FORD W-EL3-2003 PROGRAMMABLE CONTROLLER REQUIREMENTS AND APPLICATION《可编程序控制器 要求和应用》.pdf
《FORD W-EL3-2003 PROGRAMMABLE CONTROLLER REQUIREMENTS AND APPLICATION《可编程序控制器 要求和应用》.pdf》由会员分享,可在线阅读,更多相关《FORD W-EL3-2003 PROGRAMMABLE CONTROLLER REQUIREMENTS AND APPLICATION《可编程序控制器 要求和应用》.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、 printed copies are uncontrolled. Page 1 of 19 Standard Number w-EL3 Issue Date: 20030219 Global Manufacturing Standards Rev: PROGRAMMABLE CONTROLLER REQUIREMENTS AND APPLICATION 1. GENERAL: 1.1 PURPOSE AND SCOPE: This Standard describes the requirements for programmable controllers (PLCs), hardware
2、, software, and applications, intended for general use throughout Ford Motor Company that will promote: (1) Safety to personnel. (2) Uninterrupted production. (3) Long life of equipment. (4) Ease and low cost of maintenance. 1.1.1 Sections 1 thru 7 of this Standard pertains mainly to PLC hardware an
3、d software manufacturers. 1.1.2 Sections 8 thru 11 of this Standard pertains mainly to the application and use of the PLC hardware and software. 1.2 MANDATORY AND PREFERRED ITEMS: Mandatory requirements of this Standard are characterized by the use of the word “shall“. Preferred items are characteri
4、zed by the use of the word “should“. 1.3 DEVIATIONS: Deviations from this Standard shall have the approval of the requisitioning activity in writing. Any waivers granted shall apply only to the order in question and shall not be considered as permanent. 1.4 NOTE: * Indicates the following item refer
5、enced on the attached w-EL3 Option Sheet. 1.5 REQUIREMENTS: 1.5.1 Current or voltage transients or electromagnetic effects SHALL NOT cause spurious operation or affect the normal operation of the PLC. The PLC shall meet or exceed the requirements of ANSI/IEEE C37.90.1 and NEMA ICS 1-109.6. Internal
6、protection circuitry shall fail to a safe condition. 1.5.2 The PLC shall operate properly in a temperature range of 0 to 40 degrees C (32 to 104 degrees F) measured inside the NEMA 12/IP54 enclosure in which the PLC system will be mounted. It shall be capable of operating continuously at 40 degrees
7、C without additional ventilation or active cooling systems. 1.5.3 The PLC shall operate properly in a humidity range of 5% to 95% (non-condensing) per IEC 1131-2, Sec. 2.1.1.3, Table 2, severity level RH-2. printed copies are uncontrolled. Page 2 of 19 Standard Number w-EL3 Issue Date: 20030219 Glob
8、al Manufacturing Standards Rev: 1.5.4 Fasteners used in maintenance operations (example: module replacement) shall be captive type. 1.5.5 Plug-in modules shall be mechanically secured in place. The assembled system shall be designed to withstand vibration testing of 5-10Hz at 0.2-inch displacement (
9、peak to peak) and 10-200Hz at 1 g and endurance testing (sweep test) of 10-200Hz for ninety minutes per axis and a dwell at resonance frequencies (10 minutes per resonance) per MIL Standard 810 and IEC 60068-2-6. 1.5.6 Where the PLC uses similar modules with unlike functions; the modules shall be me
10、chanically keyed to prohibit insertion in incorrect positions or electrically interlocked to prevent operation in an incorrect position. 2. REFERENCE STANDARDS: 2.1 Whenever a specific Standard is referenced, it shall be the latest revision, unless otherwise specified. 2.2 This Standard includes and
11、 supplements the requirements of NEMA IA2.1 through IA 2.4 “Programmable Controllers“, IEC 61131-1 through IEC 61131-4 “Programmable Controllers“, and as applicable, requirements in: ANSI/IEEE C37.90.1 “Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems“ ANSI B11
12、.19 - “Performance Criteria for the Design, Construction, Care, and Operation of Safeguarding When Referenced by the Other B11 Machine Tool Safety Standards“ ANSI B11.20 - “Machine Tools - Manufacturing Systems/Cells - Safety Requirements for Construction, Care, and Use“ ICS 1-109.6 - “Electrical No
