ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf
《ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf》由会员分享,可在线阅读,更多相关《ANSI NEIS 1-2015 Standard for Good Workmanship in Electrical Construction.pdf(29页珍藏版)》请在麦多课文档分享上搜索。
1、AN AMERICAN NATIONAL STANDARDNECA 1-2015Standard forGood Workmanshipin Electrical ConstructionPublished byNational Electrical Contractors AssociationStandard forGood Workmanshipin Electrical ConstructionNECA 1-2015An AmericanNational StandardPublished byNational Electrical Contractors Associationn i
2、iNOTICE OF COPYRIGHTThis document is copyrighted by NECAReproduction of these documents either in hard copy or soft (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact NECA Standards also in a hori
3、zontal or vertical position as intended.b) All materials shall be firmly secured in place, adequately supported, and permanent. Materialsembedded in concrete or masonry or otherwise part of the structure are considered sufficiently supported. c) All hardware, fittings, and accessories shall be of a
4、type designed, intended and appropriate for use and complement the items with which they are used. d) All materials and equipment including hangers, supports, fasteners or fittings, and accessories shall have corrosion protection suitable for the atmosphere in which they are installed (whether locat
5、ed indoors or outdoors). Care shall be taken during the installation to assure the integrity of the corrosion protection. Damaged corrosion protection shall be repaired during or after installation.e) All screws, bolts, nuts, clamps, fittings or other fastening devices shall be made up tight in acco
6、rdance with manufacturers and/or listing instructions.f) Plans and specifications shall be carefully followed when installing equipment. NOTE: Local building codes may have seismic requirements that affect equipment installation. Installers shall consult these codes or coordinate with the general co
7、ntractor prior to installing equipment.3. General RequirementsFigure 1 (Courtesy of Cogburn Bros., Inc.)n 41. ScopePermanence and neat appearance, a part of good workmanship, require that consideration be given to the type of atmosphere surrounding anchors and fasteners. Anchors and fasteners shall
8、be non-corrosive or have adequate corrosion resistant coatings or treatment. Weather conditions must be considered for outdoor locations, but there are also indoor locations that may be wet or damp. Fumes from industrial processing also may cause corrosive atmospheres. The possibility of corrosion d
9、ue to incompatibility between dissimilar metals must also be considered. Corrosion and deterioration is addressed in Section 300.6 of the NEC.a) All anchors and fasteners shall be of a type designed for the purpose and rated capable of adequately and safely securing the item on the base material in
10、which the anchor or fastener is used. Selection shall be based on the amount and type of load, base material, safe working load and atmosphere.b) In addition to the weight of the material, consideration should also be given to vibration, such as with motors or fans; variable loading resulting from i
11、nternal or external forces, such as operation of safety switches or circuit breakers; and shock load, when possible (see Figure 2).c) Anchors or fasteners used shall be a type designed and intended for use in the base material to which the material or support is to be attached. Generally, screws are
12、 used on wood, masonry anchors on concrete or brick, toggle bolts or similar on hollow walls, machine screws, bolts or welded studs on steel. Nails are normally used only for temporary support or for light loads, such as nonmetallic outlet and device boxes, in wood frame construction.4. Anchors and
13、FastenersFigure 2 (Courtesy of IAEI)5 n1. ScopeThe weight of the hanger or support must be considered as part of the total load. The total load also includes the materials within an enclosure. For example, the weight of the conductors in a raceway or junction or pull box shall be added to the load o
14、f the raceway or box. External forces such as vibration, operation of equipment, such as switch handles, or possible shock load shall also be considered. Safe working load shall be determined by applying recognized safety factors to the rated strength of the complete assembly and shall be based on t
15、he weakest component member. a) Hangers and supports shall be used to properly and firmly support electrical materials or equipment in a safe and permanent manner. They may be standard manufactured items or fabricated in the shop or on the job site (see Figure 3). b) They shall be of a type designed
16、 or appropriate for the purpose, have a neat and finished appearance and complement the installation.c) Job fabricated hangers and supports shall be made from standard structural shapes and hardware or systems of shapes, fittings and hardware designed for the purpose. One example would be angle iron
17、s. d) All bolts, screws, nuts, and other threaded devices shall have standard threads and heads so that they do not require special tools and may be readily replaced when necessary unless required for tamper-proof installation.e) All threads shall be fully engaged (or covered) and all parts made up
18、tight.f) The selection of hangers and supports shall be based on the following criteria:1. Amount and type of load2. Safe working load3. Atmosphere4. Manufacturers recommendations5. Job specifications6. Listing for the application (where applicable)7. Spacing intervals required by the NEC (where app
19、licable).g) Hangers and supports, whether standard manufactured items or job fabricated, shall have corrosion protection suitable for the atmosphere in which they are installed (whether located indoors or outdoors). Care shall be taken during the installation to assure the integrity of corrosion pro
20、tection. Damaged corrosion protection shall be repaired during or after installation.h) When hangers and supports that have corrosion protection are field cut, the material shall be protected by field application of an approved zinc-enriched paint or similar sealant in accordance with 300.6.5. Hange
21、rs and SupportsFigure 3 (Courtesy of IAEI)n 6NECA 1 Standard for Good Workmanship in Electrical Constructioni) Care must be taken to prevent corrosion that might result from the use of dissimilar metals in damp or wet locations. Damaged corrosion protection coatings shall be repaired during or after
22、 installation.j) Hangers and supports shall be adequately and safely attached to the building structure or structural member.k) The equipment or materials to be supported shall be securely fastened to the supporting means with material suitable for the purpose.7 n1. Scopea) Outlet and device boxes s
23、hall be of a type designed for the use and location (see Figure 4). b) Outlet and device boxes shall be securely and rigidly attached or supported plumb, level, and true. c) Box supports, hangers or brackets, when used, shall be of a type designed or suitable for the type of box used and the buildin
24、g structural member to which they are attached. In determining the type of support or fastener, consider the total load caused by any device or equipment, such as lighting fixtures, which are in turn supported by the outlet box (see Figure 5).d) Outlet and device boxes and their covers shall have co
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSINEIS12015STANDARDFORGOODWORKMANSHIPINELECTRICALCONSTRUCTIONPDF

链接地址:http://www.mydoc123.com/p-437434.html