ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 18-2012 VARIABLE REFRIGERANT FLOW.pdf
《ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 18-2012 VARIABLE REFRIGERANT FLOW.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC SYSTEMS AND EQUIPMENT IP CH 18-2012 VARIABLE REFRIGERANT FLOW.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、18.1CHAPTER 18VARIABLE REFRIGERANT FLOWStandards 18.3Equipment 18.4VRF Heat Pump System Operation. 18.4Design Considerations . 18.7VRF System Design Example . 18.8ARIABLE-refrigerant-flow (VRF) HVAC systems are aVdirect-expansion (DX) heat pump technology platform builton the standard reverse Rankin
2、e vapor compression cycle. Thesesystems are thermodynamically similar to unitary and other com-mon DX systems, and share many of the same components (i.e.,compressor, expansion device, and heat exchangers). VRF sys-tems transport heat between an outdoor condensing unit and a net-work of indoor units
3、 located near or within the conditioned spacethrough refrigerant piping installed in the building. Attributes thatdistinguish VRF from other DX system types are multiple indoorunits connected to a common outdoor unit (single or combinedmodules), scalability, variable capacity, distributed control, a
4、ndsimultaneous heating and cooling.VRF systems are highly engineered, with single or multiple com-pressors, multiple indoor units (ducted and nonducted types), andoil and refrigerant management and control components. VRF pro-vides flexibility by allowing for many different indoor units (withdiffere
5、nt capacities and configurations), individual zone control,and the unique ability to offer simultaneous heating and cooling inseparate zones on a common refrigerant circuit, and heat recoveryfrom one zone to another. Typical capacities range from 18,000 to760,000 Btu/h for outdoor units and from 500
6、0 to 120,000 Btu/h forindoor units.Many VRF systems are equipped with at least one variable-speedand/or variable-capacity compressor. Figure 1 illustrates capacitycontrol of a single variable-speed compressor; the compressor var-ies its speed to operate only at the levels necessary to maintainindoor
7、 environments to the specified requirements.System TypesThere are three basic types of VRF systems: cooling only (Figure2), heat pump (Figure 2), and heat recovery (see Figures 3 and 4).Heat pumps are air-conditioning systems capable of reversing thedirection of the refrigerant flow to provide heati
8、ng or cooling to theindoor space. All indoor units connected to a heat pump system canuse individual control and set points, but they operate in the samemode of either heating or cooling at any given time.Heat recovery units are heat pump systems that can providesimultaneous heating and cooling. All
9、 indoor units connected to aheat recovery system not only can use individual control and setpoints, but they can also individually operate in heating or coolingmode at any given time. To match the buildings load profiles,energy is transferred from one indoor space to another through therefrigerant l
10、ine, and only one energy source is necessary to provideboth heating and cooling. VRF systems also operate efficiently atpart load because of the compressors variable capacity control.Note: Figures 2 to 4 represent various methods of VRF systempiping configurations. Please refer to each manufacturers
11、 data forspecifics.The following definitions are based on AHRI Standard 1230.A heat pump multisplit system is an encased, factory-made,permanently installed assembly that takes heat from a heat sourceThe preparation of this chapter is assigned to TC 8.7, Variable RefrigerantFlow.Fig. 1 Compressor Fr
12、equencyFig. 2 Cooling-Only Heat Pump VRF SystemFig. 3 Two-Pipe Heat Recovery VRF System18.2 2012 ASHRAE HandbookHVAC Systems and Equipment and delivers it to the conditioned space when heating is desired. Itmay remove heat from the conditioned space and discharge it to aheat sink if cooling and dehu
13、midification are desired from the sameequipment. Normal components include multiple indoor condition-ing coils, compressor(s), and outdoor coil(s). Equipment may be pro-vided in multiple assemblies, intended for use together. Otherfunctions may include cleaning, circulating, and humidifying the air.
14、A VRF multisplit system is a split-system air conditioner or heatpump with a single refrigerant circuit, one or more outdoor units, atleast one variable-speed compressor or other compressor combina-tion that can vary system capacity by three or more steps, and multipleindoor fan-coil units that are
15、individually metered and individuallycontrolled by an integrated control device and common communica-tions network. A VRF heat recovery multisplit system operates asan air conditioner or as a heat pump, and also can provide simultane-ous heating and cooling operation by transferring recovered energy
16、from the indoor units operating in one mode to other indoor unitsoperating in the other mode. Variable refrigerant flow implies three ormore steps of control on common, interconnecting piping.VRF ApplicationsVRF systems can be used in various applications, such asHigh- or low-rise officesEducational
17、 facilities (schools, universities)Health care facilities, including clinics and long-term-care nurs-ing homesMultiple-tenant residential buildingsRetail storesHospitality centers, restaurants, banquet halls, hotels, and motelsData center cooling-only applicationsCultural facilities, including relig
18、ious centersZoned Comfort ControlVRF systems achieve temperature control on a zone-by-zonebasis primarily by using refrigerant-side control. Indoor unitsconstantly react to changes in the zones heating/cooling loads,and maintain conditions by controlling target superheat with anelectronic expansion
19、valve (EEV) or a linear expansion valve (LEV).The inverter compressors or combination of inverter and constant-speed compressors generally found in VRF systems modulate refrig-erant flow, and work in unison with the refrigerant volume requiredby the indoor units.Maintaining comfort conditions effici
20、ently can be challenging forHVAC systems during the “shoulder” seasons, usually periods dur-ing fall and spring when both heating and cooling maybe required.The ideal changeover from predominantly heating operation to pre-dominantly cooling operation, or vice versa, is often determined bya preset ou
21、tdoor ambient temperature. Many traditional unitaryHVAC systems operate heating and cooling systems simultaneouslyfor extended periods during shoulder seasons, providing heating andcooling through a four-pipe network. With decentralized systemssuch as VRF, buildings can be zoned so that switchover i
22、s seamlessand comfort is maintained.Indoor Air QualityIndoor air quality (IAQ) provided by an HVAC system dependson the design zone air change rate, level of ventilation air supplied,and degree of airflow filtration. VRF systems, like traditional unitarysystems, must follow associated filtration lev
23、els outlined in ASH-RAE Standard 62.1 for ventilation, with filtration provided eithercentrally, if using a cooling coil, and/or at zone level, if higher levelsof filtration are required beyond that provided by the central unit.To meet ASHRAE Standard 62.1 requirements, VRF systems arefrequently int
24、egrated with a dedicated outdoor air system (DOAS)where ventilation airflow delivery rates remain consistent, regard-less of the zones peak heating or cooling loads or the minimumdamper (variable-air-volume terminal unit or central air-handlingunit) position.Annual Operating Efficiency Characteristi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACSYSTEMSANDEQUIPMENTIPCH182012VARIABLEREFRIGERANTFLOWPDF

链接地址:http://www.mydoc123.com/p-455041.html