《ARMY MIL-PRF-44035 B-1997 REFRIGERATION UNITS ELECTRIC 4000 BTU FOR REFRIGERATOR-CONTAINER FIELD 8 FEET BY 8 FEET BY 10 FEET《8 英尺×8 英尺×10英尺野外冷藏集装箱的4000 BTU电制冷装置》.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-PRF-44035 B-1997 REFRIGERATION UNITS ELECTRIC 4000 BTU FOR REFRIGERATOR-CONTAINER FIELD 8 FEET BY 8 FEET BY 10 FEET《8 英尺×8 英尺×10英尺野外冷藏集装箱的4000 BTU电制冷装置》.pdf(25页珍藏版)》请在麦多课文档分享上搜索。
1、t i MIL-FRF-44035B 9949906 2044633 b4T H I INCH-POUND I MIL-PRF-44035B 28 Ju IV 1997 SUPERSEDING MIL-R-44035A 21 January 1987 PERFORMANCE SPECIFICATION REFRIGERATION UNITS, ELECTRIC, 4000 BTU FOR REFRIGERATOR-CONTAINER, FIELD, 8 FEET BY 8 FEET BY 10 FEET This specification is approved for use by all
2、 Departments and Agencies of the Department of Defense. 1. SCOPE 1.1 SCOD. This document covers one type and size of insulated, electric refrigeration unit having a capacity of 4000 British thermal units (Btu) per hour and used with an 8 foot by 8 foot by 10 foot refrigerator-container (see 6.1). 2.
3、 APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3 and 4 of this specification. section does not include documents cited in other sections of this specification or recommended for additional information or as examples. completeness of this list, docum
4、ent users are cautioned that they must meet all specified requirements documents specified in sections 3 and 4 of this specification, whether or not they are listed. This While every effort has been made to ensure the 2.2 Government documents. Beneficial comments (recommendations, additions, deletio
5、ns) and any pertinent data which may be used in improving this document should be addressed to: U.S. Army Natick Research, Development and Engineering Center, Natick, MA 01760-5018 by using the Standardization Document Improvement Proposal (DD Form 1426) I appearing at the end of thi; document or- b
6、y letter. AMSC N/A FSC 4110 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- MIL-PRF-44035B 0b 2044bL4 5Bb = 2.2.1 Sta ndards. The following standards form part of this document to the extent specified herein. Unless otherwise specified, the issues o
7、f these documents are those listed in the issue of the Department of Defense Index of Specifications and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2). STANDARDS DEPARTMENT OF DEFENSE MIL-STD-461 - Requirements for the Control of MIL-STD-462 - Measurement of Electrom
8、agnetic Interference MIL-STD-810 - Environmental Test Methods and Engineering MIL-STD-1474- Noise Limits for Army Materiel (Metric) Electromagnetic Interference Emissions and Susceptibility Characteristics Guidelines (Unless otherwise indicated, copies of the above standards are available from The S
9、tandardization Documents Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094). 2.3 Non-Government mblications. The following documents form a part of this specification to the extent specified herein. Unless otherwise specified, the issues of the documents which are DoD adopted
10、are those listed in the issue of the DoDISS cited in the solicitation. Unless otherwise specified, the issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2). NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) Standard No. 70 - National Electrical C
11、ode (Application for copies should be addressed to the National Fire Protection Association, One Battery March Park, Quincy, MA 02269-9101). NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) Standards Publication No. 250 - Enclosures for Electrical Equipment 2 Provided by IHSNot for ResaleNo repr
12、oduction or networking permitted without license from IHS-,-,- MIL-PRF-44035B W 9999906 2044635 412 W MIL-PRF-44035B (Application for copies should be addressed to the National Electrical Manufacturers Association, 1300 No. 17th Street, Suite 1847, Rosalyn, VA 22209). UNDERWRITERS LABORATORIES INC.
13、(UL) Standard 207 - Refrigerant Containing Components and Standard 303 - Refrigerant and Air Conditioning Condensing and Standard 353 - Limit Controls Accessories, Nonelectrical Compressor Units (Application for copies should be addressed to the Underwriters Laboratories Inc., 333 Pfingsten Road, No
14、rthbrook, IL 60062- 2096). INTERNATIONAL ORGANIZATION FOR STANDARDIZATION Standard 1496-2 - Thermal Containers (Application for copies should be addressed to the American National Standards Institute, 11 West 42nd Street, New York, NY 10036). 2.4 Order of p recedence. In the event of a conflict betw
15、een the text of this document and the references cited herein, the text of this document takes precedence. document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. Nothing in this 3. REQUIREMENTS 3.1 First article . When specified (see 6.2), a samp
16、le shall be subjected to first article inspection in accordance with 4.1.1. 3.2 op eratinu recruirementa. Refrigeration units shall satisfy the following minimum functional, operational and performance requirements. 3.2.1 4-hour orieration. Refrigeration units shall operate properly with suction and
17、 discharge pressures safely controlled. 3.2.2 72-hour operation. Refrigeration units shall operate properly and maintain proper conditions at thermostat sittings of 0F and 35F. 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-44035B 9999906
18、2044616 359 m MIL-PRF-44035B 3.2.3 Refriaerat ion caDacity. Refrigeration units shall have minimum net capacities of 4000 Btu/hr at a thermostat setting of OF and 6000 Btu/hr at a thermostat setting of 35OF. 3.2.4 Heatinu caDacitv. Refrigeration units shall have a gross heating capacity of not less
19、than 3000 Btu/hr at a thermostat setting not less than 45F. 3.2.5 Defrost svst.em. Refrigeration units shall have a defrost cycle terminated by temperature, automatically initiated by a time control adjustable between 4 and 24 hours and have the capacity to produce not less than 6 pounds of condensa
20、te within 30 minutes. The defrost system shall have provisions for manual defrost override. 3.2.6 Draj nacre svstem . Refrigeration units shall have a drainage system for the collection and discharge of condensate to the outside of the unit. 3.2.7 Moisture content. The moisture content of the refrig
21、eration system shall be kept at a minimum to maintain proper operation of the refrigeration unit. 3.2.8 Refrigerant leakaae. Refrigerant containing components shall be gastight. 3.2.9 - n 1. The refrigeration units shall have a control panel for the operator having, but not limited tor the following
22、 items: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. li. 3.2.10 Start and stop control Operation indicator Refrigerator internal temperature control Refrigeration unit running time indicator High and low side pressure indicators Refrigerator interior temperature indicator Manual defrost control Defrost operation
23、indicator Heating cycle operation indicator Refrigeration cycle operation indicator Power supply circuit breaker Ozone - depletina substances. The refrigerant shall be commercially available nonozone-depleting, and environmentally safe. Class I ozone-depleting substances, as determined by the Enviro
24、nmental Protection Agency (EPA), shall not be contained in, 4 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,- MIt-PRF-qY035B D 9999906 2044637 295 D MIL-PRF-44035B and shall be prohibited from use during the fabrication of the refrigeration units (s
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF44035B1997REFRIGERATIONUNITSELECTRIC4000BTUFORREFRIGERATORCONTAINERFIELD8FEETBY8FEETBY10FEET8

链接地址:http://www.mydoc123.com/p-447246.html