1、Designation: C1283 11C1283 15Standard Practice forInstalling Clay Flue Lining1This standard is issued under the fixed designation C1283; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parenth
2、eses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the minimum requirements for installing clay flue lining for residential concrete or masonry chimneys.1.2 The values stated in inch
3、-pound units are to be regarded as standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is
4、 the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C24 Test Method for Pyrometric Cone Equivalent (PCE) of Fireclay and High Alumina Refr
5、actory MaterialsC27 Classification of Fireclay and High-Alumina Refractory BrickC55 Specification for Concrete Building BrickC90 Specification for Loadbearing Concrete Masonry UnitsC99 Test Method for Modulus of Rupture of Dimension StoneC129 Specification for Nonloadbearing Concrete Masonry UnitsC1
6、70 Test Method for Compressive Strength of Dimension StoneC199 Test Method for Pier Test for Refractory MortarsC216 Specification for Facing Brick (Solid Masonry Units Made from Clay or Shale)C270 Specification for Mortar for Unit MasonryC315 Specification for Clay Flue Liners and Chimney PotsC652 S
7、pecification for Hollow Brick (Hollow Masonry Units Made From Clay or Shale)C896 Terminology Relating to Clay Products3. Terminology3.1 GeneralTerminology C896 should be used for clarification of definitions in this practice.3.2 Definitions of Terms Specific to This Standard:3.2.1 chimney connectort
8、ubular unit or pipe used to convey products of combustion from a heating or cooking appliance tothe chimney.3.2.2 fluepassageway within a chimney through which products of combustion are conveyed.3.2.3 flue linermanufactured tubular nonloadbearing fired clay unit, normally used for conveying hot gas
9、es in chimneys.3.2.4 masonry chimneyvertical structure constructed of brick, concrete, concrete masonry units, or stone, which contains oneor more flues, and conveys products of combustion from a heat source or cooking appliance.3.2.5 smoke chambersection of a fireplace above the throat and below th
10、e flue, which is an area of transition from the shapeof the throat to the shape of the flue.1 This practice is under the jurisdiction of ASTM Committee C04 on Vitrified Clay Pipe and is the direct responsibility of Subcommittee C04.20 on Methods of Test andSpecifications.Current edition approved Nov
11、. 1, 2011Dec. 1, 2015. Published November 2011December 2015. Originally approved in 1994. Last previous edition approved in 20072011as C1283 07a.C1283 11. DOI: 10.1520/C1283-11.10.1520/C1283-15.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at se
12、rviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version
13、. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International,
14、 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.6 thimblemanufactured tubular nonloadbearing fired clay unit normally used to connect the chimney connector from anappliance through the wall of the chimney to the flue.4. Footings and Foundations4.1 Footings fo
15、r masonry chimneys shall be constructed of concrete or solid masonry at least 12 in. (305 mm) thick, and it shallextend at least 6 in. (150 mm) beyond the face of the foundation or support wall on all sides. Footings shall be founded belowfrost depth on natural undisturbed earth or engineered fill.
16、In areas not subjected to freezing, footings shall be founded at least 12in. (305 mm) below finished grade.4.2 The foundation shall be placed, with respect to adjacent structures existing or anticipated, to minimize the possibility ofdamage by construction operations or by transmission of additional
17、 loads to the supporting soils.4.3 Concrete footings and foundations shall conform to local building codes.4.3.1 In the absence of a local building code, concrete with a minimum 28 day compressive strength of 3000 psi (21 MPa) shallbe used.4.4 Where a chimney or fireplace is added to the outside of
18、the exterior wall of an existing structure, the following shall apply:4.4.1 The new footing shall be installed at the same level or below the existing footing, provided the level is below the frostline and the new footing is placed on soil with adequate bearing capability.4.4.2 The existing drainage
19、 provision shall not be obstructed.5. Chimney Construction5.1 Materials:5.1.1 Flue LiningsSpecification C315.5.1.2 Refractory MortarTest Method C24 (cone 10) and Test Method C199 (medium duty and water insoluble).5.1.3 Concrete BlockSpecification C90 or Specification C129.5.1.4 BrickSpecification C5
20、5 or Specification C216, Grade SW.5.1.5 MortarSpecification C270.5.1.6 FirebrickClassification C27.5.1.7 Natural StoneTest Method C170 or Test Method C99.5.2 The chimney consists of a flue liner and the chimney wall. When used to vent a fireplace, the chimney is constructed directlyon the smoke cham
21、ber.5.3 The flue lining shall start from a point not less than 8 in. (205 mm) below the entrance of the lowest chimney connector.5.4 Flue liners shall be installed, each flue liner carefully bedded on the previous one, using water insoluble refractory mortarcomplying with Test Method C199 (medium du
22、ty). All joints of flue liners shall be 116 in. (1.6 mm) to 18 in. (3.2 mm) thick, andstruck flush so as to produce a straight, smooth, fully aligned flue. Liners shall be placed in such a manner as to minimize ledgesor steps within the flue passageway.5.5 Flue liners shall be maintained by filling
23、any voids in the interior, or hot face, with medium duty water insoluble refractorymortar conforming to Test Method C199.5.6 Flue liners shall be surrounded by masonry on all sides but shall not be bonded to the surrounding masonry. The flue linershall contact the chimney wall only as necessary for
24、support and alignment in order to permit the flue liner to expand and contractfreely. The separation of the flue liner from the surrounding concrete or masonry shall not exceed the wall thickness of the flueliner. Where seismic reinforcing requires the space between the flue liner and the chimney wa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC12832015STANDARDPRACTICEFORINSTALLINGCLAYFLUELINING 安装 粘土 烟道 内衬 标准 实施 规程 PDF

链接地址:http://www.mydoc123.com/p-464072.html