1、*USACE / NAVFAC / AFCESA / NASA UFGS-09 67 23.15 (August 2010)-Preparing Activity: NAVFAC SupersedingUFGS-09 67 23.15 (February 2010)UFGS-09 67 23.15 (August 2009)UFGS-09 67 23.15 (August 2008)UFGS-09 62 50.10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL
2、dated July 2010*SECTION TABLE OF CONTENTSDIVISION 09 - FINISHESSECTION 09 67 23.15FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM08/10PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 QUALITY ASSURANCE1.3.1 Test Reports1.3.1.1 Joint Sealant1.3.1.2 Thin Film Flooring System1.3.1.3 Primer1.3.1.4 Urethane
3、Topcoat1.3.1.5 Daily Inspection Report1.3.2 Certificates1.3.2.1 Work Plan1.3.2.2 Flooring System Applicator Qualifications1.3.2.3 Joint Sealant1.3.2.4 Thin Film Flooring System1.3.2.5 Warranty1.3.3 Product Data1.3.3.1 Joint Sealant1.3.3.2 Thin Film Flooring System1.3.3.3 Water-Based Alkaline Degreas
4、er1.4 DELIVERY, STORAGE, AND HANDLING1.5 COATING HAZARDS1.6 JOB SITE REFERENCES1.7 PATCH TEST DEMONSTRATIONPART 2 PRODUCTS2.1 JOINT SEALANT2.2 THIN FILM FLOORING SYSTEM2.2.1 Primer Coat2.2.2 Urethane Topcoat2.3 WHITE ALUMINUM OXIDE NON-SKID GRITSECTION 09 67 23.15 Page 1Provided by IHSNot for Resale
5、No reproduction or networking permitted without license from IHS-,-,-2.4 PREAPPROVED MATERIALSPART 3 EXECUTION3.1 COATING SAMPLE COLLECTION3.2 TILE AND TILE ADHESIVE REMOVAL3.3 JOINT MATERIAL REMOVAL, RE-SAW CUTTING, CRACK CHASING3.4 DEGREASING3.5 COATING SYSTEM REMOVAL3.6 SURFACE PREPARATION3.7 JOI
6、NT TREATMENT3.7.1 Install Backer Rod3.7.2 Sealant Application3.8 PRE-APPLICATION TESTING FOR CONTAMINATION3.9 COATING APPLICATION3.9.1 Primer Application3.9.2 Non-Skid Grit Broadcast3.9.3 Application of Topcoats3.9.3.1 First Topcoat3.9.3.2 Second Topcoat3.9.3.3 Walkway Stripe and Grounding Rod Marki
7、ngs3.10 CURING3.11 FIELD TESTS AND INSPECTION3.11.1 Coating Inspector3.11.2 Inspection3.11.2.1 Daily Inspection Report3.11.2.2 Inspection Logbook3.11.2.3 Inspection Equipment3.11.3 Adhesion Testing3.12 FINAL CLEANUP- End of Section Table of Contents -SECTION 09 67 23.15 Page 2Provided by IHSNot for
8、ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-09 67 23.15 (August 2010)-Preparing Activity: NAVFAC SupersedingUFGS-09 67 23.15 (February 2010)UFGS-09 67 23.15 (August 2009)UFGS-09 67 23.15 (August 2008)UFGS-09 62 50.10 (April 2006) UN
9、IFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2010*SECTION 09 67 23.15FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM08/10*NOTE: This guide specification covers the requirements for a three-coat, liquid flooring system with reflective urethane topcoats, slip r
10、esistance, and joint work.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not br
11、ackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of Technical Proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UF
12、GS should be submitted as a Criteria Change Request (CCR).*NOTE: The thin film flooring system is appropriate for use in: aircraft maintenance hangars, equipment maintenance shops, and all other industrial floors where resistance to abrasion and fuel is required. Installation costs: $2.00 to $4.50 p
13、er 0.1 square meters square foot. Nominal thickness: 0.375 mm 15.0 mils. Can be rejuvenated by replacing urethane topcoats, and non-skid, only. Approximate service life: Urethane top coating with non-skid grit at three or more years. The flooring system is neither conductive nor Electro-Static Dissi
14、pative (ESD), however, either formulation is easily designed upon SECTION 09 67 23.15 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-request. This specification is not for use in overcoating existing sound floor coatings.*NOTE: Prior to the fl
15、ooring systems installation, a concrete condition assessment in accordance with the Naval Facilities Engineering Service Centers (NFESC) Users Guide (UG)-2036-SHR is highly recommended. The condition assessment is designed to identify problem floors and eliminate premature flooring failures produced
16、 by: 1) coating concrete with low surface strength, 2) coating concrete with high levels of surface contamination (oils, fuels, fats, waxes, etc.), and 3) coating concrete with a high rate of Moisture Vapor Emission (MVE). The thin film flooring system is suitable for application to: A) “smooth“ con
17、crete surface texture, B) concrete with a rate of MVE no more than 169.0 micrograms moisture per second, square meter3.0 pounds moisture per 24 hours, 1000 square feet (ASTM F 1869), C) concrete with surface strength greater than 1.34 MPa 200 psi (ASTM D 4541), and D) concrete with fuel/oil contamin
18、ation to a depth no more than 6.25 mm 1/4 inch.*NOTE: If a concrete floor has a rate of Moisture Vapor Emission (MVE) more than 197.0 micrograms moisture per second, square meter 3.5 pounds moisture per 24 hours, 1000 square feet (ASTM F 1869), apply a layered Moisture Reducing System (MRS) prior to
19、 the application of the thin film flooring system. The MRS shall be compatible with the submitted flooring system and approved / warranted by the manufacturer of the thin film flooring system. Apply the MRS to shot blasted concrete and reduce the rate of MVE to less than 169.0 micrograms moisture pe
20、r second, square meter 3.0 pounds moisture per 24 hours, 1000 square feet. MRSs can employ combinations of concrete sealers, specific epoxies, and moisture insensitive grouts, with or without mesh. MRSs are available from the following partial list of vendors: Tennant (800) 553-8033, Stonhard (856)
21、779-7500, General Polymers (800) 543-7694, Crawford Labs (800) 356-7625, Floor Seal (800) 295-0221. Moisture Vapor Emission Test Kits (MVETK) are available from the following partial list of vendors: Floor Seal (800) 295-0221, Sinak (619)231-1771, General Polymers (800)534-7694, Crawford Labs (800)
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS096723152010FUELRESISTIVERESINOUSFLOORING3COATSYSTEM3 涂层 系统 阻燃 树脂 地板 材料 PDF

链接地址:http://www.mydoc123.com/p-984760.html