1、02-11 22 67 19.16 - 1 SECTION 22 67 19.16 REVERSE-OSMOSIS WATER EQUIPMENT SPEC WRITER NOTES: 1. Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraph. 2. RO systems require a duplex water softener on the inle
2、t water side for optimum performance and reduced maintenance. 3. For boiler plants, the application of RO is indicated when make-up rates are high and the solids content of the make-up water is 450 ppm or higher. If the make-up water analysis indicates a dealkalyzer is needed, then an RO system shou
3、ld definitely be evaluated in lieu of the dealkalyzer. Use of RO will often decrease boiler water chemical costs by 80%, and will reduce blowdown energy losses. Normal make-up rates are 5% 10%. PART 1 GENERAL 1.1 DESCRIPTION Provide complete industrial-type packaged reverse osmosis (RO) water treatm
4、ent system producing high purity water by removal of dissolved minerals, bacteria, particles and organic impurities. Designed for continuous automatic operation. The system shall include pre-filter, product storage tank and all devices necessary for fully operational system. RO system operation will
5、 be controlled by the water level in the product storage tank. 1.2 RELATED WORK A. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS. B. Systems for service other than boiler plant make-up water, Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. C. Section 22 31 11, WA
6、TER SOFTENERS. D. Section 23 07 11, HVAC, PLUMBING & BOILER PLANT INSULATION E. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATION F. SECTION 22 08 00, COMMISSIONING OF PLUMBING SYSTEMS. Requirements for commissioning, systems readiness checklist, and training. 1.3 QUALITY ASSURANCE Manufact
7、urer shall have been engaged in the manufacture of reverse osmosis systems as a primary product for at least ten years. The ten Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-11 22 67 19.16 - 2 year requirement supersedes any conflicting requirem
8、ent in other parts of the project specification. 1.4 SUBMITTALS A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. B. Manufacturers Literature and Data: 1. Catalog cuts, complete description and specifications of all equipment and accessories 2. Accessories incl
9、uding filters, product storage tank, pressure gages and test kit. 3. Performance data including normal and maximum flow and pressure drop. Certification that required performance will be achieved. 4. Piping. C. Complete detailed layout, setting, arrangement, and installation drawings including. Draw
10、ings shall also show all parts of the apparatus including relative positions, dimensions, and sizes and general arrangement of connecting piping. D. Completed System Readiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on
11、 the date of completion, in accordance with the requirements of Section 22 08 00,COMMISSIONING OF PLUMBING SYSTEMS. 1.5 PROJECT CONDITIONS A. Influent Water Analysis: Maximum Silt Density Index (SDI) Rating _ Turbidity, NTU _ Maximum Free Chlorine and/or Chloramine _ppm Color: _ Maximum pH (continuo
12、us) _ Minimum pH (continuous) _ Maximum pH (cleaning-30 minutes) _ Minimum pH (cleaning30 minutes) _ Confirm the analysis with current samples and tests. B. Design Parameters: Normal System Flow: _L/s (_gpm) Maximum System Flow: _L/s (_gpm) Daily Water Usage: _liters per day (_gallons per day) Daily
13、 Hours of Water Demand: _ Operating Temperature Range: _-_ degrees C (_ - _ degrees F) Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-11 22 67 19.16 - 3 1.6 APPLICABLE PUBLICATIONS: A. The publications listed below form a part of this specificati
14、on to the extent referenced. The publications are referenced in the text by the basic designation only. B. American Society of Mechanical Engineers (ASME): B40.100-2005Pressure Gages and Gage Attachments C. ASTM International (ASTM): A269-07.Seamless and Welded Austenitic Stainless Steel Tubing for
15、General Service. D1785-06Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120. D. American Water Works Association (AWWA): B300-04.Hypochlorites B301-04.Liquid Chlorine C651-05.Disinfecting Water Mains E. National Electrical Manufacturers Association (NEMA): ICS-6-1993(R2001, R2006) I
16、ndustrial Control and Systems: Enclosures F. National Fire Protection Association (NFPA): 70- 08 .National Electrical Code. G. Department of Health and Human Services, Food and Drug Administration (FDA): CFR 21, Chapter 1, Part 175.300, 02 Resinous and Polymeric Coatings PART 2 - PRODUCTS SPEC WRITE
17、R NOTE: Make material requirements agree with applicable requirements specified in the referenced Applicable Publications. Update and specify only that which applies to the project. 2.1 REVERSE OSMOSIS SYSTEM A. Packaged automatic reverse osmosis system mounted on steel frame, designed for project c
18、onditions. Equipment arranged on the frame to allow easy access for operating, maintenance and repair. Unit shall include reverse osmosis membrane, pressure vessels, pre-filtration system, high pressure pump and all required piping, wiring and controls for a fully operational system. B. Performance
19、Requirements: 1. Membrane reject ratio: 98% minimum. TDS of product is 2% maximum of input TDS. 2. Capture rate: 70% minimum. Maximum amount of water to drain 30% of input. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-11 22 67 19.16 - 4 C. RO M
20、embrane Elements: Thin-film composite with FRP over-wrap, anti-telescoping device, u-cup brine seal. The design salt rejection shall be 98% based on 2000 ppm water at 225 psig at 77 degrees F. D. RO Element Housings: Type 304 stainless steel with PVC end caps held in place with stainless steel bands
21、. Each housing assembly complete with one set of O-rings and O-ring lubricant. Housings for systems over 9000 gallons per day shall be constructed of fiberglass reinforced polyester (FRP). Provide cleaning connections. E. High Pressure Pumps and Motors: / Single / Duplex / vertical multistage high e
22、fficiency centrifugal type with Type 304 stainless steel casing, shaft, impellers. Tungsten carbide and ceramic shaft seals. Cast iron frame with flanged piping connections. Premium efficiency TEFC motor selected to be non-overloading on the entire performance curve. F. Manual Valves: 1. Pump Thrott
23、le Valve: Type 316 stainless steel ball valve, socket welded. 2. Concentrate Throttle Valve, Recycle Throttle Valve: In-line needle style, stainless steel, rated for 300 psi minimum. 3. Inlet Isolation Valve, Product and Concentrate Check Valves: PVC with EPDM seats and seals. 4. Feedwater Sample Va
24、lve, Product Water Sample Valve: PVC plug valve with EPDM seats and seals. 5. High Pressure Sample Valve: Type 316 stainless steel plug valve. G. Automatic Valves: 1. Automatic Inlet Shut Off Valve: Solenoid type, diaphragm actuated, normally closed, constructed of glass-filled Noryl thermoplastic.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA226719162011REVERSEOSMOSISWATEREQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-1074895.html