《ASTM D4388-2002 Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes《非金属半导电性及电绝缘橡胶带的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM D4388-2002 Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes《非金属半导电性及电绝缘橡胶带的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 4388 02An American National StandardStandard Specification forNonmetallic Semi-Conducting and Electrically InsulatingRubber Tapes1This standard is issued under the fixed designation D 4388; the number immediately following the designation indicates the year oforiginal adoption or, in
2、the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 Th
3、is specification covers nonmetallic semi-conductingand electrical insulating tapes designed for the splicing andrepair of electrical wire and cables operating at voltages up to325 kV, phase to phase.1.2 The SI values are the standard. The values stated ininch-pound units given in parentheses are for
4、 informationpurposes only.2. Referenced Documents2.1 ASTM Standards:D 4325 Test Methods for Nonmetallic Semi-Conductingand Electrically Insulating Rubber Tapes23. Classification3.1 Types:3.1.1 Type IA low voltage rubber insulating tape designedfor use on wires and cables operating up to 2000 V phase
5、 tophase in dry locations with conductor temperatures up to 80C(176F) for continuous operation, up to 95C (203F) foremergency overload conditions, and up to 150C (302F) forshort-circuit conditions. For outdoor use, protect the tape fromozone attack and ultraviolet radiation by the use of a suitableo
6、verwrap. Apply the tape to the wire or cable within anambient temperature range of 10 and 40C (14 and 104F).3.1.2 Type IIA medium voltage, ozone-resistant, rubberinsulating tape designed for use with wires and cables operat-ing up to 35 000 V phase to phase in either wet or drylocations with conduct
7、or temperatures up to 90C (194F) forcontinuous operation, up to 130C (266F) for emergencyoverload conditions, and up to 250C (482F) for short-circuitconditions when installed in accordance with the manufactur-ers instruction. For wet or dry outdoor use, protect the tapefrom ultraviolet radiation by
8、the use of a suitable overwrap.Apply the tape to the wire or cable within an ambienttemperature range of 10 and 40C (14 and 104F).3.1.3 Type IIIA high voltage, ozone-resistant, rubber in-sulating tape designed for use with wires and cables operatingup to 138 000 V phase to phase in either wet or dry
9、 locationswith conductor temperatures up to 90C (194F) for continu-ous operation, up to 130C (266F) for emergency overloadconditions, and up to 250C (482F) for short-circuit condi-tions when installed in accordance with the manufacturersinstructions. This tape is suitable for wet or dry outdoor use.
10、Apply the tape to the wire or cable within an ambienttemperature range of 10 and 40C (14 and 104F).3.1.4 Type IVA nonmetallic semi-conducting tape de-signed for shielding various portions of joints and terminationsin electrical wires and cables operating at any voltage underwet or dry conditions wit
11、h conductor temperatures up to 90C(194F) for continuous operation, or up to 130C (266F) foremergency overload conditions. This tape is suitable for wet ordry outdoor use. Apply the tape to the wire or cable within anambient temperature range of 10 and 40C (14 and 104F).3.1.5 Type VA higher voltage,
12、ozone-resistant, rubberinsulating tape designed for use with wires and cables operat-ing up to 325 000 V phase to phase in either wet or drylocations with conductor temperatures up to 90C (194F) forcontinuous operation, up to 130C (266F) for emergencyoverload, and up to 250C (482F) short-circuit con
13、ditionswhen installed in accordance with the manufacturers instruc-tions. This tape is suitable for wet or dry outdoor use. Apply thetape to the wire or cable within an ambient temperature of 10and 40C (14 and 104F).4. Physical Properties4.1 The tape shall consist of a non-crosslinked or partiallycr
14、osslinked rubber nonmetallic semi-conducting or insulatingcompound. The compound shall be well, evenly, and smoothlyprocessed, cut to the specified widths, and tightly wound inrolls with a separator between layers. Where a non-removableseparator is used, the separator will be considered an integralp
15、art of the tape.1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D09.07 on Flexible and Rigid Insulation Materials.Current edition approved March 10, 2002. Published June 2002. Origina
16、llypublished as D 4388 84. Last previous edition D 4388 97.2Annual Book of ASTM Standards, Vol 10.02.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.2 The separator shall be parchment paper, glazed orplastic sheeting, or any suitab
17、le material interposed betweenadjacent layers. The removable or non-removable separatorshall not interfere with the use of the roll during application.Where a removable separator is used, the separator shall bereadily removable from the rubber insulation without tearing ordamaging the tape insulatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD43882002STANDARDSPECIFICATIONFORNONMETALLICSEMICONDUCTINGANDELECTRICALLYINSULATINGRUBBERTAPES 非金属

链接地址:http://www.mydoc123.com/p-516938.html