1、02-10 22 35 00 - 1 SECTION 22 35 00 DOMESTIC WATER HEAT EXCHANGERS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section describes the requir
2、ements for domestic hot water heat exchangers including thermometers and all necessary accessories, connections and equipment. 1.2 RELATED WORK: A. Section 09 91 00, PAINTING: Preparation and finish painting. B. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING. C. Section 22 11 23, DOMESTIC WATER
3、PUMPS: Circulating Pump. D. Section 23 07 11, HVAC, PLUMBING, AND BOILER PLANT INSULATION: Heater Insulation. E. Section 22 05 19, METERS AND GAGES FOR PLUMBING PIPING, 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING, and 22 11 00, FACILITY WATER DISTRIBUTION: Piping, Fittings, Valves and Gages. 1
4、.3 SUBMITTALS: A. Submit manufacturers literature and data pertaining to the water heater in properly bound package, in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Include the following as a minimum: 1. Heat Exchangers. 2. Pressure and Temperature Relief Valves. 3. St
5、eam Control Valves. 4. Thermometers. 5. Pressure Gages. 6. Vacuum Breakers. B. Equipment components in contact with potable water shall meet NSF compliance requirements in document NSF 61, “Drinking Water System Components Health Effects. C. A form U-1 or other documentation stating compliance with
6、the ASME Boiler and Pressure Vessel code. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 35 00 - 2 1.4.APPLICABLE PUBLICATIONS: A. The publications listed below form a part of this specification to the extent referenced. The publications ar
7、e referenced in the text by the basic designation only. B. American National Standard Institute (ANSI): Z21.22-00/4.4A-00 Relief Valves for Hot Water Supply systems C. American Society of Mechanical Engineers (ASME): B1.20.1-01 . Pipe Threads, General Purpose B16.5-03 . Pipe Flanges and Flanged Fitt
8、ings, NPS through NPS 24 B16.24-06 Cast Copper Alloy Pipe Flanges, Class 150, 300,600, 900, 1500, 2500 PTC 25.3-02 Pressure Relief Devices Section IV-07 Heating Boilers Section VIII-07 Pressure Vessels Division 1 SPEC WRITER NOTE: Delete between /_/ if not applicable to project. Also delete any othe
9、r item or paragraph not applicable in the section and renumber the paragraphs. 1.5 AS-BUILT DOCUMENTATION A. The electronic documentation and copies of the Operations and Maintenance Manual, approved submittals, shop drawings, and other closeout documentation shall be prepared by a computer software
10、 program complying with Section 508 of the Rehabilitation Act of 1973, as amended (29 U.S.C 794d). The manufacturer or vendor of the software used to prepare the electronic documentation shall have a Voluntary Product Accessibility Template made available for review and included as part of the Opera
11、tions and Maintenance Manual or closeout documentation. All available accessibility functions listed in the Voluntary Accessibility Template shall be enabled in the prepared electronic files. As Adobe Acrobat is a common industry format for such documentation, following the document, “Creating Acces
12、sible Adobe PDF files, A Guide for Document Authors“ that is maintained and made available by Adobe free of charge is recommended.” B. Four sets of manufacturers literature and data updated to include submittal review comments and any equipment substitutions. C. Four sets of operation and maintenanc
13、e data updated to include submittal review comments shall be inserted into a three ring binder. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 35 00 - 3 All aspects of system operation and maintenance procedures, including piping isometrics
14、, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall include troubleshooting techniques and procedures for emergency situations. Notes
15、 on all special systems or devices such as damper and door closure interlocks shall be included. A List of recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools the owner will be required to employ shall be insert
16、ed into the As-Built documentation. PART 2 - PRODUCTS 2.1 SHELL AND TUBE, DOMESTIC WATER HEAT EXCHANGERS: A. The shell and tube heat exchangers shall be semi-instantaneous type, /vertical/ /horizontal/ with water in the shell and steam in the tubes. The shell and tube heat exchanger shall be a packa
17、ged assembly of tank, heat exchanger coils, controls, and specialties constructed of ASME code copper lined, carbon steel shell with 1035 kPa (150 psig) minimum working pressure. B. The stand shall be factory fabricated for floor mounting. C. The tappings shall be factory fabricated of materials com
18、patible with heat exchanger shell. For sizes 50 millimeter or DN50 (NPS 2) and smaller, the tappings shall be threaded ends fabricated in accordance to ASME B1.20.1. For sizes 65 millimeters or DN65 (NPS 2-1/2) and larger, the tappings shall be flanged according to ASME B16.5 for steel and stainless
19、 steel flanges and ASME 16.24 for copper and copper alloy flanges. D. Shell insulation shall comply with ASHRAE 890.1 and suitable for operating temperature. The entire shell and nozzles shall be completely surrounded except connections and controls. E. The heat exchanger coils shall be constructed
20、from copper and fabricated in a helix wound for steam heating medium. The pressure rating shall be equal to or greater than the steam supply pressure plus 50%. F. The temperature controls shall be based upon an adjustable temperature transmitter that operates a control valve and is capable of mainta
21、ining outlet water temperature within 2 degrees C (4 degrees F) of setting. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 35 00 - 4 G. Safety control shall be automatic, high temperature limit shutoff device. H. The relief valves shall be
22、ASME rated and stamped for combination temperature and pressure relief valves. One or more relief valves with total relieving capacity at least as great as heat input shall be included. The pressure setting shall be less than the working pressure rating of the heat exchanger minus 10 percent. /I. Th
23、e Pressure storage vessel shall be all welded construction and ASME Code Section VIII stamped for a working pressure of 1035 kPa (150 psig) . The storage tank shall be / carbon steel with a minimum of 16 mm (5/8 inch) thick cement lining / carbon steel with 4.9 kg/sq. meter (3 lb./sq. ft) copper lin
24、ing / solid copper-silicon, grade SB-96 / solid stainless steel type / 304 / 316L /epoxy lined/. The storage vessel shall be provided with a fiberglass insulation system in compliance with ASHRAE 90.1./ J. Controls: 1. Steam control valve shall regulate the control of steam flow to the heating coil
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2235002010DOMESTICWATERHEATEXCHANGERSPDF

链接地址:http://www.mydoc123.com/p-1074886.html