NAVY MIL-PRF-32228-2006 ALARM PANEL ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)警报信号板》.pdf
《NAVY MIL-PRF-32228-2006 ALARM PANEL ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)警报信号板》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-PRF-32228-2006 ALARM PANEL ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS)《高级火和烟敏感元件系统(AFSSS)警报信号板》.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、Comments, suggestions, or questions on this document should be addressed to: Commander, Naval Sea Systems Command, ATTN: SEA 05Q, 1333 Isaac Hull Avenue, SE, Stop 5160, Washington Navy Yard DC 20376-5160 or emailed to CommandStandardsnavy.mil, with the subject line “Document Comment”. Since contact
2、information can change, you may want to verify the currency of this address information using the ASSIST Online database at http:/assist.daps.dla.mil. AMSC N/A FSC 6320 INCH-POUND MIL-PRF-32228 25 October 2006 PERFORMANCE SPECIFICATION ALARM PANEL, ADVANCED FIRE AND SMOKE SENSOR SYSTEM (AFSSS) This
3、specification is approved for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This specification covers the performance requirements for alarm panels (see 6.8.3), which are components of an overall Advanced Fire and Smoke Sensor System (AFSSS) for use on naval s
4、hips. These alarm panels may be of commercial-off-the-shelf (COTS) design, but must be rugged (see 6.8.17) enough to meet all of the requirements of this performance specification and the rigors of Navy shipboard service. Performance requirements for the other associated AFSSS components (e.g., ioni
5、zation (see 6.8.11) and photoelectric (see 6.8.13) smoke sensors (see 6.8.20), heat sensors (see 6.8.10), flame detectors (see 6.8.8), Flame Detector Zone Modules (FDZM) (see 6.8.9), Switch Closure Zone Modules (SCZM) (see 6.8.21), and isolators (see 6.8.12) are contained in their respective AFSSS s
6、pecifications. 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4, or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While e
7、very effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4, or 5 of this specification, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards, a
8、nd handbooks. The following specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. DEPARTMENT OF DEFENSE SPECIFICATIONS MIL-S-901 - Shock Tests, H
9、.I. (High Impact); Shipboard Machinery, Equipment and Systems, Requirements for MIL-E-2036 - Enclosures for Electric and Electronic Equipment, Naval Shipboard MIL-DTL-24643 - Cables and Cords, Electric, Low Smoke, for Shipboard Use General Specification for Provided by IHSNot for ResaleNo reproducti
10、on or networking permitted without license from IHS-,-,-MIL-PRF-32228 DEPARTMENT OF DEFENSE STANDARDS MIL-STD-167-1 - Mechanical Vibrations of Shipboard Equipment (Type I - Environmental and Type II Internally Excited) MIL-STD-461 - Requirements for the Control of Electromagnetic Interference Charac
11、teristics of Subsystems and Equipment (Copies of these documents are available online at http:/assist.daps.dla.mil/quicksearch/ or http:/assist.daps.dla.mil or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 Non-Government publications
12、. The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract. UNDERWRITERS LABORATORIES INC. (UL) UL 268 - Standard for Smoke Detectors for Fire Alarm Signaling Systems
13、 UL 864 - Standard for Control Units and Accessories for Fire Alarm Systems (DoD adopted) (Copies of these documents are available from Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096 or online at .) NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 72 - National Fire A
14、larm Code (Copies of this document are available from National Fire Protection Association, 11 Tracy Drive, Avon, MA 02322 or online at www.nfpa.org.) 2.4 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document take
15、s precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2 and 6.3), a sample shall be subjected to first article inspection in accordance with 4.2. 3.2 Design r
16、equirements. 3.2.1 Design, materials, and manufacturing processes. The contractor shall select the materials, but the materials shall meet all of the interface, operational, and performance requirements specified herein. 3.2.2 Recycled, recovered, or environmentally preferable materials. Recycled, r
17、ecovered, or environmentally preferable materials should be used to the maximum extent possible, provided that the material meets or exceeds the operational and maintenance requirements, and promotes economically advantageous life cycle costs. 3.2.3 Restricted materials. The use of lithium and mercu
18、ry batteries is restricted and shall not be used in equipment unless specifically required and approved by the procuring activity. 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-32228 3.3 Configuration. 3.3.1 Alarm panel. The alarm panel s
19、hall contain the microprocessor, printed circuit boards, network cards, power supplies, back-up batteries, alphanumeric display, alphanumeric keypad (for operation and programming) and all associated hardware and software necessary to operate as a fire detection system. The alarm panel shall provide
20、 power to and monitor/communicate with various addressable AFSSS analog initiating devices (6.8.5), including ionization smoke sensors, photoelectric smoke sensors, heat sensor, flame detectors, FDZMs (if required), SCZMs, and/or isolators. The total quantity of these devices will vary depending on
21、the particular installation. The alarm panel shall have an alphanumeric display of at least 60 characters, readable in all levels of light (including total darkness), which shall display all alarm and trouble information, sensor data, and system information, and shall provide user-friendly menus to
22、assist in alarm panel programming and selection of sensor alarm thresholds. The alarm panel shall also have the capability to interface and operate with other AFSSS alarm panels, AFSSS color graphic displays (see 6.8.2), and third party color graphic displays (see 6.8.22) as one alarm panel/componen
23、t on a larger distributed fire detection system. 3.3.2 Interchangeability. The AFSSS alarm panel shall have a unique model number assigned to it. All mechanical and electrical AFSSS alarm panel components shall be physically identical and interchangeable with other AFSSS alarm panel components to ea
24、se troubleshooting and parts replacement. 3.3.3 Individual addressability. The alarm panel shall communicate with, individually identify, and monitor the AFSSS ionization smoke sensors, photoelectric smoke sensors, heat sensors, flame detectors (via their FDZMs, if required), and SCZMs via their adj
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILPRF322282006ALARMPANELADVANCEDFIREANDSMOKESENSORSYSTEMAFSSS 高级 敏感 元件 系统 AFSSS 警报 信号 PDF

链接地址:http://www.mydoc123.com/p-981014.html