《ARMY MIL-PRF-43891 C-1997 REFRIGERATION UNITS ELECTRIC 9000 BTU FOR MILITARY VAN CONTAINER REFRIGERATED INSULATED [Use In Lieu Of ARMY MIL-R-0043891 B]《绝缘制冷军用大型集装箱的9000 BTU电制冷组件[代替.pdf》由会员分享,可在线阅读,更多相关《ARMY MIL-PRF-43891 C-1997 REFRIGERATION UNITS ELECTRIC 9000 BTU FOR MILITARY VAN CONTAINER REFRIGERATED INSULATED [Use In Lieu Of ARMY MIL-R-0043891 B]《绝缘制冷军用大型集装箱的9000 BTU电制冷组件[代替.pdf(26页珍藏版)》请在麦多课文档分享上搜索。
1、 MIL-PRF-YIIC 9999906 20Yb07L 630 = MIL-PRF-43891C SUPERSEDING MIL-R-0043891B (GL) 20 March 1992 MIL-R-43891A 29 December 1977 PERFORMANCE SPECIFICATION REFRIGERATION UNITS, ELECTRIC, 9000 BTU FOR MILITARY VAN CONTAINER, REFRIGERATED, INSULATED This specification is approved for use by all Departmen
2、ts and Agencies of the Department of Defense. 1. SCOPE 1.1 Scope. This document covers one type and size of insulated, electric refrigeration unit having a capacity of 9000 British thermal units (Btu) per hour and used with military van containers (see 6.1). 2. APPLICABLE DOCUMENTS 2.1 General. The
3、documents listed in this section are specified in sections 3 and 4 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. effort has been made to ensure the completeness of this list, docu
4、ment users are cautioned that they must meet all specified requirements documents cited in sections 3 and 4 of this specification, whether or not they are listed. While every Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this docu
5、ment should be addressed to: Development, and Engineering Center, Natick, MA 01760-5018 by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter. AMSC N/A FSC 4110 U.S. Army Natick Research, I Licensed by Information
6、Handling ServicesMIL-PRF-Y3%LC = 9999906 204b072 577 = MIL-PRF-43891C 2.2 Government docu ments. 2.2.1 Standards. The following standards form part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in the issue of the Departme
7、nt of Defense Index of Specifications and Standards (DoDISS) and supplement thereto, cited in the solicitation (see 6.2) . STAN DARDS DEPARTMENT OF DEFENSE MIL-STD-461 - Requirements for the Control of Electromagnetic Interference Emissions and Susceptibility Characteristics Guidelines (Metric) MIL-
8、STD-462 - Measurement of Electromagnetic Interference MIL-STD-810 - Environmental Test Methods and Engineering MIL-STD-1474 - Noise Limits for Military Materiel (Unless otherwise indicated, copies of the above standards are available from the Standardization Document Order Desk, 700 Robbins Avenue,
9、Building 4D, Philadelphia, PA 19111-5094). 2.3 Non-Government Dublicationz . The following documents form a part of this document to the extent specified herein. Unless otherwise specified, the issues of the documents which are DoD adopted are those listed in the issue of the DoDISS cited in the sol
10、icitation. Unless otherwise specified, the issues of documents not listed in the DoDISS are the issues of the documents cited in the solicitation (see 6.2). NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) Standards Publication No. 250 - Enclosures for Electrical Equipment (Application for copie
11、s should be addressed to the National Electrical Manufacturers Association, 1300 No. 17th Street, Suite 1847, Rosslyn, VA 22209). 2 Licensed by Information Handling Services. MIL-PRF-43891C 999990b 2046073 403 MIL-PRF-43891C NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) Standard No. 70 - National Elec
12、trical Code (Application for copies should be Protection Association, One Battery 9101). INTERNATIONAL ORGANIZATION addressed to the National Fire March Park, Quincy, MA 02269- FOR STANDARDIZATION Standard 1496-2 - Thermal Containers (Application for copies should be addressed to the American Nation
13、al Standards Institute, 11 West 42nd Street, New York, NY 10036). UNDERWRITERS LABORATORIES INC. (UL) Standard 207 - Refrigerant Containing Components and Accessories, Standard 303 - Refrigerant and Air Conditioning Condensing and Standard 353 - Limit Controls Nonelectrical Compressor Units (Applica
14、tion for copies should be addressed to the Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096). 2.4 Order of precedence. In the event of a conflict between the text of this document and the references cited herein, the text of this document takes precedence. Nothing in th
15、is document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 First article. When specified (see 6.2), a sample shall be subjected to first article inspection in accordance with 4.1.1. 3.2 0?3 eratina reuuirements. Refrigeration u
16、nits shall satisfy the following minimum functional, operational and performance requirements. 3.2.1 4-hour oDeration. Refrigeration units shall operate properly with suction and discharge pressures safely controlled. 3 Licensed by Information Handling ServicesMIL-PRF-43891C 99Ob 2046074 34T MIL-PRF
17、-43891C 3.2.2 72-hour oDeratio n. Refrigeration units shall operate properly and maintain proper conditions at thermostat settings of OF and 35F. 3.2.3 Befr iaeration caDacitv. Refrigeration units shall have minimum net capacities of 9,000 Btu/hr at a thermostat setting of OF and 11,000 Btu/hr at a
18、thermostat setting of 35F. 3.2.4 Heatina car, acity. Refrigeration units shall have a gross heating capacity of not less than 7,000 Btu/hr at a thermostat setting not less than 45F. 3.2.5 Defrost svs tem. Refrigeration units shall have a defrost cycle terminated by temperature, control adjustable be
19、tween 6 and 24 hours and have the capacity to produce not less than 10 pounds of condensate within 30 minutes. The defrost system shall have provisions for manual defrost override. automatically initiated by a time 3.2.6 Dra inaae svste m. Refrigeration units shall have a drainage system for the col
20、lection and discharge of condensate to the outside of the unit. 3.2.7 Moisture content . The moisture content of the refrigeration system shall be kept at a minimum to maintain proper operation of the refrigeration unit. 3.2.8 Ref riaera nt le akaae. Refrigerant containing components shall be gastig
21、ht. 3.2.9 Co ntrol Pa ne. The refrigeration units shall have a control panel for the operator having, but not limited to, the following 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. items: Start, run, stop control Operation indicator Refrigerator internal temperature control Refrigeration unit running time ind
22、icator High and low side pressure indicators Refrigerator interior temperature indicator Manual defrost control Defrost operation indicator Heating cycle operation indicator Refrigeration cycle operation indicator Power supply circuit breaker 4 Licensed by Information Handling ServicesMIL-PRF- 4 38
23、91C 3.2.10 The refrigerant shall be commercially available nonozone-depleting, and environmentally safe. Class I ozone-depleting substances, as determined by the Environmental Protection Agency (EPA), shall not be contained in, and shall be prohibited from use during the fabrication of the refrigera
24、tion unit (see 6.6) . 3.2.11 TemDe rature CO ntrol . The selected temperature of the refrigeration units shall be controlled automatically. The temperature control shall allow an incremental selection of normal refrigerator/freezer temperatures. When temperature settings are below 20F, the heating c
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF43891C1997REFRIGERATIONUNITSELECTRIC9000BTUFORMILITARYVANCONTAINERREFRIGERATEDINSULATEDUSEINLIEUOFARMYMILR0043891B

链接地址:http://www.mydoc123.com/p-447244.html