1、04-11 23 31 00 - 1 SECTION 23 31 00 HVAC DUCTS AND CASINGS SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. References to pressure in this section are gage pressure unless othe
2、rwise noted. PART 1 - GENERAL 1.1 DESCRIPTION A. Ductwork and accessories for HVAC including the following: 1. Supply air, return air, outside air, exhaust, make-up air, and relief systems. 2. Exhaust duct with HEPA filters for / Autopsy Suite / Negative Pressure Isolation Room / Biological Safety C
3、abinets / Radioisotope Hoods /. 3. Exhaust duct for chemical fume hoods, kitchen hood exhaust (grease) and “wet exhaust” ducts. B. Definitions: 1. SMACNA Standards as used in this specification means the HVAC Duct Construction Standards, Metal and Flexible. 2. Seal or Sealing: Use of liquid or masti
4、c sealant, with or without compatible tape overlay, or gasketing of flanged joints, to keep air leakage at duct joints, seams and connections to an acceptable minimum. 3. Duct Pressure Classification: SMACNA HVAC Duct Construction Standards, Metal and Flexible. 4. Exposed Duct: Exposed to view in a
5、finished room, / exposed to weather. / 1.2 RELATED WORK A. Fire Stopping Material: Section 07 84 00, FIRESTOPPING. B. Outdoor and Exhaust Louvers: Section 08 90 00, LOUVERS and VENTS. C. Kitchen Hoods: Section 23 38 13, COMMERCIAL-KITCHEN HOODS. D. Fume Hoods: Section 11 53 13, LABORATORY FUME HOODS
6、. /E. Seismic Reinforcing: Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS./ F. General Mechanical Requirements: Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. G. Noise Level Requirements: Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIP
7、ING and EQUIPMENT. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-04-11 23 31 00 - 2 H. Duct Insulation: Section 23 07 11, HVAC, PLUMBING, and BOILER PLANT INSULATION I. Plumbing Connections: Section 22 11 00, FACILITY WATER DISTRIBUTION J. Air Flow
8、 Control Valves and Terminal Units: Section 23 36 00, AIR TERMINAL UNITS. K. Duct Mounted Coils: Section 23 82 16, AIR COILS. L. Supply Air Fans: Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS. M. Return Air and Exhaust Air Fans: Section 23 34 00, HVAC FANS. N. Air Filters and Filters E
9、fficiencies: Section 23 40 00, HVAC AIR CLEANING DEVICES. O. Duct Mounted Instrumentation: Section 23 09 23, DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC. P. Testing and Balancing of Air Flows: Section 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC. Q. Smoke Detectors: Section 28 31 00, FIRE DETECTI
10、ON and ALARM. 1.3 QUALITY ASSURANCE A. Refer to article, QUALITY ASSURANCE, in Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. B. Fire Safety Code: Comply with NFPA 90A. C. Duct System Construction and Installation: Referenced SMACNA Standards are the minimum acceptable quality.
11、 D. Duct Sealing, Air Leakage Criteria, and Air Leakage Tests: Ducts shall be sealed as per duct sealing requirements of SMACNA HVAC Air Duct Leakage Test Manual for duct pressure classes shown on the drawings. E. Duct accessories exposed to the air stream, such as dampers of all types (except smoke
12、 dampers) and access openings, shall be of the same material as the duct or provide at least the same level of corrosion resistance. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Rectangular ducts: a.
13、Schedules of duct systems, materials and selected SMACNA construction alternatives for joints, sealing, gage and reinforcement. b. Duct liner. c. Sealants and gaskets. d. Access doors. 2. Round and flat oval duct construction details: Provided by IHSNot for ResaleNo reproduction or networking permit
14、ted without license from IHS-,-,-04-11 23 31 00 - 3 a. Manufacturers details for duct fittings. b. Duct liner. c. Sealants and gaskets. d. Access sections. e. Installation instructions. 3. Volume dampers, back draft dampers. 4. Upper hanger attachments. 5. Fire dampers, fire doors, and smoke dampers
15、 with installation instructions. 6. Sound attenuators, including pressure drop and acoustic performance. 7. Flexible ducts and clamps, with manufacturers installation instructions. 8. Flexible connections. 9. Instrument test fittings. 10 Details and design analysis of alternate or optional duct syst
16、ems. 11 COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. C. Coordination Drawings: Refer to article, SUBMITTALS, in Section 23 05 1.5 APPLICABLE PUBLICATIONS A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by
17、the basic designation only. B. American Society of Civil Engineers (ASCE): ASCE7-05 . Minimum Design Loads for Buildings and Other Structures C. American Society for Testing and Materials (ASTM): A167-99(2009) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet
18、, and Strip A653-09 Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy coated (Galvannealed) by the Hot-Dip process A1011-09a Standard Specification for Steel, Sheet and Strip, Hot rolled, Carbon, structural, High-Strength Low-Alloy, High Strength Low-Alloy with Impr
19、oved Formability, and Ultra-High Strength B209-07 Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate C1071-05e1 . Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material) Provided by IHSNot for ResaleNo reproduction or networking perm
20、itted without license from IHS-,-,-04-11 23 31 00 - 4 E84-09a Standard Test Method for Surface Burning Characteristics of Building Materials D. National Fire Protection Association (NFPA): 90A-09 . Standard for the Installation of Air Conditioning and Ventilating Systems 96-08 Standard for Ventilati
21、on Control and Fire Protection of Commercial Cooking Operations E. Sheet Metal and Air Conditioning Contractors National Association (SMACNA): 2nd Edition 2005 . HVAC Duct Construction Standards, Metal and Flexible 1st Edition - 1985 . HVAC Air Duct Leakage Test Manual 6th Edition 2003 . Fibrous Gla
22、ss Duct Construction Standards F. Underwriters Laboratories, Inc. (UL): 181-08 . Factory-Made Air Ducts and Air Connectors 555-06 Standard for Fire Dampers 555S-06 . Standard for Smoke Dampers PART 2 - PRODUCTS SPEC WRITER NOTE: The following ductwork is not permitted: 1. Fibrous glass ductwork 2. U
23、nderground Ductwork 3. Concrete Ductwork 2.1 DUCT MATERIALS AND SEALANTS A. General: Except for systems specified otherwise, construct ducts, casings, and accessories of galvanized sheet steel, ASTM A653, coating G90; or, aluminum sheet, ASTM B209, alloy 1100, 3003 or 5052. B. Specified Corrosion Re
24、sistant Systems: Stainless steel sheet, ASTM A167, Class 302 or 304, Condition A (annealed) Finish No. 4 for exposed ducts and Finish No. 2B for concealed duct or ducts located in mechanical rooms. C. Optional Duct Materials: 1. Grease Duct: Double wall factory-built grease duct, UL labeled and comp
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2331002011HVACDUCTSANDCASINGSPDF