ASHRAE OR-05-11-3-2005 Evaluation of a Ventilation Heat Pump for Small Commercial Buildings《小型商业大厦通风热泵的评价》.pdf
《ASHRAE OR-05-11-3-2005 Evaluation of a Ventilation Heat Pump for Small Commercial Buildings《小型商业大厦通风热泵的评价》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE OR-05-11-3-2005 Evaluation of a Ventilation Heat Pump for Small Commercial Buildings《小型商业大厦通风热泵的评价》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、OR-05- 1 1-3 Evaluation of a Ventilation Heat Pump for Small Commercial Buildings Kevin B. Mercer Associate Member ASHRAE ABSTRACT Air-to-air energy recovery can be used to reduce ventila- tion loads for small commercial buildings. Enthalpy exchang- ers are one approach to energy recovery that is co
2、mmonly employed. An alternative technology involves the use of a heat pump that operates between the ventilation and exhaust streams. In this papec the performance of a ventilation heat pump heat recovery unit was studied through simulation. A model of the heat pump was developed and validated using
3、 manufacturers and laboratory test data. This component model was then incorporated within a system simulation to investigate operating cost savings for the heat pump relative to a buse case that does not employ energy recovery but utilizes jxed minimum ventilation rates with an enthalpy economizer.
4、 The operating costs were found to begreater than the base case in moderate climates with relatively small savings in more extreme climates (hot or cold). The performance is not compet- itive with the performance of enthalpy exchangers or demand- controlled ventilation. The breakeven ambient conditi
5、onsfor positive savings utilizing a ventilation heat pump were also investigated. The primary performance penalties associated with the use of a heat pump are added fan and compressor power consumption, along with lost economizer savings. INTRODUCTION For many small commercial buildings, the ventila
6、tion airstream can contribute up to 40% of the building thermal load (ASHRAE 1993). The ventilation airstream is necessary to satisfy the indoor air quality (IAQ) requirements associated with ASHRAE Standard 62-2001. Several new technologies have been introduced to the market for preconditioning the
7、 fresh airstream and reducing primary equipment power James E. Braun, PhD, PE Member ASHRAE consumption. Heat pipes, run-around loops, enthalpy exchangers, and, most recently, heat pump heat recovery have all been introduced as alternative technologies. The investiga- tion described in this paper ev
8、aluates the performance of a heat pump heat recovery (HPHR) system for ventilation air pretreatment. During the cooling season, the ventilation heat pump operates to cool and possibly dehumidify outside air entering the primary rooftop unit (RTU). Heat is rejected from the heat pump into the exhaust
9、 airstream from the building. This exhaust air in turn cools the condenser coil at a lower temper- ature than the ambient. During the heating season, the heat pump operates in reverse to extract heat from the exhaust air and preheat the outside air. Figure 1 illustrates the location of the ventilati
10、on, exhaust, mixed, and return air conditions for a ventilation heat pump. The mixed air is further conditioned with a primary rooftop unit. Generally, the exhaust air is cooler than the ventilation air during the cooling season and warmer than the ventilation air during the heating season. Therefor
11、e, the heat pump operates very efficiently in both cooling and heating modes, and its COP should actually increase as the conditions become more extreme (i.e., more hot and humid for cooling and colder for heating). The heat pump requires an added exhaust an for circu- lating exhaust air. A ventilat
12、ion fan may also be required if the added static pressure of an extra heat exchanger is too high for the RTU supply fan to overcome. The heat pump is designed to be a retrofit to an existing RTU and, as such, all results presented assume a retrofit application. For new designs, the primary RTU could
13、 be downsized because of the addition of the heat pump. Kevin B. Mercer is a product development engineer at Modine Manufacturing Company, Racine, Wisconsin. James E. Braun is a professor of mechanical engineering at Ray W. Hemck Laboratories, Purdue University, West Lafayette, Indiana. 890 02005 AS
14、HRAE. Cooline Mode Ventilation - Exhaust Heatine Mode - Mixed i Ventilation Qm$ Figure I Heut pump conjgurution und operution with u rooftop unit. Heat pump heat recovery is a relatively new technology for application to ventilation air pretreatment and only a few studies have been published that re
15、late to this technology. Riffat and Gillott (2002) tested a revolving heat pipe ventila- tion heat pump system. The authors found an annual energy savings to exist for certain applications. However, the authors noted lower motor and compressor power would still be neces- sary to justi commercial imp
16、lementation of such a system. Another study conducted by Fehrm et al. (2002) addressed exhaust air heat pumps for markets in Sweden and northern Germany. The authors found an exhaust air heat pump reduced energy consumption and peak demand by as much as 20% when compared to a conventional gas-fired
17、boiler. The goal of the study described in this paper was to provide an assessment of heat pump heat recovery technology. A heat pump model was developed based on manufacturers and test data from a sample unit. The model was validated and then implemented into a ventilation strategy assessment tool
18、(VSAT) for analyzing performance (Braun and Mercer 2003). Annual cost savings were evaluated for a range of buildings and climates and compared with savings associated with alter- native technologies for reducing ventilation loads. The breakeven ambient conditions for positive savings with appli- ca
19、tion of a ventilation heat pump were also investigated. LAB TEST SETUP The ventilation heat pump was installed in the outdoor room of an arrangement of psychrometric chambers. The unit was set up for operation between controlled ambient and exhaust airstreams, as shown in Figure 2. In order to provi
20、de the correct air flow velocity for reading pressure drop and relative humidity, a 12x10 inch duct was selected to connect the outdoor and indoor rooms for both the supply and exhaust airstreams. The heat pump was fitted with two switches for managing operation. One switch controlled fan power and
21、the other switch was a toggle between cooling and heating mode. In order to change the fan speeds, a wire setting located on the supply and exhaust air fan was adjusted. The outside air damper was maintained at the factory default Figure 2 Intilution heat pump. setting of 45“ throughout testing. A d
22、rain pan was also fabri- cated to collect any condensate. In order to measure tempera- ture, four thermocouple grids were placed at the ends of each duct section and at the air intake entrance to the heat pump. The temperature data points were then averaged to get an over- all reading. The rated acc
23、uracy of the thermocouple measure- ments was f O. I “C. Two pitot tube arrays, consisting of five pitot tubes each, were constructed to evenly traverse the open cross-sectional area of the supply and exhaust air ducts. These arrays provided a reasonably accurate pressure difference for calculating a
24、ir flow velocity. A voltage output of O to 5 volts DC equated to a velocity pressure range of O to O. 1 in. H,O. Humidity in each airstream was measured using a chilled- mirror dew-point meter and then checked against a reading from a portable thermo-hygrometer. The hygrometer had an accuracy of *3%
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEOR051132005EVALUATIONOFAVENTILATIONHEATPUMPFORSMALLCOMMERCIALBUILDINGS 小型 商业 大厦 通风 评价 PDF

链接地址:http://www.mydoc123.com/p-455596.html