VA 23 21 11-2011 BOILER PLANT PIPING SYSTEMS.pdf
《VA 23 21 11-2011 BOILER PLANT PIPING SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《VA 23 21 11-2011 BOILER PLANT PIPING SYSTEMS.pdf(43页珍藏版)》请在麦多课文档分享上搜索。
1、09-11 23 21 11 - 1 SECTION 23 21 11 BOILER PLANT PIPING SYSTEMS SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable to the project and renumber the paragraphs. 2. References to pressure in this section are gage pressure unless
2、 otherwise noted. PART 1 GENERAL: 1.1 DESCRIPTION: All boiler plant piping systems, except plumbing and sanitary, including piping supports. Piping located outside of the boiler plant building is not included except for gas regulator and meter stations. 1.2 RELATED WORK: /A. Section 13 05 41, SEISMI
3、C RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS./ B. Section 23 05 10, COMMON WORK RESULTS FOR Boiler Plant and STEAM GENERATION C. Section 23 05 51, NOISE and VIBRATION CONTROL FOR BOILER PLANT. D. Section 23 07 11, HVAC and BOILER PLANT INSULATION. E. Section 22 05 23, GENERAL-DUTY VALVES F
4、OR PLUMBING PIPING. F. Section 22 31 11, WATER SOFTENERS. G. Section 22 67 21, WATER DEALKALIZING SYSTEM. H. Fuel oil tanks and piping: Section 23 10 00, FACILITY FUEL SYSTEMSS. I. Control valves: Section 23 52 39, FIRE-TUBE BOILERS. J. Control valves: Section 23 52 33, WATER-TUBE BOILERS. K. Contro
5、l valves: Section 23 50 11, BOILER PLANT MECHANICAL EQUIPMENT. L. Flow Meters: Section 23 09 11, INSTRUMENTATION and CONTROL FOR BOILER PLANT. M. Section 23 08 11, DEMONSTRATIONS and TESTS FOR BOILER PLANT. N. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS. Requirements for commissioning, systems r
6、eadiness checklists, and training 1.3 QUALITY ASSURANCE: A. Entire installation shall comply with ASME Power Piping Code, ASME B31.1 and appendices. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 23 21 11 - 2 B. Boiler External Piping, as defi
7、ned in the ASME Boiler and Pressure Vessel Code, Section I, is required to be constructed and inspected in conformance with the ASME Code. C. Mechanics shall be skilled in their work or trade. Welders on pressure vessels or piping shall show evidence of qualification in accordance with the ASME Powe
8、r Piping Code and the ASME Boiler and Pressure Vessel Code. Certify that each welder has passed American Welding Society (AWS) qualification tests for the welding processes involved, and that certification is current. Each welder shall utilize a stamp to identify all work performed by the welder. Th
9、e Government reserves the right to reject any personnel found unqualified in the performance of work for which they are employed. 1.4 SUBMITTALS: A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Piping: 1. ASTM material specification number. 2. Grade, class
10、 or type, schedule number. 3. Manufacturer. C. Pipe Fittings, Unions, Flanges: 1. ASTM material specification number. 2. ASME standards number. 3. Catalog cuts. 4. Pressure and temperature ratings. D. Valves - Gate, Globe, Check, Plug, Butterfly, Ball: 1. Catalog cuts showing design and construction
11、. 2. Pressure and temperature ratings. 3. Materials of construction. 4. Accessories. E. Sight flow indicators: 1. Catalog cuts showing design and construction. 2. Pressure and temperature ratings. 3. Materials of construction. F. Quick-Couple Hose Connectors and Steam Hose: 1. Catalog cuts showing d
12、esign and construction. 2. Pressure and temperature ratings. 3. Materials of construction. 4. Type of seal between couplings. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 23 21 11 - 3 5. Flexibility of steam hose. G. Pressure Reducing and Re
13、gulating Valves, Back Pressure Relief Valves, Safety Valves, Relief Valves: 1. Catalog cuts showing design and construction. 2. Service limitations (type of fluid, maximum pressure and temperatures). 3. Materials of construction. 4. Flow capacity at required set pressure. 5. Predicted sound levels,
14、at operating condition, for steam pressure reducing valves. H. Strainers: 1. Catalog cuts showing design and construction. 2. Pressure and temperature ratings. 3. Materials of construction. 4. Strainer basket or liner mesh. 5. Pressure loss and flow rate data. I. Emergency Gas Safety Shutoff Valves,
15、 Automatic Earthquake Gas Valves: 1. Catalog cuts showing design and construction. 2. Maximum pressure rating. 3. Material of construction. 4. Pressure loss and flow rate data. J. Steam Traps: 1. Catalog cuts showing design and construction. 2. Service limitations (maximum pressures and temperatures
16、). 3. Materials of construction. 4. Flow rates at differential pressures shown on drawings. 5. Orifice size for each trap. K. Flexible Connectors: 1. Catalog cuts showing design and construction. 2. Pressure and temperature ratings. 3. Materials of construction. 4. Maximum allowable lateral and axia
17、l movements. 5. Description of type of movement permitted, intermittent offset or continuous vibration. L. Pipe Support Systems: 1. Credentials of technical personnel who will design the support systems. 2. Validation of computer program for pipe support selection. Provided by IHSNot for ResaleNo re
18、production or networking permitted without license from IHS-,-,-09-11 23 21 11 - 4 3. Input and output data for pipe support selection program for all piping systems with pipe sizes 60 mm (2-1/2 inches) and above. 4. Boiler and feedwater deaerator steam nozzle (pipe connection) allowable and actual
19、forces and moments imposed by connecting piping. 5. Hanger load calculation methods and results for piping systems with pipe sizes 50 mm (2 inches) and below. 6. Piping layouts showing location and type of each hanger and support. 7. Catalog cuts showing design and construction of each hanger and su
20、pport and conformance of hangers and supports to MSS standards. 8. Drawings showing arrangement and sizes of all components comprising each spring-type hanger and support assembly. 9. Load rating and movement tables for all spring hangers, and seismic shock absorbing devices. 1.5 PRODUCT DELIVERY, S
21、TORAGE AND HANDLING: All piping shall be stored and kept free of foreign material and shall be internally and externally cleaned of all oil, dirt, rust and foreign material. Deliver and store valves and pipe hangers in sealed shipping containers with labeling in place. Storage must be in dry, protec
22、ted location. SPEC WRITER NOTE: Fill blank spaces within this paragraph. Specification is based on high pressure saturated steam, 110 to 1025 kPa (16 - 150 psi), main header pressure in the boiler plant. The entire specification must be revised if header pressures are significantly lower or higher.
23、1.6 INFORMATION ON PRESSURE-TEMPERATURE DESIGN OF PIPING SYSTEMS: A. Steam service pressures are selected to provide optimum pressure to the facilities served by the boiler plant. Main steam header pressure shall be controlled at _kPa (_psi). Maximum pressure capability of steam systems between boil
24、ers and through first pressure reducing valve protected by a safety valve shall be governed by the pressure/temperature relationship of the highest safety valve setting shown for the boilers. B. Steam distribution systems protected by safety valves following pressure reducing stations or protected b
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2321112011BOILERPLANTPIPINGSYSTEMSPDF