UL 60079-0 (ND)-2013 National Differences For UL 60079-0 Explosive atmospheres - Part 0 Equipment - General requirements (Sixth Edition Reprint with revisions through and including.pdf
《UL 60079-0 (ND)-2013 National Differences For UL 60079-0 Explosive atmospheres - Part 0 Equipment - General requirements (Sixth Edition Reprint with revisions through and including.pdf》由会员分享,可在线阅读,更多相关《UL 60079-0 (ND)-2013 National Differences For UL 60079-0 Explosive atmospheres - Part 0 Equipment - General requirements (Sixth Edition Reprint with revisions through and including.pdf(42页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences ForUL 60079-0Explosive Atmospheres - Part 0: Equipment - General RequirementsUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION
2、 FROM ULNational Differences ForUL 60079-0Explosive Atmospheres - Part 0: Equipment - General RequirementsEdition: 6Edition Date: July 26, 2013ANSI/UL 60079-0 is an adoption of IEC 60079-0, the Standard for Safety for ExplosiveAtmospheres Part 0: Equipment General Requirements, issued by the IEC Jun
3、e 2011). Pleasenote that the national difference document incorporates all of the U.S. national differences forUL 60079-0.This document provides a single listing of the National Differences included in the UL adoption ofthe corresponding IEC standard.All rights reserved. No part of this publication
4、may be reproduced, stored in a retrieval system, ortransmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwisewithout prior permission of UL.UL provides this standards document as is without warranty of any kind, either expressed or implied,including but not li
5、mited to, the implied warranties of merchantability or fitness for any purpose.In no event will UL be liable for any special, incidental, consequential, indirect or similar damages,including loss of profits, lost savings, loss of data, or any other damages arising out of the use of or theinability t
6、o use this standards document, even if UL or an authorized UL representative has been advisedof the possibility of such damage. In no event shall ULs liability for any damage ever exceed the pricepaid for this standards document, regardless of the form of the claim.Users of the electronic versions o
7、f ULs Standards for Safety agree to defend, indemnify, and hold ULharmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonableattorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronicStandard on the purchaser
8、s computer system.Copyright Underwriters Laboratories Inc.JULY 26, 2013NATIONAL DIFFERENCES FOR UL UL 60079-02UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULPrefaceThis document provides a single listing of the technical National Differences
9、included in the UL adoptionof the corresponding IEC standard.In its IEC-based standards, UL uses the notations indicated below to identify national difference type, andthese types are additionally noted in this document. The standard may not use all types of thesedeviations.D1 - These are deviations
10、 which are based on basic safety principles and requirements, elimination ofwhich would compromise safety for U.S. consumers and users of products.D2 - These are deviations based on safety practices. These are deviations for IEC requirements that maybe acceptable, but adopting the IEC requirements w
11、ould require considerable retesting or redesign on themanufacturers part.DC - These are deviations based on the component standards and will not be deleted until a particularcomponent standard is harmonized with the IEC component standard.DE - These are deviations based on editorial comments or corr
12、ections.DR - These are deviations based on the national regulatory requirements.Each national difference contains a description of what the national difference entails. Typically one of thefollowing words is used to explain how the text of the national difference is to be applied to the base IECtext
13、:Addition / Add - An addition entails adding a complete new numbered clause, subclause, table,figure, or annex. Addition is not meant to include adding select words to the base IEC text.Deletion / Delete - A deletion entails complete deletion of an entire numbered clause, subclause,table, figure, or
14、 annex without any replacement text.Modification / Modify - A modification is an altering of the existing base IEC text such as theaddition, replacement or deletion of certain words or the replacement of an entire clause,subclause, table, figure, or annex of the base IEC text.JULY 26, 2013 NATIONAL
15、DIFFERENCES FOR UL UL 60079-0 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULNational Differences1DV.1 DR Modification of Clause 1, first paragraph to replace with the following:1DV.1.1 This standard specifies the general requirements for co
16、nstruction, testing andmarking of electrical equipment and Ex Components intended for use in explosiveatmospheres. Explosive atmospheres are identified by the National Electrical Code, NFPA70 as hazardous (classified) locations and include the following specified locations: Class I, Zone 0 Class I,
17、Zone 1 Class I, Zone 2 Zone 20 Zone 21 Zone 22See 6.1 for the relationship of the Equipment Protection Level (EPL) to the zone areaclassification.1DV.2 DR Modification of Clause 1, third paragraph as follows:1DV.2.1 Delete “(IEC 60079-1)” and “(IEC 60079-11)”1DV.3 DR Modification of Clause 1 to dele
18、te NOTE 3.1DV.3.1 This NOTE does not apply.1DV.4 DR Modification of Clause 1, sixth paragraph to replace with the following: ISA 60079-2: Gas Pressurized enclosures “p”; ISA 60079-31: Dust Protection by enclosure “t”; ISA 61241-4: Dust Pressurization “pD”; UL 60079-1: Gas Flameproof enclosures d; UL
19、 60079-5: Gas Powder filling q; UL 60079-6: Gas Oil immersion o; UL 60079-7: Gas Increased safety e; UL 60079-11: Gas Intrinsic safety i;JULY 26, 2013NATIONAL DIFFERENCES FOR UL UL 60079-04UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL UL 60
20、079-15: Gas Type of protection “n”; UL 60079-18: Gas and dust Encapsulation m;1DV.5 DR Modification of Clause 1, sixth paragraph to replace with the following whichdeletes IEC 60079-13, IEC 62013-1, IEC 60079-30-1 and adds ANSI/IEEE 514 and NOTE 7:1DV.5.1 This standard is supplemented or modified by
21、 the following equipment standards:ISA 60079-25 (12.02.05): Explosive atmospheres Part 25: Intrinsically safe electricalsystemsIEC 60079-26 (12.00.03): Explosive atmospheres Part 26: Equipment with equipmentprotection level (EPL) GaIEC 60079-28 (12.21.02): Explosive atmospheres Part 28: Protection o
22、f equipment andtransmission systems using optical radiationANSI/IEEE 515: Standard for Testing, Design, Installation, and Maintenance of ElectricalHeat Tracing for Industrial Applications.NOTE 7 Components such as power connections, splices, end terminations, as well as cable entries, fittings, ands
23、eals, are to be evaluated according to the type of protection employed.1DV.6 DR Addition of 1DV.6.11DV.6.1 Where references are made to other IEC 60079 standards, the referencedrequirements found in these standards shall apply as modified by any applicable U.S.National Differences.2DV.1 DR Modificat
24、ion of the title in Clause 2 as follows:2DV.1.1 Delete “Normative”.JULY 26, 2013 NATIONAL DIFFERENCES FOR UL UL 60079-0 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM UL2DV.2 DR Modification of Clause 2 references to replace with the following
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL600790ND2013NATIONALDIFFERENCESFORUL600790EXPLOSIVEATMOSPHERESPART0EQUIPMENTGENERALREQUIREMENTSSIXTHEDITIONREPRINTWITHREVISIONSTHROUGHANDINCLUDINGPDF

链接地址:http://www.mydoc123.com/p-1068339.html