1、09-11 23 09 23 - 1 SECTION 23 09 23 DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC SPEC WRITER NOTES: 1. Delete between / - / if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 2. Engineer shall provide control schematics, operati
2、ng sequences, DDC Control object lists, and Gateway Interoperability Schedules on the drawings. 3. Control schematics shall describe each HVAC system. For example schematics shall be provided for the chilled water system, the heating water system, the condenser water system, each air handling system
3、, the lab exhaust system, the general exhaust system, etc. 4. Operating sequences shall be written in the component style: it shall include descriptions of how each component behaves in each operating mode. 5. The DDC control object list shall include for each “point name” the following columns: har
4、dware point/ analog input, hardware point/analog output, hardware point/binary input, hardware point/binary output, software point/analog value, software point/ binary value, software point schedule, trending (interval or differential value or change of value), and if the point should appear on a gr
5、aphic. 6. The gateways interoperability schedules shall include for each device access through the gateway a listing of all of the BIBBs required through the gateway. PART 1 - GENERAL 1.1 DESCRIPTION A. Provide (a) direct-digital control system(s) as indicated on the project documents, point list, i
6、nteroperability tables, drawings and as described in these specifications. Include a complete and working direct-digital control system. Include all engineering, programming, controls and installation materials, installation labor, commissioning and start-up, training, final project documentation an
7、d warranty. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 23 09 23 - 2 1. The direct-digital control system(s) shall consist of high-speed, peer-to-peer network of DDC controllers, a control system server, and an Engineering Control Center. P
8、rovide a remote user using a standard web browser to access the control system graphics and change adjustable setpoints with the proper password. 2. The direct-digital control system(s) shall be native BACnet. All new workstations, controllers, devices and components shall be listed by BACnet Testin
9、g Laboratories. All new workstations, controller, devices and components shall be accessible using a Web browser interface and shall communicate exclusively using the ASHRAE Standard 135 BACnet communications protocol without the use of gateways, unless otherwise allowed by this Section of the techn
10、ical specifications, specifically shown on the design drawings and specifically requested otherwise by the VA. SPEC WRITER NOTE: Gateways, if used, shall be of sufficient quantity, capacity, and processing speed to allow for extensive trending and controller-level adjustment of controlled devices in
11、 VA healthcare and lab facilities. Gateways, if used, shall be of sufficient quantity, capacity, and processing speed to allow for limited trending and supervisory-level adjustment of controlled devices in other VA facilities. a. If used, gateways shall support the ASHRAE Standard 135 BACnet communi
12、cations protocol. SPEC WRITER NOTE: Design engineer shall indicate on drawings interoperability schedules for each gateway. The interoperability schedules shall include the following information: for each device access through the gateway, list all of the BACnet Interoperability Building Blocks (BIB
13、Bs) required for adequate interoperability. See ASHRAE Standard 135, Annex K for a description of available BIBBs. b. If used, gateways shall provide all object properties and read/write services shown on VA-approved interoperability schedules. SPEC WRITER NOTE: Gateways are often used to interface
14、with the internal controls of engineered equipment or systems such as chillers, packaged rooftop air conditioners, skid-mounted pressure Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 23 09 23 - 3 booster pump systems and similar. Engineer sha
15、ll investigate those internal controls, and make sure that those internal controls do not control other pieces of equipment, such as the start/stop of chilled water pumps, condenser water pumps or cooling towers. Deferring control of equipment external to the equipment viewed through the gateway imp
16、oses undue problems on troubleshooting the HVAC systems controls. 3. The work administered by this Section of the technical specifications shall include all labor, materials, special tools, equipment, enclosures, power supplies, software, software licenses, Project specific software configurations a
17、nd database entries, interfaces, wiring, tubing, installation, labeling, engineering, calibration, documentation, submittals, testing, verification, training services, permits and licenses, transportation, shipping, handling, administration, supervision, management, insurance, Warranty, specified se
18、rvices and items required for complete and fully functional Controls Systems. 4. The control systems shall be designed such that each mechanical system shall operate under stand-alone mode. The contractor administered by this Section of the technical specifications shall provide controllers for each
19、 mechanical system. In the event of a network communication failure, or the loss of any other controller, the control system shall continue to operate independently. Failure of the ECC shall have no effect on the field controllers, including those involved with global strategies. SPEC WRITER NOTE: E
20、dit the number of Engineering Control Center (ECC) workstation locations and web-based users in the paragraph below after discussing with the VA facility. The VA typically has only one ECC in each facility. 5. The control system shall accommodate / 1 / 2 / Engineering Control Center(s) and the contr
21、ol system shall accommodate / 5 / 10 / 20 / web-based Users simultaneously, and the access to the system should be limited only by operator password. B. Some products are furnished but not installed by the contractor administered by this Section of the technical specifications. The contractor admini
22、stered by this Section of the technical specifications shall formally coordinate in writing and receive from other contractors Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-09-11 23 09 23 - 4 formal acknowledgements in writing prior to submission t
23、he installation of the products. These products include the following: 1. Control valves. 2. Flow switches. 3. Flow meters. 4. Sensor wells and sockets in piping. 5. Terminal unit controllers. C. Some products are installed but not furnished by the contractor administered by this Section of the tech
24、nical specifications. The contractor administered by this Section of the technical specifications shall formally coordinate in writing and receive from other contractors formal acknowledgements in writing prior to submission the procurement of the products. These products include the following: 1. /
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2309232011DIRECTDIGITALCONTROLSYSTEMFORHVACPDF

链接地址:http://www.mydoc123.com/p-1074907.html