1、01-11 23 38 13 - 1 SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between / _ / if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber the paragraphs. 3. Select grease-extracting ventilators according to usage req
2、uirements and codes. PART 1 - GENERAL 1.1 DESCRIPTION This section specifies food service, grease-extracting, energy saving, exhaust ventilators. 1.2 DEFINATIONS A. Ventilator, kitchen hood, hood and canopy; for purposes of this specification section, these terms all have the same definition. B. UL
3、Listed grease extractor: a slotted (not mesh) type grease extractor that has been tested and rated by Underwriters Laboratories. C. Eyebrow, compensating, short circuit, short cycle types are not allowed. 1.3 RELATED WORK A. Section 05 50 00, METAL FABRICATIONS: Supports for Ventilators. B. Section
4、11 44 00, FOOD COOKING EQUIPMENT: Cooking Equipment. C. Section 11 40 21, FOOD SERVICE EQUIPMENT-UTILITY DISTRIBUTION SYSTEM: Utility Distribution Systems. SPEC WRITER NOTE: Retain first paragraph below if required for project location. D. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STR
5、UCTURAL COMPONENTS: Seismic Restraint of Equipment. E. Section 22 11 00, FACILITY WATER DISTRIBUTION: Plumbing Connections. F. Section 21 10 00, WATER-BASED FIRE-SUPPRESSION SYSTEMS: / Section 21 13 13, WET-PIPE SPRINKLER SYSTEMS: / Building Fire-Protection System. G. Section 23 34 00, HVAC FANS: Up
6、-blast kitchen hood exhaust fans. /H. Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC: Remote monitoring of the kitchen ventilation system./ I. Section 26 05 21, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW): Electrical Connections. Provided by IHSNot for ResaleNo
7、 reproduction or networking permitted without license from IHS01-11 23 38 13 - 2 1.4 QUALITY CONTROL A. Installer Qualifications: Experienced in food service equipment installation or supervised by an experienced food service equipment installer. 1. Where required to complete equipment installation,
8、 electrician and plumber shall be licensed in jurisdiction where project is located. B. NSF Compliance: Equipment bears NSF Certification Mark or UL Classification Mark indicating compliance with applicable NSF standards, including NSF/ANSI 2, NSF 2-Supplement, and NSF/ANSI 4. C. UL Listing: Equipme
9、nt has been evaluated according to UL 710, is listed in UL “Heating, Cooling, Ventilating and Cooking Equipment Directory,“ and is labeled for intended use. D. Fire-Protection Systems: Comply with NFPA 96 and NFPA 17A. E. Welding: Perform welding according to AWS D9.1M/D9.1. SPEC WRITER NOTE: Retain
10、 paragraph and subparagraphs below if required for project location. F. Seismic Restraint: 1. Comply with requirements in Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. 2. Comply with applicable guidelines for seismic restraint of kitchen equipment contained in SMACN
11、As “Kitchen Ventilation Systems and Food Service Equipment Guidelines,“ Appendix A. G. In-Use Service: At least one factory-authorized service agency for equipment shall be located in the geographical area of the installation and shall have the ability to provide service within 24 hours after receiv
12、ing a service call. 1.5 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Include manufacturers address and telephone number. 2. Include catalog or model numbers, and illustrations and descriptions of ventilat
13、ors and accessories. C. Installation Drawings: Show dimensions; method of assembly; and details of installation, adjoining construction, coordination with service utilities, and other work required for a complete installation. D. Field Test Reports: Indicate dates and times of tests and certify test
14、 results. Provided by IHSNot for Resale-,-,-01-11 23 38 13 - 3 E. Operating Instructions: Include operating instructions covering operation of all components and maintenance procedures covering proper cleaning and necessary lubrication or adjustments to controls. SPEC WRITER NOTE: Edit the following
15、 requirements to coordinate with LEED certification goals. F. LEED Information: 1. LEED (v 3.0) MR Credit 4, Recycled Content: Product data indicating percentages, by weight of post-consumer and post-industrial recycled content for products having recycled content: a. Include statement indicating co
16、sts for each product having recycled content. 2. LEED (v 3.0) MR Credit 5, Regional Materials: Manufacturers data identifying point of origin for products procured within 500 mile radius of the project: a. Include statement indicating costs for each product submitted. 1.6 WARRANTY A. Warrant food se
17、rvice equipment to be free from defects in materials and workmanship in accordance with requirements of “Warranty of Construction“ article in FAR clause 52.246-21. 1.7 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publication
18、s are referenced in the text by the basic designation only. B. American Welding Society (AWS): D9.1M/D9.1-2006.Sheet Metal Welding Code C. ASTM International (ASTM): A666-03.Standard Specification for Annealed or Cold-Worked Austenitic Stainless Steel Sheet, Strip, Plate, and Flat Bar D. National As
19、sociation of Architectural Metal Manufacturers (NAAMM): AMP500-06.Metal Finishes Manual for Architectural and Metal Products, 2006 E. NFPA International (NFPA): #96-2008Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations F. NSF International/American National Standa
20、rds Institute (NSF/ANSI): Standard #2-2009Food Service Equipment Provided by IHSNot for Resale-,-,-01-11 23 38 13 - 4 Standard #4-2009Commercial Cooking, Rethermalization, and Powered Hot Food Holding and Transport Equipment G. Sheet Metal and Air Conditioning Contractors National Association (SMACN
21、A): 1767-2001.Kitchen Ventilation Systems and Food Service Equipment Fabrication and Installation Guidelines H. Underwriters Laboratories Inc. (UL): #710-06.Exhaust Hoods for Commercial Cooking Equipment PART 2 PRODUCTS 2.1 EXHAUST HOODS A. The hood shall be constructed of a minimum of 18 gauge, (ty
22、pe 304) stainless steel with a #3 finish. Hood shall be constructed using the standing seam method for optimum strength. The seams on the canopy shall be welded liquidtight, and all exposed external welds shall be ground and polished to match the original finish of the metal. Lighter material gauges
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2338132011COMMERCIALKITCHENHOODSPDF