1、*USACE / NAVFAC / AFCESA / NASA UFGS-08 56 46.20 20 (August 2011)-Preparing Activity: NAVFAC SupersedingUFGS-08 56 46.20 20 (April 2006) UFGS-13094N (December 2001)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2011*SECTION TABLE OF CONTENTSDIVISION 08 - OPEN
2、INGSSECTION 08 56 46.20 20RADIO FREQUENCY SHIELDED ENCLOSURES, WELDED TYPE08/11PART 1 GENERAL1.1 REFERENCES1.2 GENERAL REQUIREMENTS1.2.1 Mechanical Work1.2.2 Electrical Work1.2.3 Acoustical Ceiling System1.3 SUBMITTALS1.4 RELIABILITY1.5 DELIVERY AND STORAGE1.6 QUALITY ASSURANCE1.6.1 Certifications1.
3、6.1.1 Performance Test Plan1.6.1.2 Qualifications of the Shielding Enclosure Testing Agency1.6.1.3 Door Static Load Test1.6.1.4 Door Sag Test1.6.1.5 Swinging Door Closure TestPART 2 PRODUCTS2.1 SHIELDED ENCLOSURE CHARACTERISTICS2.1.1 Radio Frequency Interference Attenuation2.1.2 Sound Transmission C
4、lass (STC)2.2 STEEL AND WELDING MATERIALS2.2.1 Shielding Steel2.2.2 Welding Electrodes2.2.3 Floor2.2.3.1 Floor Finish2.2.3.2 Subfloor2.2.3.3 Heavy Duty Floor2.3 DOOR ASSEMBLIES2.3.1 Finger Stock2.3.2 Latching Type2.3.3 Nonlatching Type2.3.4 Special Door AssembliesSECTION 08 56 46.20 20 Page 1Provide
5、d by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.3.4.1 Hydraulic or Pneumatic Sealing Mechanism2.3.4.2 Sliding Doors2.4 LINE FILTERS2.4.1 Power Line Filters2.4.2 Telephone and Signal Line Filters2.5 WAVEGUIDE-TYPE AIR VENTS2.6 GROUNDING STUD2.7 SERVICE ENT
6、RANCE PLATES (SET-UP PANELS)2.8 NAMEPLATES2.9 LIGHTING2.10 EXHAUST FANS2.11 COAXIAL CABLE PENETRATIONSPART 3 EXECUTION3.1 SHIELDING STEEL INSTALLATION3.1.1 Surface Preparation3.1.2 Installation Supervision3.1.3 Floor Panel Setting3.1.4 Welding3.2 DOOR ASSEMBLIES3.3 LINE FILTERS3.4 WAVEGUIDE-TYPE AIR
7、 VENTS3.5 EXHAUST FAN3.6 CONDUCTOR INSTALLATION3.7 GROUNDING3.8 SERVICE ENTRANCE PLATE3.9 FIELD TESTS3.9.1 Weld Testing3.9.2 Seam Leak Detection Testing3.9.3 Attenuation Testing3.9.3.1 Test Procedure, Frequencies, and Equipment3.9.3.2 Additional Test Points3.9.3.3 Final In Service Testing- End of Se
8、ction Table of Contents -SECTION 08 56 46.20 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-08 56 46.20 20 (August 2011)-Preparing Activity: NAVFAC SupersedingUFGS-08 56 46.20 20 (April 2006) UFGS-13094N
9、 (December 2001)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated July 2011*SECTION 08 56 46.20 20RADIO FREQUENCY SHIELDED ENCLOSURES, WELDED TYPE08/11*NOTE: This guide specification covers the requirements for radio frequency shielded enclosures, welded type in size
10、s under 50 square meters 500 square feet.Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, o
11、r revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments, suggestions and recommended changes for this guide specification are welcome and sh
12、ould be submitted as a Criteria Change Request (CCR).*NOTE: For larger enclosures and for High Altitude Electromagnetic Pulse (HEMP) protected enclosures, contact NAVFAC Engineering Innovation and Criteria Office (Code EICO) before beginning design. The electrical designer should refer to MIL-HDBK-4
13、19 Volumes I and II for special grounding and bonding requirements for EMC enclosures and to NACSIM 5203 for TEMPEST enclosures. All metallic electrical conduits which penetrate a TEMPEST shield must be isolated within 50 mm 2 inches of the exterior of the shield by a nonmetallic conduit section at
14、least 150 mm six inches long to prevent conduction of information from the shielded enclosure. Although not addressed in this specification, it is recognized that fiber optic cable has gained acceptance as an effective method of transmitting SECTION 08 56 46.20 20 Page 3Provided by IHSNot for Resale
15、No reproduction or networking permitted without license from IHS-,-,-data across the boundary of shielded enclosures without filtering. If fiber optic cable is used, describe the penetration of the shield in detail. For a discussion of the advantages and disadvantages of fiber optic systems see NAVF
16、AC DM-12.02. Designer should consult these documents and other appropriate sources before applying this guide specification to large scale EMI enclosures to HEMP and to TEMPEST Projects. The potential requirement for thermal expansion joints inherent to large scale enclosures is not addressed in thi
17、s guide specification. The extent and location of the work to be accomplished and wiring, equipment, and accessories necessary for a complete installation should be indicated on the project drawings.*NOTE: The following information shall be shown on the project drawings:1. Assembly details;2. Penetr
18、ation details;3. Location and method of mounting shielded enclosure within building;4. Location of mechanical and electrical equipment within shielded enclosure;5. Interior wall finish;6. Suspended ceiling; and7. Raised computer floor.*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to lis
19、t the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Secti
20、ons Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project SECTION 08 56 46.20 20 Page 4Provided b
21、y IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-specification when you choose to reconcile references in the publish print process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to withi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS08564620202011RADIOFREQUENCYSHIELDEDENCLOSURESWELDEDTYPE 焊接 屏蔽 无线电 频率 围墙 PDF

链接地址:http://www.mydoc123.com/p-984748.html