《NFPA 13E-2015 Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems (Effective Date 12 1 2014).pdf》由会员分享,可在线阅读,更多相关《NFPA 13E-2015 Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems (Effective Date 12 1 2014).pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、Copyright 2014 National Fire Protection Association. All Rights Reserved.NFPA13ERecommended Practice forFire Department Operations in Properties Protected by Sprinklerand Standpipe Systems2015 EditionThis edition of NFPA 13E, Recommended Practice for Fire Department Operations in PropertiesProtected
2、 by Sprinkler and Standpipe Systems, was prepared by the Technical Committee on FireService Training. It was issued by the Standards Council on November 11, 2014, with aneffective date of December 1, 2014, and supersedes all previous editions.This edition of NFPA 13E was approved as an American Nati
3、onal Standard on December 1,2014.Origin and Development of NFPA 13EIn 1933, NFPA adopted an informative brochure that was prepared by the Committee onField Practice and entitled “Use of Automatic Sprinklers by Fire Departments.” It was pub-lished as a separate pamphlet and reprinted in 1936. The wor
4、k formerly carried on by theCommittee on Field Practice was distributed to a number of new committees in 1953, and atthat time the Committee on Standpipes and Outside Protection was given responsibility forthe brochure. A subcommittee of the Committees on Standpipes and Outside Protection,Automatic
5、Sprinklers, Fire Department Equipment, and Fire Service Training prepared arevision, “Fire Department Operations in Protected Properties,” which, on recommendationof the four committees, was adopted as an informative report at the NFPAAnnual Meeting in1961. The informative report was published and c
6、irculated as a separate pamphlet, No.SPI-1961, but was not included in the annual volumes of the National Fire Codes.Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Stand-pipe Systems, NFPA 13E, was adopted with minor revisions by NFPA at its 1966 Annual
7、Meetingon recommendation of the Committee on Standpipes and Outside Protection. It wasamended and updated in 1973, 1978, 1983, 1989, 1995, and 2000. The changes made by theTechnical Committee on Fire Service Training in the 2000 edition of this document alignedits text with changes made to NFPA 13,
8、Standard for the Installation of Sprinkler Systems.Inaddition, several chapters presenting new pre-incident planning and fireground operationalconsiderations for fire personnel were added.In the revision process for the 2005 edition, the previous numbering of chapters andparagraphs changed to reflec
9、t requirements in the 2004 edition of the Manual of Style forNFPATechnical Committee Documents.The 2010 edition included some clarifying language regarding the use of alternative watersupplies for fire department support of sprinkler and standpipe systems. In addition, thisedition included additiona
10、l illustrations of primary sprinkler/standpipe system valves and animproved illustration of a typical sprinkler system layout, using symbols from NFPA 170,Standard for Fire Safety and Emergency Symbols, 2009 edition.In the 2014 edition, the committee updated the standpipe system sections to bring th
11、emup to current practices.13E1NFPA and National Fire Protection Association are registered trademarks of the National Fire Protection Association, Quincy, Massachusetts 02169.Technical Committee on Fire Service TrainingKenneth W. Richards, Jr., ChairOld Mystic Fire Department, CT EWesley E. Barbour,
12、 CrossBar International LLC, NY SEJohn P. Brown, Nassau County Fire Service Academy,NY UW. Edward Buchanan, Jr., Hanover Fire EMSDepartment, VA UJames Cannell, Columbus Ohio Division of Fire, OH LRep. Columbus Firefighters UnionRick Egelin, Fireblast 451 Incorporated, CA MMike Gagliano, Seattle Fire
13、 Department, WA EWilliam E. Glover, High Temperature Linings (HTL),VA MCortez Lawrence, US Department of Homeland Security,MD SERoger M. LeBoeuf, Elliott, LeBoeuf if so, forhow long and at what pressure; and any issues with thebackflow device or pressure-reducing devices(11) Whether the valve was cl
14、osed after the fire, and whichemployee ordered that the valve be closed(12) Number of sprinklers replaced by the fire department(13) Type of sprinklers installed(14) Whether sprinkler protection was fully restored and bywhom(15) Actions taken to restore service(16) Whether the private water supply t
15、o sprinklers operatedsatisfactorily(17) Whether the fire prevention bureau was notified(18) Whether the representative of management was notifiedas well as the names of the employee making notificationand of those notifiedFIGURE 4.4.1 Sprinkler with Sprinkler Wedge Installed.13E7PROPERTIES PROTECTED
16、 BY AUTOMATIC SPRINKLER SYSTEMS2015 Edition4.6 Ventilation in Storage Occupancies.4.6.1 Fire department personnel should study occupancieswith a wide variety of configurations and a wide range of stor-age commodities to determine whether there is a need forspecial procedures, particularly where stor
17、age heights are inexcess of 12 ft (3.66 m). This study should be done because, insome cases, routine ventilation procedures in the early stagesof a fire can hinder effective sprinkler operation. The fire de-partment should discuss its pre-incident plan for these types ofoccupancies with the occupant
18、, sprinkler system designer, andinsurance carrier to determine whether a modification in pro-cedures is appropriate.4.6.2* Where search and rescue operations have been com-pleted prior to the fire departments performance of ventila-tion work, the incident commander should allow the auto-matic sprink
19、lers to continue to operate without furtherventilation.Chapter 5 Properties Protected by ExteriorSprinklers for Protection Against Exposure Fires5.1 General.5.1.1* Fire department personnel should be aware that manybuildings or properties that have a severe exposure problemmight be equipped with ext
20、erior sprinkler systems designed toprovide a water curtain capable of shielding the property fromfires in other buildings or in storage areas.5.1.2 Fire department training and operational protocolsshould be in place so that, when used properly, sprinklers forexterior protection (specially designed
21、for a water curtain ef-fect) and sprinkler systems will prevent an exposure fire fromentering the building.5.2 Pre-Incident Planning. In properties having exteriorsprinkler protection, fire personnel and officers assigned tothe first-due companies should thoroughly understand the fol-lowing:(1) The
22、construction and layout of the building, the nature ofthe occupancies protected by exterior sprinklers, the ex-tent of this protection, and the type and operation (auto-matic or manual) of sprinkler systems(2) The water supply to the sprinklers, including the sourceand type of supply, the flow and p
23、ressure normally avail-able, and the anticipated duration of the available supply(3) The location of all sprinkler control valves, the area con-trolled by each valve, and the consequence of shutting offeach valve(4) The location of fire department connections to sprinklersystems, the specific area e
24、ach connection serves, and thewater supply, hose, and pumper layout that will be used tofeed the sprinkler connections(5) The specific company assignment having the primary re-sponsibility for charging the sprinkler connection(6) The location of water supplies for handlines that can beused without j
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFPA13E2015RECOMMENDEDPRACTICEFORFIREDEPARTMENTOPERATIONSINPROPERTIESPROTECTEDBYSPRINKLERANDSTANDPIPESYSTEMSEFFECTIVEDATE1212014PDF

链接地址:http://www.mydoc123.com/p-1008289.html