《ASTM D4246-2014 Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable 90° C Operation《工作温度为90 ℃的电线和电缆的耐臭氧热塑性弹性体绝缘的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM D4246-2014 Standard Specification for Ozone-Resistant Thermoplastic Elastomer Insulation For Wire and Cable 90° C Operation《工作温度为90 ℃的电线和电缆的耐臭氧热塑性弹性体绝缘的标准规格》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D4246 02 (Reapproved 2010)D4246 14Standard Specification forOzone-Resistant Thermoplastic Elastomer Insulation ForWire and Cable, 90 C 90C Operation1This standard is issued under the fixed designation D4246; the number immediately following the designation indicates the year oforiginal
2、adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope Scope*1.1 This specification covers an ozone-resistant insulating compo
3、und for electrical wire and cables 14 AWG and larger. Thiscompound consists substantially of a thermoplastic elastomer.1.2 This type of insulation is considered suitable for continuous operation at conductor temperatures not exceeding 90 C 90Cin dry locations. Operating voltages are not to exceed 20
4、00 V. The minimum installation temperature is 40 C.is -40C.1.3 Whenever two sets of values are presented, in different units, the values in the first set are the standard, while those inparentheses are for information only.1.4 In many instances the insulation material cannot be tested unless it has
5、been formed around a conductor or cable. Therefore,tests are done on insulated wire or cable in this specification solely to determine the relevant property of the insulation materialand not to test the conductor or completed cable.2. Referenced Documents2.1 ASTM Standards:2D470 Test Methods for Cro
6、sslinked Insulations and Jackets for Wire and CableD1711 Terminology Relating to Electrical InsulationD2633 Test Methods for Thermoplastic Insulations and Jackets for Wire and Cable3. Terminology3.1 Definitions: DefinitionsFor definitions of terms used in this specification refer to Terminology D171
7、1.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nthe exposure of materials to air at 121 C 121C for 168 h.4. Physical Properties4.1 Requirements for physical properties are listed in Table 1.4.2 Thickness of InsulationTable 1(a), (Conductor Sizes, Insulation Thicknesses, a
8、nd AC Test Voltages for RubberInsulations) of Test Methods D470 lists the minimum average thickness for the insulation. The required minimum thickness is90 % of the specified average thickness.5. Electrical Requirements5.1 Order of TestingPerform the ac voltage, insulation resistance, and dc voltage
9、 tests in that order when any of these testsare specified. The sequence of other testing is not specified.5.2 AC Voltage TestUnless otherwise specified, omit this test if the dc voltage test described in 5.4 is to be performed. Testeach insulated conductor for 5 min at the ac voltage given in Table
10、1(a) (Conductor Sizes, Insulation Thicknesses, and AC TestVoltages, for Rubber Insulations) of Methods D470, under the columns labelledlabeled “Ozone-Resisting Insulations.”1 This specification is under the jurisdiction of ASTM Committee D09 on Electrical and Electronic Insulating Materials and is t
11、he direct responsibility of SubcommitteeD09.18 on Solid Insulations, Non-Metallic Shieldings and Coverings for Electrical and Telecommunication Wires and Cables.Current edition approved March 1, 2010Nov. 1, 2014. Published August 2010November 2014. Originally approved in 1983. Last previous edition
12、approved in 20022010as D4246D4246 02 (2010).02. DOI: 10.1520/D4246-02R10.10.1520/D4246-14.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summ
13、ary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends
14、 that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, We
15、st Conshohocken, PA 19428-2959. United States15.3 Insulation ResistanceThe insulated conductor shall have an insulation resistance value of at least that corresponding toa constant of 10 000 at 60 F (15.6 C).60F (15.6C).5.3.1 If the water temperature at the time measurement was made differs from 60
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD42462014STANDARDSPECIFICATIONFOROZONERESISTANTTHERMOPLASTICELASTOMERINSULATIONFORWIREANDCABLE90DEGCOPERATION

链接地址:http://www.mydoc123.com/p-516631.html