1、 AMSC N/A FSC 5925 INCH-POUND MIL-PRF-39019F 14 May 2010 SUPERSEDING MIL-PRF-39019E 08 February 2008 PERFORMANCE SPECIFICATION CIRCUIT BREAKERS, MAGNETIC, LOW-POWER SEALED, TRIP-FREE GENERAL SPECIFICATION FOR This specification is approved for use by all Departments and Agencies of the Department of
2、 Defense. 1. SCOPE 1.1 Scope. This specification covers the requirements and test procedures for single and multipole, trip-free, sealed, low-power, magnetic circuit breakers with current ratings of 0.050 amperes to 20.0 amperes inclusive, up to and including 240 volts, 60 hertz (Hz) and 400 Hz alte
3、rnating current (ac), and 50 volts direct current (dc) (see 6.1 and 6.7). These circuit breakers may also include auxiliary contacts (see 6.6.1) and terminals for monitoring circuits. Designers are CAUTIONED that these circuit breakers may contain a pure tin finish on some of the component parts (se
4、e 6.5). 1.2 Part or Identifying Number (PIN). The PIN will consist of the letter “M”, the basic number of the specification sheet, and an assigned dash number (see 3.1), as shown in the following example: M 39019/XX -XXX Designator Specification Dash number sheet number (see 3.1 for details) 2. APPL
5、ICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4 or 5 of this specification. This section does not include documents cited in other sections of this specification or recommended for additional information or as examples. While every effort has been ma
6、de to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4 or 5 of this specification, whether or not they are listed. 2.2 Government documents. 2.2.1 Specifications, standards, and handbooks. The follow
7、ing specifications, standards, and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract (see 6.2). FEDERAL SPECIFICATIONS TT-I-735 - Isopropyl Alcohol. FEDERAL STANDARDS FED-ST
8、D-H28 - Screw-Thread Standards for Federal Services. Comments, suggestions, or questions on this document should be addressed to: US Army Communications-Electronics RDEC, ATTN: RDER-PRT, Fort Monmouth, NJ 07703-5023 or emailed to Robert.Francisus.army.mil. Since contact information can change, you m
9、ay want to verify the currency of this address information using the ASSIST Online database at https:/assist.daps.dla.mil.Copyright Communications - Electronics Command Provided by IHS under license with CRAINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-3
10、9019F 2 DEPARTMENT OF DEFENSE SPECIFICATIONS (See supplement 1 for list of specification sheets.) DEPARTMENT OF DEFENSE STANDARDS MIL-STD-202 - Test Methods for Electronic and Electrical Component Parts MIL-STD-1285 - Marking of Electrical and Electronic Parts. (Copies of these documents are availab
11、le online at https:/assist.daps.dla.mil/quicksearch/ or https:/assist.daps.dla.mil/ or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094). 2.3 Non-Government publications. The following documents form a part of this document to the extent spec
12、ified herein. Unless otherwise specified, the issues of these documents are those cited in the solicitation or contract (see 6.2). AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) NCSL-Z540.3 - Calibration Laboratories and Measuring and Test Equipment - General Requirements. INTERNATIONAL ORGANIZATION F
13、OR STANDARDS (ISO) ISO 10012 - Measurement management systems - Requirements for measurement processes and measuring equipment. (A Copy of this document is available from http:/www.ansi.org/ or the American National Standards Institute (ANSI), 11 West 42nd Street, New York, NY 10036-8002). INSTITUTE
14、 OF ELECTRICAL AND ELECTRONIC ENGINEERS, INC. (IEEE) IEEE STD 315-1975 - Graphic Symbols for Electrical and Electronic Diagrams. (A Copy of this document is available from http:/www.ieee.org or from the Institute of Electrical and Electronic Engineers (IEEE), IEEE Operations Center, 445 Hoes Lane, P
15、. O. Box 1331, Piscataway, NJ 08855-1331, Phone: +1 732 981 0060, Fax: +1 732 981 1721.) 2.4 Order of precedence. Unless otherwise noted herein or in the contract, in the event of a conflict between the text of this document and the references cited herein (except for related specification sheets) t
16、he text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. 3. REQUIREMENTS 3.1 Specification sheets. The individual item requirements shall be as specified herein and in accordance with the a
17、pplicable specification sheet. In the event of any conflict between the requirements of this specification and the specification sheet, the latter shall govern. 3.2 Qualification. Circuit breakers furnished under this specification shall be products that are authorized by the qualifying activity for
18、 listing on the applicable qualified products list before contract award (see 4.5 and 6.3). 3.3 Material. Material shall be used which will enable the circuit breakers to conform to the performance requirements of this specification. Acceptance or approval of any constituent material shall not be co
19、nstrued as a guaranty of the acceptance of the finished product. Copyright Communications - Electronics Command Provided by IHS under license with CRAINot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-PRF-39019F 3 3.3.1 Metals. Metals shall be of a corrosion-resi
20、stant type or shall be suitably plated or treated to resist corrosion (see 3.21). Cadmium and zinc plating shall not be used. 3.3.1.1 Dissimilar metals. When dissimilar metals are used in intimate contact with each other, protection against electrolysis and corrosion shall be provided. The use of di
21、ssimilar metals in contact, which tend toward active electrolytic corrosion (particularly brass, copper, or steel used in contact with aluminum or aluminum alloy), is not acceptable. However, metal plating or metal spraying of dissimilar base metals to provide similar or suitable abutting surfaces i
22、s permitted. The use of dissimilar metals separated by a suitable insulating material is also permitted. Dissimilar metals are defined in 6.4. 3.3.2 Fungus resistance. Materials used shall be non-nutrient to fungus growth. 3.3.3 Solder and soldering flux. The solder and solder flux shall be of such
23、a quality as to enable the circuit breaker to meet the performance requirements of this specification. 3.4 Interface and physical dimensions. Circuit breakers shall be of the interface and physical dimensions specified (see 3.1). 3.4.1 Trip-free feature. Circuit breakers shall be so designed that th
24、e circuit cannot be maintained closed by physically holding the lever in the closed position when any pole is carrying overload currents which would normally automatically trip the breaker to the open position. 3.4.2 Trip indication. Circuit breakers shall be so designed that when the circuit breake
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARMYMILPRF39019F2010CIRCUITBREAKERSMAGNETICLOWPOWERSEALEDTRIPFREEGENERALSPECIFICATIONFOR 功率 自动 跳闸 密封

链接地址:http://www.mydoc123.com/p-447242.html