13、ise Tests (Showering Arc)“ MIL Standard 810 - “Environmental Engineering Considerations and Laboratory Tests“ IEC 60068-2-6 - “Environmental Testing - Test Fc and Guidance: Vibration (Sinusoidal)“ IEC 60204-1 - “Safety of Machinery - Electrical Equipment of Machines - Part 1: General Requirements“ E
14、N 954 - “Safety of Machinery - Safety Related Parts of Control Systems - General Principles for Design“ UL 1277 - “Electrical Power and Control Tray Cables with Optional Optical-Fibre Members“ SAE HS-1738 - “SAE Electrical Standard for Industrial Machinery - Supplement to NFPA 79“ Ford Manufacturing
15、 Standard EX1 - “Electrical Standards for Mass Production Equipment“ Ford Manufacturing Standard U-EX001 - “Safety of Machinery - Electrical Equipment of Machines“ printed copies are uncontrolled. Page 3 of 19 Standard Number w-EL3 Issue Date: 20030219 Global Manufacturing Standards Rev: 3. CENTRAL
16、PROCESSING UNIT (CPU): 3.1 In the event of a power failure, the CPU shall be capable of retaining the status or accumulated values in its memory associated with arithmetic operations, data files, latching states and timing functions. Non-volatile memory systems are preferred. Where batteries are use
17、d for memory retention, refer to Clause 3.8. 3.2 PLC FUNCTIONS: 3.2.1 The CPU shall offer a minimum function menu consisting of ladder programming including: a) Basic Relay b) “Latching“ or “Retentive“ Relay c) Retentive Timing d) Non-retentive Timing e) Incremental Counting 3.2.2 The logic line sha
18、ll accept a minimum of seven (7) elements in series and a minimum of four (4) in parallel. 3.2.3 Program saving to a remote device shall default to include the entire control program memory. 3.2.4 Programming instructions for the smallest controllers shall be a subset of the largest for full upward
19、compatibility. 3.3 The PLC shall not increment/decrement counters nor otherwise cause false movement or change in retained data when the power is turned on or off. 3.4 The PLC shall have Self-Diagnostic routines to insure the safe and reliable operation of the entire system. Upon fault detection, ou
20、tput devices shall be capable of being individually de-energized or held in last state (necessary in PID or analog control). 3.5 Status lights on the CPU shall verify normal operation. Typical lights are: AC and DC power, processor running, parity error, memory fault, memory support battery low, pro
21、cessor fault, power supply fault, and I/O fault. 3.6 Error Detection and Fault Isolation (EDFI) shall be integral and shall localize faults to the lowest modular (plug-in) level. 3.7 Program accessible status bits shall be available to provide local fault annunciation via lights printed copies are u
22、ncontrolled. Page 4 of 19 Standard Number w-EL3 Issue Date: 20030219 Global Manufacturing Standards Rev: 3.8 BATTERIES: 3.8.1 Where a battery is required to retain the PLC memory, an internal bit or output, operating as part of the CPU, shall be available to indicate that the memory battery is low.
23、3.8.2 Where a battery is required to retain PLC memory, it shall be replaceable without loss of memory (with power on). The battery shall maintain processor memory for a minimum of 90 days with no power on. The battery shall be a readily available, long life type. 3.9 A selector switch shall be furn
24、ished to allow programming or editing only in the program or program/run position. 3.10 Removal of any processor module shall shut down the PLC system. 4. PROGRAMMING AND DATA ACCESS: 4.1 Programming devices shall provide indication of the logic state of each element comprising a rung or network of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- FORDWEL32003PROGRAMMABLECONTROLLERREQUIREMENTSANDAPPLICATION 程序 控制器 要求 应用 PDF

链接地址:http://www.mydoc123.com/p-748366.html