《UL SUBJECT 1801-2008 OUTLINE OF INVESTIGATION FOR POWER DISTRIBUTION CENTERS FOR COMMUNICATIONS EQUIPMENT (Issue 3)《通信设备用配电中心调查大纲 发布编号 3》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 1801-2008 OUTLINE OF INVESTIGATION FOR POWER DISTRIBUTION CENTERS FOR COMMUNICATIONS EQUIPMENT (Issue 3)《通信设备用配电中心调查大纲 发布编号 3》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJune 6, 20081SUBJECT 1801OUTLINE OF INVESTIGATIONFORPOWER DISTRIBUTION CENTERS FOR COMMUNICATIONS EQUIPMENTIssue Number: 3June 6, 2008Summary of TopicsThis new issue of Outline of Investigation,
2、Subject 1801 revises referencesto IEC 61204-7 to reflect that it is no longer a draft document.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the requirements contained in thisStandard, the current version of the UL Foreword is locat
3、ed onULStandardsInfoNet at: http:/ 2008 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULJUNE 6, 2008SUBJECT 18012No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION W
4、ITHOUT PERMISSION FROM ULCONTENTSINTRODUCTION1 General 41.1 Scope .41.2 Definitions .61.7 Markings and instructions 72 Protection from hazards .73 Wiring, connections, and supply .104 Physical requirements 105 Electrical requirements and simulated abnormal conditions .10JUNE 6, 2008 SUBJECT 1801 3UL
5、 COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULINTRODUCTION1 General1.1 Scope1.1.0 Addition of text to 1.1:The requirements in this Outline are to be used as a supplement to the requirements located within IEC61204-7: Low Voltage Power Supplies
6、, D.C. Output Part 7, Annex PS-E.Referenced within IEC 61204-7 is the third edition of the Standard for Safety of Information TechnologyEquipment, UL 60950/CSA C22.2 No. 60950-00. Therefore, the numbering scheme of the clauses andsubclauses located in this Outline correspond to those found in UL 609
7、50/CSA C22.2 No. 60950-00. Therequirements of UL 60950/CSA C22.2 No. 60950-00 are applicable with the exceptions noted in theOutline as replacements, additions, and deletions.The requirements from IEC 61204-7: Low Voltage Power Supplies, D.C. Output Part 7, Annex PS-E,shall apply where details are n
8、ot specifically provided in this Outline.Where a particular subclause of IEC 61204-7 and UL 60950/CSA C22.2 No. 60950-00 is not mentionedin this outline, that subclause shall apply. The relevant requirement, test specification, or note in UL60950/CSA C22.2 No. 60950-00 should be adapted accordingly
9、where this Outline states addition,modification, or replacement,.The block diagram in Figure 1A displays, in single line form, a typical d.c. power distribution system. Therectifiers provide the power for the telecommunications load equipment and maintain the charge (float) inthe batteries. The batt
10、eries and/or the backup generator provide the energy when interruption ofcommercial a.c. power occurs. The d.c. distribution system is to provide energy to the telecommunicationsload equipment with minimal power losses regardless of the state of commercial a.c. power. The d.c.power distribution syst
11、em transmits the energy from the rectifiers or batteries to the telecommunicationsload equipment. Overcurrent protection devices may be provided within the distribution among the rectifieroutputs, batteries, or the input to the primary distribution system. The rigid bus bar, which is typically used,
12、is designed for a minimum voltage drop and is a distribution structure capable of withstanding faultcurrents.The distribution system may be divided into the primary and secondary distribution. The primarydistribution system contains the overcurrent protection devices, the wire, and cable to connect
13、the outputvoltage from the batteries and rectifiers to the secondary distribution system. The overcurrent protectiondevices provide the fault and isolation protection when a short or overload condition occurs on the wire orcable between the primary and secondary distribution systems. The secondary d
14、istribution systemcontains the overcurrent protection devices (such as fuses and circuit breakers), the wire, and cable toconnect the output voltage from the rectifiers and the primary distribution system to thetelecommunications load equipment. The overcurrent protection devices in the secondary di
15、stributionsystem are intended to protect the wire and cable from faults in the secondary distribution system.Equipment faults are normally protected by overcurrent protection devices either within thetelecommunications load equipment of the frames, which contain the telecommunications load equipment
16、,or within the D.C. SECONDARY DISTRIBUTION circuit.This is generated text for figtxt.JUNE 6, 2008SUBJECT 18014UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULAddition of Figure:Figure 1ATypical line block diagram of a d.c. power distribution s
17、ystemJUNE 6, 2008 SUBJECT 1801 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL1.1.3.102 ExclusionsAddition:This outline does not apply to the following: power units other than Class 2 covered by the Standard for Power Units Other Than Class
18、2,UL 1012, and General Use Power Supplies, CSA C22.2 No. 107.1; Class 2 power units covered by the Standard for Class 2 Power Units, UL 1310, and PowerSupplies With Extra-Low-Voltage Class 2 Outputs, C22.2 No. 223; Telephone equipment covered by the Standard for Information Technology Equipment Safe
19、ty- Part 1: General Requirements, UL 60950-1, and CSA C22.2 No. 225; and Uninterruptible power supply equipment (d.c. to a.c. inverters) covered by the Standard forUninterruptible Power Systems, UL 1778, and General Use Power Supplies, CSA C22.2 No.107.1.1.2 DefinitionsAddition:The definitions locat
20、ed within IEC 61204-7: Low Voltage Power Supplies, D.C. Output Part 7, AnnexPS-E apply with the following additions:Definitions in alphabetical order of nounsDISTRIBUTION, D.C. BRANCH 1.2.8.101DISTRIBUTION, D.C. PRIMARY 1.2.8.102DISTRIBUTION, D.C. SECONDARY 1.2.8.103SYSTEM, CENTRALIZED D.C. POWER 1.
21、2.12.101TERMINAL, FIELD WIRING 1.2.5.101VOLTAGE, BATTERY FLOAT (OPERATING) 1.2.12.102VOLTAGE, BATTERY EQUALIZE 1.2.12.1031.2.5.101 FIELD WIRING TERMINAL : Any terminal to which a power supply circuit can be connected by aninstaller in the field is a field-wiring terminal unless the wire is pre-conne
22、cted as a part of the product,including the following: a pressure terminal connector, soldering lug, soldered loop, or crimped eyelet.1.2.8.101 D.C. BRANCH DISTRIBUTION : The circuit conductors, external to the equipment, between anovercurrent protective device and the downstream equipment.1.2.8.102
23、 D.C. PRIMARY DISTRIBUTION : All d.c. power circuits from the discharge bus to the input, and fromthe input to the second overcurrent protection devices downstream from the discharge bus (as shown inFigure 1A). The overcurrent protection devices shall be fuses, circuit breakers, or other devices whi
24、chprovide equivalent protection.1.2.8.103 D.C. SECONDARY DISTRIBUTION : Includes all circuits between the D.C. PRIMARY DISTRIBUTION and theload equipment (as shown in Figure 1A). The overcurrent protection devices shall be fuses, circuitbreakers or other devices which provide equivalent protection,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ULSUBJECT18012008OUTLINEOFINVESTIGATIONFORPOWERDISTRIBUTIONCENTERSFORCOMMUNICATIONSEQUIPMENTISSUE3 通信

链接地址:http://www.mydoc123.com/p-1069195.html