REG NASA-LLIS-1383-2003 Lessons Learned Autoclave Purge Blower Failure.pdf
《REG NASA-LLIS-1383-2003 Lessons Learned Autoclave Purge Blower Failure.pdf》由会员分享,可在线阅读,更多相关《REG NASA-LLIS-1383-2003 Lessons Learned Autoclave Purge Blower Failure.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Lessons Learned Entry: 1383Lesson Info:a71 Lesson Number: 1383a71 Lesson Date: 2003-10-14a71 Submitting Organization: MSFCa71 Submitted by: Louise SemmelSubject: Autoclave Purge Blower Failure Abstract: A mishap occurred in a large (18 X 20) autoclave resulting in damage to government property of ap
2、proximately $23K. The mishap was likely the result of a small amount of accumulated debris around a pneumatic valve, coupled with a minor error in pressure system logic, which failed to alert operators of the event prior to failure.Description of Driving Event: A mishap occurred in a large (18 X 20)
3、 autoclave at MSFC on August 13, 2002 resulting in damage to government property of approximately $23K. Two to four minutes into pressurizing the autoclave, operators noted that vessel pressure was not following the set-point value. Operators heard a loud noise outside the building and sent personne
4、l to investigate. Bystanders outside indicated the noise came from nearby construction. Approximately 5 minutes later, another loud noise was heard coming from the nitrogen pressure regulating assembly of the autoclave. Other than the noise, no system warning or error indicators were encountered. Th
5、e cycle was aborted and appropriate safety personnel were notified. A checkout of the facility revealed a failure of the purge blower. Equipment damage resulted from the mishap. Damaged components included the purge blower assembly, purge valve solenoid assembly (solenoid in green), purge valve (bel
6、ow the solenoid assembly) and the entire purge line from the blower to the autoclave pressure vessel. A piece of fan blade sheared from the shaft, ripped through the blower housing and hit the purge valve solenoid just before it came to rest on some nearby nitrogen supply piping. The investigation r
7、evealed the purge valve had remained open during pressurization of the autoclave allowing pressurizing gas (nitrogen) to back-flow into the purge blower and spin it in reverse until it Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-failed due to exc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- REGNASALLIS13832003LESSONSLEARNEDAUTOCLAVEPURGEBLOWERFAILUREPDF

链接地址:http://www.mydoc123.com/p-1019022.html