1、 Printed Copies are Uncontrolled Page 1 of 10 Document Number: w-EM1Issue Date: 16-Feb-2001Global Manufacturing Standards Rev Date: 06-Nov-2003AC ELECTRIC MOTORS TOTALLY ENCLOSED TYPE 1.0 GENERAL: PURPOSE AND SCOPE: To provide functional, performance, and dimensional requirements for Totally Enclose
2、d (TE) motors for industrial applications at Ford Motor Company (hereinafter the Company) operations located worldwide. Deviations from this Standard are permitted only upon written waiver by the requisitioning activity. Note: This Standard contains three sets of requirements: Those for North Americ
3、a, both NEMA (NA-NEMA) and IEC (NA-IEC), and those for Europe and/or those countries that follow Euro-Norm Directives and require CE Marked products. Those requirements marked as (NA-ALL) refer to both NEMA and IEC motors for use in North America. For use in North America, motors shall be Underwrite
4、rs Recognized ( ) and CSA Certified ( ) to ensure that their construction is in compliance with the appropriate UL/CSA Standards. For use in Countries who follow the Euro-Norm Directives, motors shall be CE Marked ( ) to ensure that their construction is in compliance with the appropriate EN/IEC Dir
5、ectives. It is preferred that all motors be triple certified and marked with all three above symbols. MANDATORY AND PREFERRED ITEMS: Mandatory requirements of this Standard are characterized by the use of the word “shall“. Preferred items are characterized by the use of the word “should“. 1.1 TYPES
6、OF MOTORS (NA-NEMA): w-EM1 applies to ALL non-explosion proof three-phase, squirrel cage, 575 volts or less, totally enclosed non-ventilated (IP54 Rated) and fan or blower cooled, 80 degree C rise, 1/4 horsepower or more, alternating current, induction type electric motors. 1.1.1 TYPES OF MOTORS (NA
7、-IEC): w-EM1 applies to ALL non-explosion proof, three-phase, 500 volts or less, Rated IP54 or better and IC 40, IC41, or IC46 cooled 80 degree C rise, 0.18 kilowatt or more, alternating current, induction type electric motors, as defined by IEC 60034. 1.1.2 TYPES OF MOTORS (CE): w-EM1 applies to AL
8、L three-phase, 500 volts or less, IP5x, 80 degree C rise, 0.18 kilowatt or more, alternating current, induction type electric motors, as defined by IEC 60034. 1.2 INCLUDED FRAMES (NA-NEMA): w-EM1 applies to inch-sized NEMA Standard electric motors and to fractional horsepower motors in frame size 56
9、, OR to those Ratings designated in NEMA Standard MG-1 Section 11.31, medium (integral) alternating current machines, frames 143T through 449T. Printed Copies are Uncontrolled Page 2 of 10 Document Number: w-EM1Issue Date: 16-Feb-2001Global Manufacturing Standards Rev Date: 06-Nov-20031.2.1 INCLUDED
10、 FRAMES (NA-IEC): w-EM1 applies to metric-sized IEC electric motors, frame sizes 63 to 400, as designated by IEC 60072. 1.2.2 INCLUDED FRAMES (CE): w-EM1 applies to metric-sized IEC electric motors, frame sizes 56 to 400, as designated by IEC 60072. 2.0 REFERENCE STANDARDS: Whenever a specific Stand
11、ard is mentioned in this Standard, it is the latest revision, unless otherwise specified. 2.1 Ford Motor Company Manufacturing Standard EX1 supplemental requirements to SAE HS-1738. 2.2 INDUSTRY STANDARDS: 2.2.1 NEMA MG1, Motors and Generators. 2.2.2 NEMA MW1000, Magnet Wire Standards. 2.2.3 IEEE 84
12、1, Standard for Petroleum and Chemical Industry - Severe Duty Totally Enclosed Fan-Cooled (TEFC) Squirrel Cage Induction Motors - Up to and Including 500 HP. 2.2.4 NEC/NFPA 70 Article 430, Motors, Motor Circuits, and Controllers 2.2.5 CSA C22.2-100, Motors and Generators 2.2.6 SAE HS-1738, Electrica
