference between radiant and air temperatures, the nominal temperature ranges for S55 compliance are
5、 shown in the table and figure below. Occupant Type Clo Met Op T. Max RH PMV PPD Gowned Healthcare Workers 1.4 1.4 59.9 20 -0.50 10.16 Gowned Healthcare Workers 1.4 1.4 58.3 60-0.50 10.22 Gowned Healthcare Workers 1.4 1.4 71.7 20 0.50 10.22 Gowned Healthcare Workers 1.4 1.4 69.4 600.50 10.22 Healthc
6、are workers 0.5 1.4 73.7 2 -0.50 10.25 Healthcare workers 0.5 1.4 71.5 60 -0.50 10.21 Healthcare workers 0.5 1.4 80.8 2 0.49 10.06 Healthcare workers 0.5 1.4 78.1 60 0.49 10.06 Healthcare workers 1 1.4 66.4 2 -0.50 10.23 Healthcare workers 1 1.4 64.1 60 -0.50 10.17 Healthcare workers 1 1.4 76.4 2 0.
7、50 10.28 Healthcare workers 1 1.4 73.2 60 0.50 10.26 Patients 0.31 0.7 85.7 2 -0.47 9.64 Patients 0.31 0.7 83.3 60 -0.50 10.22 Patients 0.31 0.7 88.4 2 0.50 10.23 Patients 0.31 0.7 85.9 60 0.50 10.23 Workers, patients, or guests 0.5 1 79.6 2 -0.50 10.22 Workers, patients, or guests 0.5 1 77.2 60 -0.
8、50 10.22 Workers, patients, or guests 0.5 1 84.5 2 0.50 10.22 Workers, patients, or guests 0.5 1 81.7 60 0.50 10.22 Workers, patients, or guests 1 1 74.2 2 -0.50 10.22 Workers, patients, or 1 1 71.4 60 -0.50 10.22 Interpretation IC 170-2013-X Page 2 of 3 2014 ASHRAE. All Rights reserved. Classified
9、- Internal use Occupant Type Clo Met Op T. Max RH PMV PPD guests Workers, patients, or guests 1 1 81.0 2 0.50 10.22 Workers, patients, or guests 1 1 77.6 60 0.50 10.22 Table 1: S55 Temperature and Humidity Ranges yielding -0.50.5 Fig. 1: S55 Temperature and Humidity Ranges yielding -0.50.5 Using the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAE170INT22014VENTILATIONOFHEALTHCAREFACILITIESPDF

链接地址:http://www.mydoc123.com/p-454201.html