ASHRAE FUNDAMENTALS IP CH 18-2017 Nonresidential Cooling and Heating Load Calculations.pdf
《ASHRAE FUNDAMENTALS IP CH 18-2017 Nonresidential Cooling and Heating Load Calculations.pdf》由会员分享,可在线阅读,更多相关《ASHRAE FUNDAMENTALS IP CH 18-2017 Nonresidential Cooling and Heating Load Calculations.pdf(66页珍藏版)》请在麦多课文档分享上搜索。
1、18.1CHAPTER 18NONRESIDENTIAL COOLING AND HEATING LOAD CALCULATIONSCooling Load Calculation Principles 18.1Internal Heat Gains . 18.3Infiltration and Moisture Migration Heat Gains . 18.14Fenestration Heat Gain . 18.16Heat Balance Method 18.16Radiant Time Series (RTS) Method 18.22Heating Load Calculat
2、ions 18.30System Heating and Cooling Load Effects. 18.41Example Cooling and Heating Load Calculations 18.44Previous Cooling Load Calculation Methods 18.57Building Example Drawings 18.61EATING and cooling load calculations are the primary designHbasis for most heating and air-conditioning systems and
3、 com-ponents. These calculations affect the size of piping, ductwork, dif-fusers, air handlers, boilers, chillers, coils, compressors, fans, andevery other component of systems that condition indoor environ-ments. Cooling and heating load calculations can significantly affectfirst cost of building c
4、onstruction, comfort and productivity of occu-pants, and operating cost and energy consumption.Simply put, heating and cooling loads are the rates of energyinput (heating) or removal (cooling) required to maintain an indoorenvironment at a desired temperature and humidity condition. Heat-ing and air
5、 conditioning systems are designed, sized, and controlledto accomplish that energy transfer. The amount of heating or coolingrequired at any particular time varies widely, depending on external(e.g., outdoor temperature) and internal (e.g., number of peopleoccupying a space) factors.Peak design heat
6、ing and cooling load calculations, which are thischapters focus, seek to determine the maximum rate of heating andcooling energy transfer needed at any point in time. Similar princi-ples, but with different assumptions, data, and application, can beused to estimate building energy consumption, as de
7、scribed in Chap-ter 19.This chapter discusses common elements of cooling load calcula-tion (e.g., internal heat gain, ventilation and infiltration, moisturemigration, fenestration heat gain) and two methods of heating andcooling load estimation: heat balance (HB) and radiant time series(RTS).1. COOL
8、ING LOAD CALCULATION PRINCIPLESCooling loads result from many conduction, convection, and radi-ation heat transfer processes through the building envelope and frominternal sources and system components. Building components orcontents that may affect cooling loads include the following:External: Wall
9、s, roofs, windows, skylights, doors, partitions, ceil-ings, and floorsInternal: Lights, people, appliances, and equipmentInfiltration: Air leakage and moisture migrationSystem: Outdoor air, duct leakage and heat gain, reheat, fan andpump energy, and energy recovery1.1 TERMINOLOGYThe variables affect
10、ing cooling load calculations are numerous,often difficult to define precisely, and always intricately interrelated.Many cooling load components vary widely in magnitude, and pos-sibly direction, during a 24 h period. Because these cyclic changes inload components often are not in phase with each ot
11、her, each compo-nent must be analyzed to establish the maximum cooling load for abuilding or zone. A zoned system (i.e., one serving several indepen-dent areas, each with its own temperature control) needs to provide nogreater total cooling load capacity than the largest hourly sum ofsimultaneous zo
12、ne loads throughout a design day; however, it musthandle the peak cooling load for each zone at its individual peak hour.At some times of day during heating or intermediate seasons, somezones may require heating while others require cooling. The zonesventilation, humidification, or dehumidification
13、needs must also beconsidered.Heat Flow RatesIn air-conditioning design, the following four related heat flowrates, each of which varies with time, must be differentiated.Space Heat Gain. This instantaneous rate of heat gain is the rateat which heat enters into and/or is generated within a space. Hea
14、t gainis classified by its mode of entry into the space and whether it is sen-sible or latent. Entry modes include (1) solar radiation through trans-parent surfaces; (2) heat conduction through exterior walls and roofs;(3) heat conduction through ceilings, floors, and interior partitions;(4) heat ge
15、nerated in the space by occupants, lights, and appliances;(5) energy transfer through direct-with-space ventilation and infiltra-tion of outdoor air; and (6) miscellaneous heat gains. Sensible heat isadded directly to the conditioned space by conduction, convection,and/or radiation. Latent heat gain
16、 occurs when moisture is added tothe space (e.g., from vapor emitted by occupants and equipment). Tomaintain a constant humidity ratio, water vapor must condense on thecooling apparatus and be removed at the same rate it is added to thespace. The amount of energy required to offset latent heat gain
17、essen-tially equals the product of the condensation rate and latent heat ofcondensation. In selecting cooling equipment, distinguish betweensensible and latent heat gain: every cooling apparatus has differentmaximum removal capacities for sensible versus latent heat for par-ticular operating conditi
18、ons. In extremely dry climates, humidifica-tion may be required, rather than dehumidification, to maintainthermal comfort.Radiant Heat Gain. Radiant energy must first be absorbed by sur-faces that enclose the space (walls, floor, and ceiling) and objects inthe space (furniture, etc.). When these sur
19、faces and objects becomewarmer than the surrounding air, some of their heat transfers to the airby convection. The composite heat storage capacity of these surfacesand objects determines the rate at which their respective surfacetemperatures increase for a given radiant input, and thus governs there
20、lationship between the radiant portion of heat gain and its corre-sponding part of the space cooling load (Figure 1). The thermal stor-age effect is critical in differentiating between instantaneous heatgain for a given space and its cooling load at that moment. PredictingThe preparation of this cha
21、pter is assigned to TC 4.1, Load Calculation Dataand Procedures.18.2 2017 ASHRAE HandbookFundamentals the nature and magnitude of this phenomenon to estimate a realisticcooling load for a particular set of circumstances has long been ofinterest to design engineers; the Bibliography lists some early
22、workon the subject.Space Cooling Load. This is the rate at which sensible and latentheat must be removed from the space to maintain a constant spaceair temperature and humidity. The sum of all space instantaneousheat gains at any given time does not necessarily (or even fre-quently) equal the coolin
23、g load for the space at that same time.Space Heat Extraction Rate. The rates at which sensible andlatent heat are removed from the conditioned space equal the spacecooling load only if the room air temperature and humidity are con-stant. Along with the intermittent operation of cooling equipment,con
24、trol systems usually allow a minor cyclic variation or swing inroom temperature; humidity is often allowed to float, but it can becontrolled. Therefore, proper simulation of the control system givesa more realistic value of energy removal over a fixed period thanusing values of the space cooling loa
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEFUNDAMENTALSIPCH182017NONRESIDENTIALCOOLINGANDHEATINGLOADCALCULATIONSPDF

链接地址:http://www.mydoc123.com/p-454712.html