VA 23 34 00-2009 HVAC FANS.pdf
《VA 23 34 00-2009 HVAC FANS.pdf》由会员分享,可在线阅读,更多相关《VA 23 34 00-2009 HVAC FANS.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、11-09 23 34 00 - 1 SECTION 23 34 00 HVAC FANS SPEC WRITER NOTES: 1. Delete between /- / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION A. Fans for heating, ventilating and air condition
2、ing. B. Product Definitions: AMCA Publication 99, Standard l-66. 1.2 RELATED WORK A. Section 01 00 00, GENERAL REQUIREMENTS. B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. C. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. D. Section 23 05 11, COMMON W
3、ORK RESULTS FOR HVAC AND STEAM GENERATION. E. Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT. F. Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. G. Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC. H. Section 23 09 23, DI
4、RECT-DIGITAL CONTROL SYSTEM FOR HVAC. I. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS. J. Section 23 82 16, AIR COILS. K. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS. 1.3 QUALITY ASSURANCE A. Refer to paragraph, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC AND
5、 STEAM GENERATION. B. Fans and power ventilators shall be listed in the current edition of AMCA 26l, and shall bear the AMCA performance seal. C. Operating Limits for Centrifugal Fans: AMCA 99 (Class I, II, and III). D. Fans and power ventilators shall comply with the following standards: l. Testing
6、 and Rating: AMCA 2l0. 2. Sound Rating: AMCA 300. E. Vibration Tolerance for Fans and Power Ventilators: Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT. F. Performance Criteria: Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS
7、-,-,-11-09 23 34 00 - 2 l. The fan schedule shall show the design air volume and static pressure. Select the fan motor HP by increasing the fan BHP by 10 percent to account for the drive losses and field conditions. 2. Select the fan operating point as follows: a. Forward Curve and Axial Flow Fans:
8、Right hand side of peak pressure point b. Air Foil, Backward Inclined, or Tubular: At or near the peak static efficiency G. Safety Criteria: Provide manufacturers standard screen on fan inlet and discharge where exposed to operating and maintenance personnel. H. Corrosion Protection: 1. Except for f
9、ans in fume hood exhaust service, all steel shall be mill-galvanized, or phosphatized and coated with minimum two coats, corrosion resistant enamel paint. Manufacturers paint and paint system shall meet the minimum specifications of: ASTM D1735 water fog; ASTM B117 salt spray; ASTM D3359 adhesion; a
10、nd ASTM G152 and G153 for carbon arc light apparatus for exposure of non-metallic material. 2. Fans for general purpose fume hoods, or chemical hoods, and radioisotope hoods shall be constructed of materials compatible with the chemicals being transported in the air through the fan. I. Spark resista
11、nt construction: If flammable gas, vapor or combustible dust is present in concentrations above 20% of the Lower Explosive Limit (LEL), the fan construction shall be as recommended by AMCAs Classification for Spark Resistant Construction. Drive set shall be comprised of non-static belts for use in a
12、n explosive. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: l. Fan sections, motors and drives. 2. Centrifugal fans, motors, drives, accessories and coatings. a. In-line centrifugal fans. b. Tubular Centri
13、fugal Fans. c. Up-blast kitchen hood exhaust fans. d. Industrial fans. e. Utility fans and vent sets. 3. Prefabricated roof curbs. 4. Power roof and wall ventilators. 5. Centrifugal ceiling fans. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-09
14、23 34 00 - 3 6. Propeller fans. 7. Packaged hood make-up air units. 8. Vane axial fans. 9. Tube-axial fans. 10. Air curtain units. C. Certified Sound power levels for each fan. D. Motor ratings types, electrical characteristics and accessories. E. Roof curbs. F. Belt guards. G. Maintenance and Opera
15、ting manuals in accordance with Section 01 00 00, GENERAL REQUIREMENTS. H. Certified fan performance curves for each fan showing cubic feet per minute (CFM) versus static pressure, efficiency, and horsepower for design point of operation. 1.5 APPLICABLE PUBLICATIONS A. The publications listed below
16、form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. Air Movement and Control Association International, Inc. (AMCA): 99-86.Standards Handbook 2l0-06Laboratory Methods of Testing Fans for Aerodynamic Performance Rat
17、ing 26l-09Directory of Products Licensed to bear the AMCA Certified Ratings Seal - Published Annually 300-08Reverberant Room Method for Sound Testing of Fans C. American Society for Testing and Materials (ASTM): B117-07aStandard Practice for Operating Salt Spray (Fog) Apparatus D1735-08Standard Prac
18、tice for Testing Water Resistance of Coatings Using Water Fog Apparatus D3359-08Standard Test Methods for Measuring Adhesion by Tape Test G152-06.Standard Practice for Operating Open Flame Carbon Arc Light Apparatus for Exposure of Non-Metallic Materials G153-04.Standard Practice for Operating Enclo
19、sed Carbon Arc Light Apparatus for Exposure of Non-Metallic Materials D. National Fire Protection Association (NFPA): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-09 23 34 00 - 4 NFPA 96-08Standard for Ventilation Control and Fire Protection of
20、 Commercial Cooking Operations E. National Sanitation Foundation (NSF): 37-07.Air Curtains for Entrance Ways in Food and Food Service Establishments F. Underwriters Laboratories, Inc. (UL): 181-2005Factory Made Air Ducts and Air Connectors 1.6 EXTRA MATERIALS A. Provide one additional set of belts f
21、or all belt-driven fans. PART 2 - PRODUCTS 2.1 FAN SECTION (CABINET FAN) Refer to specification Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS. 2.2 CENTRIFUGAL FANS A. Standards and Performance Criteria: Refer to Paragraph, QUALITY ASSURANCE. Record factory vibration test results on the
22、 fan or furnish to the Contractor. SPEC WRITER NOTE: Coordinate Fan arrangement with the equipment schedule on drawings. B. Fan arrangement, unless noted or approved otherwise: l. DWDl fans: Arrangement 3. 2. SWSl fans: Arrangement l, 3, 9 or l0, / except for fume hood (H7 or Hl3) exhaust fans Arran
23、gement 3 shall not be acceptable. / C. Construction: Wheel diameters and outlet areas shall be in accordance with AMCA standards. l. Housing: Low carbon steel, arc welded throughout, braced and supported by structural channel or angle iron to prevent vibration or pulsation, flanged outlet, inlet ful
24、ly streamlined. Provide lifting clips, and casing drain. Provide manufacturers standard access door. Provide 12.5 mm (1/2 inches) wire mesh screens for fan inlets without duct connections. 2. Wheel: Steel plate with die formed blades welded or riveted in place, factory balanced statically and dynami
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2334002009HVACFANSPDF