《ASTM E2358-2017 Standard Specification for Performance of Glazing in Permanent Railing Systems Guards and Balustrades《固定栏杆装置 护栏和扶手使用玻璃性能的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2358-2017 Standard Specification for Performance of Glazing in Permanent Railing Systems Guards and Balustrades《固定栏杆装置 护栏和扶手使用玻璃性能的标准规格》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2358 17Standard Specification forPerformance of Glazing in Permanent Railing Systems,Guards, and Balustrades1This standard is issued under the fixed designation E2358; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, t
2、he year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers glass in permanent railingsystems, guards, and balustrades, including components
3、suchas rails and swing gates or other forms of required guardrailopening protection installed in agricultural, assembly,commercial, educational, industrial, institutional, recreational,and residential buildings, and other structures such as towers orelevated platforms.1.2 This specification is inten
4、ded to be applied to permanentglass or other glazing railing systems for buildings and to suchrailing systems, rails, guards, and balustrades having majorstructural components made of glass or other glazing material,or the secondary components such as infill or balusters made ofglass or other glazin
5、g material.1.3 This specification considers that the overall outlook isbased on the health and safety of all potential users ofbuildings. The criteria incorporated in this specification pro-vide for normal and anticipated building uses, but not forabuses for which the building and its components are
6、 notdesigned.1.4 This specification establishes basic minimum require-ments and criteria that lead to satisfactory products undernormal use conditions and does not give consideration todesign criteria for specific field conditions, the establishment ofwhich is the prerogative and responsibility of t
7、he designer,specification writer, and regulatory agencies.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and todetermi
8、ne the applicability of regulatory limitations prior touse.1.6 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations
9、issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2E631 Terminology of Building ConstructionsE935 Test Methods for Performance of Permanent MetalRailing Systems and Rails for BuildingsE1481 Terminology of Railing Systems and R
10、ails for Build-ingsE1886 Test Method for Performance of Exterior Windows,Curtain Walls, Doors, and Impact Protective SystemsImpacted by Missile(s) and Exposed to Cyclic PressureDifferentialsE1996 Specification for Performance of Exterior Windows,Curtain Walls, Doors, and Impact Protective SystemsImp
11、acted by Windborne Debris in HurricanesE2025 Test Method for Evaluating Fenestration Componentsand Assemblies for Resistance to Impact Energies (With-drawn 2015)3E2353 Test Methods for Performance of Glazing in Perma-nent Railing Systems, Guards, and Balustrades2.2 ANSI Standard:ANSI Z97.1 Glazing M
12、aterials Used in Buildings, SafetyPerformance Specifications and Methods of Test41This specification is under the jurisdiction of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.56on Performance of Railing Systems and Glass for Floors and Stairs.Cur
13、rent edition approved Aug. 1, 2017. Published September 2017. Originallyapproved in 2004. Last previous edition approved in 2010 as E2358 04(2010).DOI: 10.1520/E2358-17.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annua
14、l Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.4Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036,
15、http:/www.ansi.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theD
16、evelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.13. Terminology3.1 DefinitionsGeneral terms used in this standard testmethod are defined in Terminologies E631 and E1481. Termscommon to this standard
17、test method and referenced testmethods are defined in the respective documents unless definedherein.4. Design Requirements4.1 Railing Height:4.1.1 Guardrail Systems:4.1.1.1 The fabricated height of a guardrail system, mea-sured from its top surface to the finished floor level, shall be inaccordance
18、with the authority having jurisdiction. When varia-tion in the evenness of the finished floor will result in anyindividual height measurement of the installed guardrail sys-tem to be less than minimum height designated by the authorityhaving jurisdiction, the fabricated height of the entire guardrai
19、lsystem shall be increased accordingly.4.1.1.2 Within an individual dwelling unit, the requiredrailing height shall be permitted to be reduced as allowed bythe governing jurisdiction.(1) Where the vertical distance between adjacent finishedfloor levels is less than 762 mm (30 in.), the height of the
20、guardrail system shall be at least 914 mm (42 in.) (Fig. 1)unless otherwise specified by the authority having jurisdiction.When variation in the evenness of the finished floor results inany individual height measurement of the installed guardrailsystem less than minimum, the fabricated height of the
21、 entireguardrail system shall be increased accordingly.4.1.1.3 In public assembly, elementary school, and multiple-family buildings where the vertical distance between stair andadjacent floor levels is more than 6100 mm (20 ft), the requiredheight of the top of the railing above the finished floorin
22、cluding any variation shall be at least 1220 mm (48 in.).4.1.1.4 For balconies in public-assembly buildings, therequired railing height in front of the first row of fixed seatsshall be reduced to 660 mm (26 in.) provided adequate safetyis established by the design and approved by the authorityhaving
23、 jurisdiction; however, it shall be a minimum of 910 mm(36 in.) at aisle ends and a minimum of 1070 mm (42 in.)where aisle steps are perpendicular to the railing system.4.1.2 Handrails and Stair-rail Systems:4.1.2.1 In corridors, ramp, walkways, and enclosed stair-ways having a slope of at least 1 i
24、n 20, the height of thehandrail of the stair-rail system, measured from its top surfaceto the finished floor level or tread-nose line, shall be not lessthan 860 mm (34 in.) nor more than 970 mm (38 in.). When astair-rail system is higher than 970 mm (38 in.), a separatehandrail shall be installed at
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME23582017STANDARDSPECIFICATIONFORPERFORMANCEOFGLAZINGINPERMANENTRAILINGSYSTEMSGUARDSANDBALUSTRADES

链接地址:http://www.mydoc123.com/p-530966.html