1、11-09 23 37 00 - 1 SECTION 23 37 00 AIR OUTLETS AND INLETS SPEC WRITER NOTE: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Roof Curbs B. Air Outlets and Inlets
2、: Diffusers, Registers, and Grilles. 1.2 RELATED WORK A. Outdoor and Exhaust Louvers: Section 08 90 00, LOUVERS AND VENTS. B. Kitchen Hoods: Section 23 38 13, COMMERCIAL-KITCHEN HOODS. C. Fume Hoods: Section 11 53 13, LABORATORY FUME HOODS. D. Seismic Reinforcing: Section 13 05 41, SEISMIC RESTRAINT
3、 REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. E. General Mechanical Requirements: Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION. F. Noise Level Requirements: Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. G. Testing and Balancing of Air Flows: Secti
4、on 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC. 1.3 QUALITY ASSURANCE A. Refer to article, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION. B. Fire Safety Code: Comply with NFPA 90A. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP
5、 DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Air intake/exhaust hoods. 2. Diffusers, registers, grilles and accessories. C. Coordination Drawings: Refer to article, SUBMITTALS, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION. 1.5 APPLICABLE PU
6、BLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. Air Diffusion Council Test Code: Provided by IHSNot for ResaleNo reproduction or networking permitted without license
7、from IHS-,-,-11-09 23 37 00 - 2 1062 GRD-84.Certification, Rating, and Test Manual 4thEdition C. American Society of Civil Engineers (ASCE): ASCE7-05Minimum Design Loads for Buildings and Other Structures D. American Society for Testing and Materials (ASTM): A167-99 (2004)Standard Specification for
8、Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet and Strip B209-07.Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate E. National Fire Protection Association (NFPA): 90A-09Standard for the Installation of Air Conditioning and Ventilating Systems F. Underwriters Lab
9、oratories, Inc. (UL): 181-08UL Standard for Safety Factory-Made Air Ducts and Connectors PART 2 - PRODUCTS 2.1 GRAVITY INTAKE/EXHAUST VENTILATORS (ROOF MOUNTED) A. Aluminum, ASTM B209, louvered, spun, or fabricated using panel sections with roll-formed edges, 13 mm (1/2 inch) mesh aluminum welded wi
10、re bird screen, with gravity or motorized dampers where shown, accessible interior, designed for wind velocity specified in Paragraph 3.3. 1. Spun Intake/Exhaust Ventilators: Spun aluminum structural components shall be constructed of minimum 1.3 mm (16 Gauge) marine alloy aluminum, bolted to a rigi
11、d aluminum support structure. The aluminum base shall have continuously welded curb cap corners for maximum leak protection. The spun aluminum baffle shall have a rolled bead for added strength. 2. Louvered Intake/Exhaust Hoods: Louvered hood constructed from 0.081 Gauge extruded aluminum tiers weld
12、ed to a minimum 3.3 mm (8 Gauge) aluminum support structure. The aluminum hood shall be constructed of a minimum 0.064 marine alloy aluminum and provided with a layer of anti-condensate coating. The aluminum base shall have continuously welded curb cap corners for maximum leak protection. 3. Low Sil
13、houette Intake/Exhaust Ventilator: The unit shall be of bolted and welded construction utilizing corrosion resistant fasteners. The aluminum hood shall be constructed of minimum 1.60 mm (14 Gauge) marine alloy aluminum, bolted to a minimum 3.25 mm (8 Gauge) aluminum support structure. The aluminum b
14、ase shall have continuously welded Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-09 23 37 00 - 3 curb cap corners for maximum leak protection. Birdscreen constructed of 13 mm (1/2 inch) mesh shall be mounted across the relief opening. B. See ven
15、tilator schedule on the drawings. Sizes shown on the drawings designate throat size. Area of ventilator perimeter opening shall be not less than the throat area. C. Dampers for Gravity Ventilators without Duct Connection: Construct damper of the same material as the ventilator and of the design to c
16、ompletely close opening or remain wide open. Hold damper in closed position by a brass chain and catch. Extend chains 300 mm (12 inches) below and engage catch when damper is closed. /D. See paragraph 3.3 for Intake/Exhaust exposed to high wind velocities. / E. Provide Roof Curb by unit manufacturer
17、. Refer to Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND STEAM GENERATION for additional requirements. 2.2 EQUIPMENT SUPPORTS Refer to Section 21 05 11, COMMON WORK RESULTS FOR FIRE SUPPRESSION, Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING, and Section 23 05 11, COMMON WORK RESULTS FOR HV
18、AC AND STEAM GENERATION. SPEC WRITER NOTE: Edit or delete distribution plate to suit project. 2.3 AIR OUTLETS AND INLETS A. Materials: 1. Steel or aluminum / except that all supply air outlets installed in operating rooms and Cystoscopy rooms (see Article 2.3C.3) shall be stainless steel. Use alumin
19、um air outlets and inlets for facilities located in high-humidity areas. Exhaust air registers located in combination toilets and shower stalls shall be constructed from aluminum. /. Provide manufacturers standard gasket. 2. Exposed Fastenings: The same material as the respective inlet or outlet. Fa
20、steners for aluminum may be stainless steel. 3. Contractor shall review all ceiling drawings and details and provide all ceiling mounted devices with appropriate dimensions and trim for the specific locations. B. Performance Test Data: In accordance with Air Diffusion Council Code 1062GRD. Refer to
21、Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT for NC criteria. C. Air Supply Outlets: 1. Ceiling Diffusers: Suitable for surface mounting, exposed T-bar or special tile ceilings, off-white finish, square or round neck Provided by IHSNot for ResaleNo reproduction or netw
22、orking permitted without license from IHS-,-,-11-09 23 37 00 - 4 connection as shown on the drawings. Provide plaster frame for units in plaster ceilings. a. Square, louver, fully adjustable pattern: Round neck, surface mounting unless shown otherwise on the drawings. Provide equalizing or control g
23、rid and volume control damper. b. Louver face type: Square or rectangular, removable core for 1, 2, 3, or 4 way directional pattern. Provide equalizing or control grid and opposed blade damper. c. Perforated face type: Manual adjustment for one-, two-, three-, or four-way horizontal air distribution
24、 pattern without change of air volume or pressure. Provide equalizing or control grid and opposed blade over overlapping blade damper. Perforated face diffusers for VAV systems shall have the pattern controller on the inner face, rather than in the neck and designed to discharge air horizontally at
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2337002009AIROUTLETSANDINLETSPDF