1、11-10 23 05 12 - 1 SECTION 23 05 12 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION: This section specifies the furnishing, installation and connection of motors for HVAC and steam generation equipment. 1.2 RELATED WORK: A. Section 26 05 11, REQUIR
2、EMENTS FOR ELECTRICAL INSTALLATIONS: General electrical requirements common to more than one Section of Division 26. B. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS: Starters, control and protection for motors. C. Section 26 24 19, MOTOR-CONTROL CENTERS: Multiple motor control assemblies, which incl
3、ude motor starters. D. Section 23 05 11, COMMON WORK RESULTS FOR HVAC. E. Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT and STEAM GENERATION. F. Section 23 21 23, HYDRONIC PUMPS. G. Section 23 22 23, STEAM CONDENSATE PUMPS. H. Section 23 34 00, HVAC FANS. I. Section 23 36 00, AIR TERMINAL U
4、NITS. J. Section 23 50 11, BOILER PLANT MECHANICAL EQUIPMENT. K. Section 23 64 00, PACKAGED WATER CHILLERS. L. Section 23 65 00, COOLING TOWERS. M. Section 23 72 00, AIR-TO-AIR ENERGY RECOVERY EQUIPMENT. N. Section 23 73 00, INDOOR CENTRAL-STATION AIR-HANDLING UNITS. O. Section 23 74 13, PACKAGED, O
5、UTDOOR, CENTRAL-STATION AIR-HANDLING UNITS. P. Section 23 81 00, DECENTRALIZED UNITARY HVAC EQUIPMENT. Q. Section 23 81 23, COMPUTER-ROOM AIR-CONDITIONERS. R. Section 23 81 43, AIR-SOURCE UNITARY HEAT PUMPS. S. Section 23 81 46, WATER-SOURCE UNITARY HEAT PUMPS. T. Section 23 23 00, REFRIGERANT PIPIN
6、G. U. Section 23 82 00, CONVECTION HEATING and COOLING UNITS. V. Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS: Requirements for commissioning, systems readiness checklists, and training. 1.3 SUBMITTALS: A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the
7、following: B. Shop Drawings: 1. Provide documentation to demonstrate compliance with drawings and specifications. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 23 05 12 - 2 2. Include electrical ratings, efficiency, bearing data, power factor
8、, frame size, dimensions, mounting details, materials, horsepower, voltage, phase, speed (RPM), enclosure, starting characteristics, torque characteristics, code letter, full load and locked rotor current, service factor, and lubrication method. C. Manuals: 1. Submit simultaneously with the shop dra
9、wings, companion copies of complete installation, maintenance and operating manuals, including technical data sheets and application data. D. Certification: Two weeks prior to final inspection, unless otherwise noted, submit four copies of the following certification to the Resident Engineer: 1. Cer
10、tification that the motors have been applied, installed, adjusted, lubricated, and tested according to manufacturer published recommendations. E. Completed System Readiness Checklists provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on t
11、he date of completion, in accordance with the requirements of Section 23 08 00 COMMISSIONING OF HVAC SYSTEMS. SPEC WRITER NOTES: Designer shall review current published standards references listed below applicable to this specification. 1.4 APPLICABLE PUBLICATIONS: A. The publications listed below f
12、orm a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. National Electrical Manufacturers Association (NEMA): MG 1-2006 Rev. 1 2009 . Motors and Generators MG 22001 Rev. 1 2007 Safety Standard for Construction and Guide
13、 for Selection, Installation and Use of Electric Motors and Generators C. National Fire Protection Association (NFPA): 70-2008 National Electrical Code (NEC) D. Institute of Electrical and Electronics Engineers (IEEE): 112-04 . Standard Test Procedure for Polyphase Induction Motors and Generators E.
14、 American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE): 90.1-2007 Energy Standard for Buildings Except Low-Rise Residential Buildings Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 23 05 12 - 3 PART 2 - PRODUCTS 2.
15、1 MOTORS: A. For alternating current, fractional and integral horsepower motors, NEMA Publications MG 1 and MG 2 shall apply. B. All material and equipment furnished and installation methods shall conform to the requirements of Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS; and Section 26 05 21, LOW-
16、VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW). Provide all electrical wiring, conduit, and devices necessary for the proper connection, protection and operation of the systems. Provide premium efficiency type motors as scheduled. Unless otherwise specified for a particular app
17、lication, use electric motors with the following requirements. C. Single-phase Motors: Motors for centrifugal fans and pumps may be split phase or permanent split capacitor (PSC) type. Provide capacitor-start type for hard starting applications. /1. Contractors Option - Electrically Commutated motor
18、 (EC Type): Motor shall be brushless DC type specifically designed for applications with heavy duty ball bearings and electronic commutation. The motor shall be speed controllable down to 20% of full speed and 85% efficient at all speeds./ D. Poly-phase Motors: NEMA Design B, Squirrel cage, inductio
19、n type. 1. Two Speed Motors: Each two-speed motor shall have two separate windings. Provide a time- delay (20 seconds minimum) relay for switching from high to low speed. E. Voltage ratings shall be as follows: 1. Single phase: a. Motors connected to 120-volt systems: 115 volts. b. Motors connected
20、to 208-volt systems: 200 volts. c. Motors connected to 240 volt or 480 volt systems: 230/460 volts, dual connection. 2. Three phase: a. Motors connected to 208-volt systems: 200 volts. b. Motors, less than 74.6 kW (100 HP), connected to 240 volt or 480 volt systems: 208-230/460 volts, dual connectio
21、n. c. Motors, 74.6 kW (100 HP) or larger, connected to 240-volt systems: 230 volts. d. Motors, 74.6 kW (100 HP) or larger, connected to 480-volt systems: 460 volts. e. Motors connected to high voltage systems (Over 600V): Shall conform to NEMA Standards for connection to the nominal system voltage s
22、hown on the drawings. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-11-10 23 05 12 - 4 F. Number of phases shall be as follows: 1. Motors, less than 373 W (1/2 HP): Single phase. 2. Motors, 373 W (1/2 HP) and larger: 3 phase. 3. Exceptions: a. Herm
23、etically sealed motors. b. Motors for equipment assemblies, less than 746 W (one HP), may be single phase provided the manufacturer of the proposed assemblies cannot supply the assemblies with three phase motors. G. Motors shall be designed for operating the connected loads continuously in a 40C (10
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2305122010GENERALMOTORREQUIREMENTSFORHVACANDSTEAMGENERATIONEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-1074899.html