1、Designation: C 1280 04Standard Specification forApplication of Gypsum Sheathing1This standard is issued under the fixed designation C 1280; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in pare
2、ntheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the minimum requirements forand methods of application of gypsum sheathing for use as asubstrate for exterior wall claddin
3、g.1.2 Details of construction for a specific assembly toachieve the required fire resistance shall be obtained fromreports of fire-resistance tests, engineering evaluations, orlistings from recognized fire testing laboratories.1.2.1 This specification shall govern where it is morestringent (size or
4、thickness of framing and size and spacing offasteners) than the fire-rated construction.1.3 Where sound control is required for a gypsum sheathingassembly, the details of construction shall be in accordancewith the acoustical test report of an assembly that has met therequired acoustical value(s).1.
5、3.1 This specification shall govern where it is morestringent (size or thickness of framing and size and spacing offasteners) than the sound-rated construction.1.4 Where resistance to racking loads or shear is requiredfor a gypsum sheathing assembly, the details of constructionshall be in accordance
6、 with the racking or shear test report ofan assembly that has met the required racking or shear value(s).1.4.1 This specification shall govern where it is morestringent (size or thickness of framing and size and spacing offasteners) than the racking or shear-tested construction.1.5 The values stated
7、 in inch-pound units are to be regardedas the standard. The SI (metric) values given in parentheses areapproximate and are provided for information purposes only.1.6 The text of this standard references footnotes whichprovide explanatory material. These footnotes shall not beconsidered as requiremen
8、ts of the standard.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to
9、use.2. Referenced Documents2.1 ASTM Standards:2C 11 Terminology Relating to Gypsum and Related Build-ing Materials and SystemsC 79/C 79M Specification for Gypsum Sheathing BoardC 954 Specification for Steel Drill Screws for the Applica-tion of Gypsum Panel Products or Metal Plaster Bases toSteel Stu
10、ds from 0.033 in. (0.84 mm) to 0.112 in. (2.84mm) in ThicknessC 955 Specification for Load-Bearing (Transverse andAxial) Steel Studs, Runners (Tracks), and Bracing orBridging for Screw Application of Gypsum Panel Productsand Metal Plaster BasesC 1002 Specification for Steel Self-Piercing TappingScre
11、ws for the Application of Gypsum Panel Products orMetal Plaster Bases to Wood Studs or Steel StudsC 1007 Specification for the Installation of Load Bearing(Transverse and Axial) Steel Studs and Related Accesso-riesC 1063 Specification for Installation of Lathing and Furringto Receive Interior and Ex
12、terior Portland Cement-BasedPlaster2.2 U.S. Department of Commerce Publication:PS20 American Softwood Lumber Standard33. Terminology3.1 Definitions: Definitions shall be in accordance withTerminology C 11.3.2 Definitions of Terms Specific to This Standard:3.2.1 exterior cladding, na permanent materi
13、al or systemthat impedes the transmission of environmental elements to thesheathing.3.2.2 fastener, nnails, staples, or screws used for applica-tion of the sheathing.3.2.3 framing member, nstuds, headers, bracing, andblocking that serve to receive the sheathing.1This specification is under the juris
14、diction of ASTM Committee C11 onGypsum and Related Building Materials and Systems and is the direct responsibilityof Subcommittee C11.03 on Specifications for Application of Gypsum and OtherProducts in Assemblies.Current edition approved May 1, 2004. Published June 2004. Originallyapproved in 1994.
15、Last previous edition approved in 1999 as C 1280 - 99.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Availa
16、ble from Standardization Documents Order Desk, Bldg. 4 Section D, 700Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.4 horizontal application, na synonym for perpendicu-lar a
17、pplication.3.2.5 parallel application, ngypsum sheathing appliedwith the edges parallel to the framing members; a synonym forvertical application.3.2.6 perpendicular application, ngypsum sheathing ap-plied with the edges at right angles to the framing members; asynonym for horizontal application.3.2
18、.7 require, vto mandate by a force outside this speci-fication, such as a building code, project specification, contract,or purchase order.3.2.8 specified, adjpertaining to a mandatory requirementof this specification or a referenced requirement.3.2.9 specify, vto mandate by an obligation of this st
19、an-dard or a referenced document.3.2.10 vertical application, nsynonym for parallel appli-cation.3.2.11 weather resistive barrier, na temporarily exposedprotective membrane that is intended to impede the penetrationof environmental elements until the installation of a permanentexterior cladding.4. E
20、xposure After Installation4.1 Gypsum sheathing board is a substrate that shall becovered by an exterior cladding or other weather-resistivebarrier and is not intended for long-term exposure. It shall notbe exposed to the elements for more than 30 days after it hasbeen installed. Gypsum sheathing sha
21、ll be covered with aweather-resistive barrier within 30 days if the exposure timewill be more than 30 days.NOTE 1Some building codes require an additional weather-resistivebarrier. The exterior face paper of the sheathing shall be dry prior toapplication of the additional weather-resistive barrier.5
22、. Materials and Manufacture5.1 Gypsum SheathingSpecification C 79/C 79M.5.1.1 Type X (Special Fire-Resistant) Gypsum SheathingGypsum sheathing that provides a greater degree of fireresistance than regular gypsum sheathing as defined in Speci-fication C 79/C 79M.5.2 FastenersFasteners shall be as des
23、cribed in 5.2.1through 5.2.3. The fastener length shall be not less than thatspecified in Table 1.5.2.1 NailsNails shall be not less than 12-gagegalvanized,716-in. (11.1-mm) diameter head.5.2.2 Screws:5.2.2.1 Screws for fastening gypsum sheathing to woodframing members, and to steel framing members
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC12802004STANDARDSPECIFICATIONFORAPPLICATIONOFGYPSUMSHEATHING 石膏 保护 应用 标准规范 PDF

链接地址:http://www.mydoc123.com/p-464057.html