13、l Standard for Industrial Machinery - Supplement to NFPA 79. 2.2.7 IEC 60204-1, Safety of Machinery, Electrical Equipment of Machines Part 1: General Requirements. 2.2.8 IEC 60034-1, Rotating Electrical Machines Part 1: Rating and Performance. 2.2.9 IEC 60034-5, Rotating Electrical Machines: Classif
14、ication of Degrees of Protection Provided by Enclosures of Rotating Electrical Machines (IP Code). 2.2.10 IEC 60034-11, Rotating Electrical Machines Part 11: Built-in Thermal Protection Chapter 1: Rules for Protection of Rotating Electrical Machines. 2.2.11 IEC 60072, Dimensions and Output Series fo
15、r Rotating Electrical Machines: Frame Numbers 56 to 400 and Flange Numbers 55 to 1080. 2.3 CONFORMANCE: Printed Copies are Uncontrolled Page 3 of 10 Document Number: w-EM1Issue Date: 16-Feb-2001Global Manufacturing Standards Rev Date: 06-Nov-20032.3.1 SUPPLIERS RESPONSIBILITY: All materials and comp
16、onents supplied to this Standard shall be equivalent in all respects to material upon which approval was originally granted. Any deviations from this Standard, without written notice and subsequent review and re-approval by the Ford Global Manufacturing Standards - Electrical Technical Committee, wi
17、ll be sufficient cause for removal from the Ford Global Manufacturing Standards - Electrical Qualified Source List (E1-QSL). 2.3.2 APPROVALS: All products submitted for evaluation shall be “off-the-shelf“ catalog types manufactured with normal production procedures and quality control. Prototype mot
18、ors will not be considered. Suppliers shall submit an itemized DATA SHEET, correspondingly numbered with this Standard, completely addressing their compliance with each provision. The Vice President of Engineering or a higher officer of the Suppliers (Manufacturers) company shall sign this Data Shee
19、t. Suppliers shall also submit copies of any and all test Agency certificates and associated letters and documentation, which cite the actual standards their motors/products were tested to. Approvals shall be made based on conformance to this Standard as certified by the above DATA SHEET, the requir
20、ed Agency approvals, as well as laboratory and performance tests and documented Shop Trials. All documentation is subject to the review of Ford Global Manufacturing Standards - Electrical Technical Committee. 2.4 MARKINGS (NA-ALL): All motors shall be Underwriters Recognized, CSA Certified, and shal
21、l bear the marks of these agencies. 2.4.1 MARKINGS (CE): All motors shall be CE Marked. Note: To facilitate the use of motors on global applications, all motors should Underwriters Recognized, CSA Certified, and CE Marked and bear the above three marks/symbols. 3.0 PERFORMANCE: 3.1 ENERGY EFFICIENCY
22、 (NA-ALL): All motors shall conform to the Energy Policy Act of 1992 (EPACT) as amended, NRCan, IEEE 841 Section 8, and NEMA MG1 Table 12-10 as tested in accordance with NEMA MG1 Part 12.59, independent of application. NEMA Premium Efficiency rated motors that exceed EPACT shall always be specified.
23、 3.1.1 ENERGY EFFICIENCY (CE): All motors shall conform to IEC 60034-1. 3.2 VIBRATION (NA-NEMA): All motors shall meet requirements stated in IEEE 841 Section 6.9 and NEMA MG1 Part 7.07 thru 7.09. Printed Copies are Uncontrolled Page 4 of 10 Document Number: w-EM1Issue Date: 16-Feb-2001Global Manufa
24、cturing Standards Rev Date: 06-Nov-20033.2.1 VIBRATION (NA-IEC): All motors shall conform to IEC 60034-14. 3.2.2 VIBRATION (CE): All motors shall conform to IEC 60034-14. 3.3 ENCLOSURES (NA-NEMA): All motors shall conform to IEEE 841 Section 4.5. 3.3.1 ENCLOSURES (NA-IEC): All motors shall be a mini
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDWEM12003ACELECTRICMOTORSTOTALLYENCLOSEDTYPE 封闭式 交流电动机 PDF

链接地址:http://www.mydoc123.com/p-748368.html