ANSI ASHRAE 90.1-2016 I-P INT 2-2017 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf
《ANSI ASHRAE 90.1-2016 I-P INT 2-2017 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf》由会员分享,可在线阅读,更多相关《ANSI ASHRAE 90.1-2016 I-P INT 2-2017 Energy Standard for Buildings Except Low-Rise Residential Buildings.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Page 1 of 2 2017 ASHRAE. All Rights reserved. INTERPRETATION IC 90.1-2016-2 OF ANSI/ASHRAE/IES STANDARD 90.1-2016 Energy Standard for Buildings Except Low-Rise Residential Buildings Date Approved: April 20, 2017 Request from: Kenneth M. Fulk, Reed, Wells, Benson and Company, 12001 N. Central Express
2、way, Suite 1100, Dallas, TX 75243. Reference: This request for interpretation refers to the requirements presented in ANSI/ASHRAE/IES Standard 90.1-2016, Section 6.5.4.4, regarding chilled and hot water temperature reset controls. Background: Section 6.5.4.4 Exception 2 states “Where a specific temp
3、erature is required for a process.” The term “process” is vague and is not defined in the standard. Typically when people think of “processes” they think of heating or cooling for a specific process such as cooling for a manufacturing process or for a data center but generally not comfort cooling. I
4、n the 2013 version of the standard, there was an exception 1) that stated “Where the supply temperature reset controls cannot be implemented without causing improper operation of heating, cooling, humidifying, or dehumidifying systems”. In the 2013 version it was clear that if the temperature reset
5、controls were implemented and resulted in a negative impact, such as unacceptable increase in space relative humidity above current recommended levels, then one was exempt from the standard within those limitations. By deleting that exception and adding the undefined term process, it appears there c
6、ould be a limitation to the exception, and its requiring temperature reset controls for non-process applications that require a specific temperature. Depending on how one defines “process” this could have unintended implications. What about comfort cooling applications that require upper limit humid
7、ity control which requires water to be cold enough to control humidity? Is that a process? Interpretation: If humidity control and specific system temperatures are required for comfort cooling, regardless of the application, then the design would meet exception 2 and be exempt from Section 6.5.4.4 f
8、or the duration that the temperature or relative humidity limits could not be maintained if reset as noted in the standard. Question: Is this interpretation correct? Answer: No Comment: Exception 2 applies to a “process” which refers to processes using process energy, which is defined as: IC 90.1-20
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASHRAE9012016IPINT22017ENERGYSTANDARDFORBUILDINGSEXCEPTLOWRISERESIDENTIALBUILDINGSPDF

链接地址:http://www.mydoc123.com/p-431586.html