1、11-10 23 05 41 - 1 SECTION 23 05 41 NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION Noise c
2、riteria, / seismic restraints for equipment /, vibration tolerance and vibration isolation for HVAC and plumbing work. 1.2 RELATED WORK /A. Section 03 30 00, CAST-IN-PLACE CONCRETE: Requirements for concrete inertia bases. / B. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMP
3、ONENTS: Seismic requirements for non-structural equipment C. Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION: General mechanical requirements and items, which are common to more than one section of Division 23. D. Section 23 22 13, STEAM and CONDENSATE HEATING PIPING: Requirement
4、s for flexible pipe connectors to reciprocating and rotating mechanical equipment. E. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS: Requirements for optional Air Handling Unit internal vibration isolation. F. Section 23 31 00, HVAC DUCTS and CASINGS: requirements for flexible duct con
5、nectors, sound attenuators and sound absorbing duct lining. G. SECTION 23 05 93, TESTING, ADJUSTING, and BALANCING FOR HVAC: requirements for sound and vibration tests. H. SECTION 23 37 00, AIR OUTLETS and INLETS: noise requirements for G-grilles. I. SECTION 23 21 23, HYDRONIC PUMPS: vibration isola
6、tion requirements for pumps. J. SECTION 23 34 00, HVAC FANS: sound and vibration isolation requirements for fans. K. SECTION 23 65 00, COOLING TOWERS: requirements for sound and vibration isolation for cooling towers. L. SECTION 26 32 13, ENGINER GENERATORS: requirements for sound and vibration isol
7、ation. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-06M 23 05 41 - 2 M. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checklists, and training. SPEC WRITER NOTE: The designer shall perform an
8、 acoustic analysis, as stipulated in the VA HVAC Design Manual, to ensure compliance with the specified Room Design NC Levels. The designer is responsible for evaluating and controlling equipment noise and shall select equipment, specify sound ratings, and provide attenuators so that noise criteria
9、listed below, local noise ordinance levels, and OSHA requirements will not be exceeded. It is recognized that for the rooms equipped with self-contained cooling units, room noise levels shall be at least 5 dB higher than the specified values. 1.3 QUALITY ASSURANCE A. Refer to article, QUALITY ASSURA
10、NCE in specification Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. SPEC WRITER NOTE: Edit list of rooms and NC levels to suit specific project being designed. Add rooms and NC levels if required. B. Noise Criteria: 1. Noise levels in all 8 octave bands due to equipment and duc
11、t systems shall not exceed following NC levels: TYPE OF ROOM NC LEVEL Audio Speech Pathology 25 Audio Suites 25 Auditoriums, Theaters 35-40 Bathrooms and Toilet Rooms 40 Chapels 35 Conference Rooms 35 Corridors (Nurse Stations) 40 Corridors(Public) 40 Dining Rooms, Food Services/ Serving 40 Examinat
12、ion Rooms 35 Gymnasiums 50 Kitchens 50 Laboratories (With Fume Hoods) 45 to 55 Laundries 50 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-06M 23 05 41 - 3 Lobbies, Waiting Areas 40 Locker Rooms 45 Offices, Large Open 40 Offices, Small Private 35
13、 Operating Rooms 40 Patient Rooms 35 Phono/Cardiology 25 Recreation Rooms 40-45 Shops 50 SPD (Decontamination and Clean Preparation) 45 Therapeutic Pools 45 Treatment Rooms 35 Warehouse 50 X-Ray and General Work Rooms 40 2. For equipment which has no sound power ratings scheduled on the plans, the c
14、ontractor shall select equipment such that the fore-going noise criteria, local ordinance noise levels, and OSHA re-quirements are not exceeded. Selection procedure shall be in accordance with ASHRAE Fundamentals Handbook, Chapter 7, Sound and Vibration. 3. An allowance, not to exceed 5db, may be ad
15、ded to the measured value to compensate for the variation of the room attenuating effect between room test condition prior to occupancy and design condition after occupancy which may include the addition of sound absorbing material, such as, furniture. This allowance may not be taken after occupancy
16、. The room attenuating effect is defined as the difference between sound power level emitted to room and sound pressure level in room. 4. In absence of specified measurement requirements, measure equipment noise levels three feet from equipment and at an elevation of maxi-mum noise generation. /C. S
17、eismic Restraint Requirements: SPEC WRITER NOTE: Brace equipment in accordance with Seismic Design Categories B, C, D, E, and F and Importance Factor as defined in ASCE-7. Brace ductwork and piping in accordance with the above Provided by IHSNot for ResaleNo reproduction or networking permitted with
18、out license from IHS-,-,-12-06M 23 05 41 - 4 guidelines as well as the Seismic Hazard Level as found in the SMACNA Seismic Restraint Manual. 1. Equipment: a. All mechanical equipment not supported with isolators external to the unit shall be securely anchored to the structure. Such mechanical equipm
19、ent shall be properly supported to resist a horizontal force of / 50 / 20 / percent of the weight of the equipment furnished. b. All mechanical equipment mounted on vibration isolators shall be provided with seismic restraints capable of resisting a horizontal force of / 100 / 50 / percent of the we
20、ight of the equipment furnished. 2. Piping: Refer to specification Section 23 05 11, COMMON WORK RESULTS FOR HVAC and STEAM GENERATION. 3. Ductwork: Refer to specification Section 23 31 00, HVAC DUCTS AND CASINGS. D. Allowable Vibration Tolerances for Rotating, Non-reciprocating Equip-ment: Not to e
21、xceed a self-excited vibration maximum velocity of 5 mm per second (0.20 inch per second) RMS, filter in, when measured with a vibration meter on bearing caps of machine in vertical, horizontal and axial directions or measured at equipment mounting feet if bearings are concealed. Measurements for in
22、ternally isolated fans and motors may be made at the mounting feet. 1.4 SUBMITTALS A. Submit in accordance with specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, and SAMPLES. B. Manufacturers Literature and Data: 1. Vibration isolators: a. Floor mountings b. Hangers c. Snubbers d. Thrust
23、restraints 2. Bases. /3. Seismic restraint provisions and bolting./ 4. Acoustical enclosures. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-12-06M 23 05 41 - 5 C. Isolator manufacturer shall furnish with submittal load calculations for selection of
24、 isolators, including supplemental bases, based on lowest operating speed of equipment supported. /D. Seismic Requirements: Submittals are required for all equipment an-chors, supports and seismic restraints. Submittals shall include weights, dimensions, standard connections, and manufacturers certi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2305412010NOISEANDVIBRATIONCONTROLFORHVACPIPINGANDEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-1074900.html