《ASTM B812-1996(2013) Standard Test Method for Resistance to Environmental Degradation of Electrical Pressure Connections Involving Aluminum and Intended for Residential Application.pdf》由会员分享,可在线阅读,更多相关《ASTM B812-1996(2013) Standard Test Method for Resistance to Environmental Degradation of Electrical Pressure Connections Involving Aluminum and Intended for Residential Application.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: B812 96 (Reapproved 2013)Standard Test Method forResistance to Environmental Degradation of ElectricalPressure Connections Involving Aluminum and Intended forResidential Applications1This standard is issued under the fixed designation B812; the number immediately following the designati
2、on indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONElectrical pressure connection syst
3、ems involving aluminum are those in which one or more of thecomponents of the system in the direct electrical path or carrying any electrical current is fabricatedof aluminum, including aluminum wires, aluminum bus bars, aluminum bolts, aluminum terminations,or any other aluminum current-carrying me
4、mber. Included are systems which must carry current forsafety purposes such as ground shields or straps attached to aluminum framing or other structuralmembers. Pressure connection systems can be evaluated by this test method. Such systems arecomprised of the wire or other structure being connected
5、and the means of connection, any elementof which is made of aluminum.Connection systems tested are exposed sequentially to ambients of high relative humidity andtemperature cycles of 75C, such as may be encountered by some connections in actual residentialapplications. Periodic observation of the po
6、tential drop across the connection interfaces while carryingrated current provides a measurement of connection performance.1. Scope1.1 This test method covers all residential pressure connec-tion systems. Detailed examples of application to specific typesof connection systems, set-screw neutral bus
7、connectors andtwist-on wire-splicing connectors, are provided in AppendixX1 and Appendix X2.1.2 The purpose of this test method is to evaluate theperformance of residential electrical pressure connection sys-tems under conditions of cyclic temperature change (withinrating) and high humidity.1.3 The
8、limitations of the test method are as follows:1.3.1 This test method shall not be considered to confirm aspecific lifetime in application environments.1.3.2 The applicability of this test method is limited topressure connection systems rated at or below 600 V d-c or a-cRMS.1.3.3 This test method is
9、limited to temperature and watervapor exposure in addition to electrical current as required tomeasure connection resistance.1.3.4 This test method does not evaluate degradation whichmay occur in residential applications due to exposure of theelectrical connection system to additional environmental
10、con-stituents such as (but not limited to) the following examples:1.3.4.1 Household chemicals (liquid or gaseous) such asammonia, bleach, or other cleaning agents.1.3.4.2 Chemicals as may occur due to normal hobby orprofessional activities such as photography, painting, sculpture,or similar activiti
11、es.1.3.4.3 Environments encountered during construction orremodeling such as direct exposure to rain, uncured wetconcrete, welding or soldering fluxes and other agents.1.3.5 This test method is limited to evaluation of pressureconnection systems.1.4 This standard does not purport to address all of t
12、hesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to become familiarwith all hazards including those identified in the appropriateMaterial Safety Data Sheet (MSDS) for this product/materialas provided by the manufacturer, to establish appropriat
13、esafety and health practices, and determine the applicability ofregulatory limitations prior to use.1.5 This standard should be used to measure and describethe properties of materials, products, or assemblies in responseto electrical current flow under controlled laboratory condi-tions and should no
14、t be used to describe or appraise the fire1This test method is under the jurisdiction of ASTM Committee B02 onNonferrous Metals and Alloys and is the direct responsibility of SubcommitteeB02.11 on Electrical Contact Test Methods.Current edition approved Aug. 1, 2013. Published August 2013. Originall
15、yapproved in 1990. Last previous edition approved in 2008 as B812 96 (2008).DOI: 10.1520/B0812-96R13.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1hazard or fire risk of materials, products, or assemblies underactual installation co
16、nditions or under actual fire conditions.However, results of this test may be used as elements of a firerisk assessment which takes into account all of the factorswhich are pertinent to an assessment of the fire hazard of aparticular end use.2. Referenced Documents2.1 ASTM Standards:2B542 Terminolog
17、y Relating to Electrical Contacts and TheirUse2.2 Underwriter Laboratory Standards:UL486B Standard for Wire Connectors For Use With Alu-minum Conductors, ANSI/UL 486B3UL486C Standard for Splicing Wire Connectors32.3 NEC Document:ANSI/NFPA 70 National Electric Code43. Terminology3.1 residential appli
18、cations, nresidential applications arethose involving a structure or vehicle used entirely for perma-nent or temporary human habitation. Included are homes(single or multiple-unit houses and mobile or modularstructures), motels, hotels, dormitories, hospitals, rest homes,and recreational vehicles. E
19、xcluded are railroad cars, boats,airplanes, nonresidential, commercial (office buildings, stores)and industrial applications (factories, warehouses).3.2 pressure connection system, nan electrical connectionintended to carry current between components or conductors incontact under mechanical pressure
20、.3.2.1 DiscussionThe mechanical pressure may be appliedby clamping, tightening of threaded components, spring force,crimping, swaging, or other means. For the purpose of the testprocedure, the connection system consists of all componentsnormally present in the application, including both current-car
21、rying and other metallic components, and non-metalliccomponents (insulators, insulation, protective boots or sleeve,etc.). Also see definition of “Connection, Pressure(Solderless),” in Article 100 of reference noted in Section 2.3(NEC).3.3 aluminum, nas the term “aluminum,” the material ofwhich cond
22、uctors (wire, cable, busbars, etc.), connectioncomponents, and test board components may be made, includesaluminum metal and its alloys.3.4 reference conductor, na continuous length of the sameconductor material (wire, cable, busbar, etc.) incorporated inthe connection system being tested by being m
23、ounted on thesame test board assembly and connected in the same seriescircuit.3.5 reference connection system, nthe reference connec-tion system is the same connection system as that which isunder evaluation, but which is exposed only to a dry environ-ment at normal room temperature.4. Summary of Te
24、st Method4.1 The environmental exposure of the connections testedconsists of weekly sequences consisting of five thermal cyclesof 75C temperature change (taking a maximum of8htoaccomplish), followed by exposure for the balance of the weekto conditions at or near 100 % relative humidity at roomtemper
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB81219962013STANDARDTESTMETHODFORRESISTANCETOENVIRONMENTALDEGRADATIONOFELECTRICALPRESSURECONNECTIONSINVOLVINGALUMINUMANDINTENDEDFORRESIDENTIALAPPLICATIONPDF

链接地址:http://www.mydoc123.com/p-462361.html