1、BRITISH STANDARD BS 4996:1973 Specification for Line traps for power line carrier systems UDC 621.315.052.63:621.316.9:621.372.54BS4996:1973 This British Standard havingbeenapproved by the Electrical Industry Standards Committee, was published underthe authorityof the Executive Boardon 31October1973
2、 BSI 12-1999 The following BSI references relate to the work on this standard: Committee reference ELE/89 Draft for comment69/13047 ISBN 0 580 07698 9 Co-operating organizations The Electrical Industry Standards Committee under whose supervision this British Standard was prepared, consists of repres
3、entatives from the following Government departments and scientific and industrial organizations: Associated Offices Technical Committee Association of Consulting Engineers* Association of Manufacturers of Domestic Electrical Appliances Association of Mining Electrical and Mechanical Engineers Associ
4、ation of Supervisory and Executive Engineers British Electrical and Allied Manufacturers Association British Electrotechnical Approvals Board for Household Equipment British Radio Equipment Manufacturers Association British Railways Board British Steel Corporation Crown Agents for Oversea Government
5、s and Administrations Department of Employment (HM Factory Inspectorate) Department of the Environment Department of Trade and Industry Electric Cable Makers Confederation Electric Contractors Association Electrical Contractors Association of Scotland Electrical Research Association Electricity Coun
6、cil, the Central Electricity Generating Board and the Area Boards in England and Wales* Electronic Engineering Association Engineering Equipment Users Association Institution of Electrical Engineers Institution of Electrical and Electronics Technician Engineers Lighting Industry Federation Limited M
7、inistry of Defence National Inspection Council for Electrical Installation Contracting National Physical Laboratory (Department of Trade and Industry) Oil Companies Materials Association Post Office South of Scotland Electricity Board The organizations marked with an asterisk in the above list, toge
8、ther with the following, were directly represented on the committee entrusted with the preparation of this British Standard: BEAMA Transmission and Distribution Association North of Scotland Hydro-Electric Board Amendments issued since publication Amd. No. Date of issue CommentsBS4996:1973 BSI 12-19
9、99 i Contents Page Co-operating organizations Inside front cover Foreword ii 1 General 1 1.1 Scope 1 1.2 Service conditions 1 1.3 Carrier frequency 1 2 Definitions 1 3 Requirements 2 3.1 General requirements 2 3.2 Blocking requirements 2 3.3 Continuous service requirements 3 3.4 Ability to withstand
10、 short-circuit 3 3.5 Inductance of the main coil 3 3.6 Insulation level 3 3.7 Tensile strength of the suspension system 4 4 Rating plates 4 5 Tests 4 5.1 General conditions for tests 4 5.2 Type tests 4 5.3 Routine tests 5 Appendix A Recommended values of rated quantities 6 Figure 1 Example of a circ
11、uit diagram of a line trap tuned for a carrier-frequency band 7 Figure 2 Definition of the bandwidth of line traps 8 Figure 3 Measuring circuit for the impulse voltage test 9 Figure 4 Measuring circuit for the determination of the blocking impedance 9 Figure 5 Measuring circuit for the blocking impe
12、dance at the tuning frequency in the case of line traps utilizing simple resonance 10 Figure 6 Measuring circuit for the determination of the insertion loss 10 Table 1 Limits of temperature rise 3 Table 2 Co-ordination of currents 6 Publications referred to Inside back coverBS4996:1973 ii BSI 12-199
13、9 Foreword This British Standard is technically identical with Publication353 of the International Electrotechnical Commission. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their correct application. Complia
14、nce with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pagesi andii, pages1 to10, an inside back cover and a back cover. This standard has been updated (see copyright date) and may have had
15、 amendments incorporated. This will be indicated in the amendment table on the inside front cover.BS4996:1973 BSI 12-1999 1 1 General 1.1 Scope This British Standard gives definitions, requirements, methods of test and recommended values of rated quantities for line traps intended to be inserted int
16、o high-voltage transmission lines to prevent undue loss of superimposed carrier signal. It does not apply to inductors which may be connected to high-voltage transmission systems for other purposes, such as series reactors. NOTEThe titles of the British Standards referred to in this standard are lis
17、ted on the inside back cover. 1.2 Service conditions Unless otherwise agreed between the manufacturer and the purchaser, the line trap shall be suitable for operation in the service conditions given below, to which the requirements of this British Standard are related: 1) Exposure. Outdoor service,
18、exposed to sunshine, rain, fog, hail, frost, snow and ice. NOTESevere atmospheric conditions such as salt-spray, industrial pollution, etc.,should be covered by special agreement between the manufacturer and the purchaser. 2) Altitude. A height above sea level not exceeding1000m. NOTEProvision is ma
19、de in3.3 and3.6 for tests on line traps designed for operation at greater altitudes. 3) Temperature of cooling medium. An air temperature between25 C and+40 C inclusive, with average temperatures not exceeding the following: +30 C for the daily average, +20 C for the annual average. NOTEProvision is
20、 made in3.3 for tests on line traps designed for higher cooling medium temperatures. 4) Wave-shape. Power-frequency current and voltage of approximately sinusoidal wave-shape. 5) Power frequency. A power system rated frequency between zero (d.c.)and60Hz inclusive. 1.3 Carrier frequency The limits of
21、 carrier frequency shall be the subject of agreement between the manufacturer and the purchaser. 2 Definitions For the purposes of this British Standard the following definitions apply. For other definitions, reference should be made toBS4727. 2.1 General definitions 2.1.1 line trap a piece of elect
22、rical apparatus intended for series insertion into a high-voltage line. Its impedance is negligible at the power frequency, so as not to disturb the power transmission, but relatively high over any frequency band appropriate to carrier transmission a line trap consists of a main coil with a protecti
23、ve device and, usually, a tuning device NOTEFigure 1 shows an example of a line trap circuit. 2.1.2 main coil the inductor which carries the power-frequency current its rated inductance L Nis that value which corresponds to the specified characteristics of the line trap at power frequency 2.1.3 tuni
24、ng device a device which serves the purpose of obtaining a relatively high line trap impedance for one or more frequencies or frequency bands. It consists of capacitors with, possibly, inductors and resistors, and is shunt-connected to the main coil 2.1.4 protective device a device which protects th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS49961973SPECIFICATIONFORLINETRAPSFORPOWERLINECARRIERSYSTEMS 电源线 载波通信 系统 线路 陷波 规范 PDF

链接地址:http://www.mydoc123.com/p-544773.html