1、02-10 22 34 00 - 1 SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS SPEC WRITER NOTE: Delete between /-/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL DESCRIPTION: This section describes the require
2、ments for installing a complete domestic gas fired hot water heating system ready for operation including water heaters, thermometers, and all necessary accessories, connections, and equipment. 1.2 RELATED WORK: A. Section 09 91 00, PAINTING: Preparation and finish painting. B. Section 22 05 11, COM
3、MON WORK RESULTS FOR PLUMBING. C. Section 22 11 23, DOMESTIC WATER PUMPS: Circulating Pump. D. Section 23 07 11, HVAC, PLUMBING, AND BOILER PLANT INSULATION: Heater Insulation. E. Section 22 05 19, METERS AND GAGES FOR PLUMBING PIPING, 22 05 23, GENERAL-DUTY VALVES FOR PLUMBING PIPING, and 22 11 00,
4、 FACILITY WATER DISTRIBUTION: Piping, Fittings, Valves and Gages. F. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENT FOR NON STRUCTURAL COMPONENTS: Seismic Restraint for Equipment. 1.3 QUALITY ASSURANCE: A. Comply with American Society of Heating, Refrigerating and Air- Conditioning Engineers (ASHRA
5、E) for efficiency performance: 1. ASHRAE 90.1, Energy Efficient Design of New Buildings except Low-Rise Residential Buildings” for commercial water heaters.” B. Electrical components, devices and accessories shall be listed and label as defined in NFPA 70 by a qualified testing agency, and marked fo
6、r intended location and application. C. ASME code construction shall be a vessel fabricated in compliance with the ASME boiler and Pressure Vessel Code: Section VIII, Division 1. D. Fabricate and label equipment components that will be in contract with potable water to comply with NSF 61, “Drinking
7、Water System Components Health Effects” E. the gas fired domestic water heater shall conform to Section 13 05 41 on Seismic restraint requirements, withstanding Seismic movement Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 34 00 - 2 witho
8、ut separation of any parts from the equipment when subjected to a Seismic event. 1.4 SUBMITTALS: A. Submit manufacturers literature and data pertaining to the water heater in properly bound package, in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Include the following
9、as a minimum: 1. Water Heaters. 2. Pressure and Temperature Relief Valves. 4. Thermometers. 5. Pressure Gages. 6. Vacuum Breakers. B. For each natural gas fired domestic hot water heater type and size, the following characteristics shall be submitted: 1. Rated Capacities 2. Operating characteristics
10、 3. Electrical characteristics 4. Furnished specialties and accessories 5. A form U-1 or other documentation stating compliance with the ASME Boiler and Pressure Vessel code. C. Shop drawings shall include wiring diagrams for power, signal and control functions. D. Seismic qualification certificates
11、 shall be submitted that details equipment anchorage components identifies equipment center of gravity with mounting and anchorage provisions, and whether the seismic qualification certificate is based on an actual test or calculations. E. The domestic water heater shall be certified and labeled by
12、a testing agency. 1.5. APPLICABLE PUBLICATIONS: A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. B. American Society Of Sanitary Engineering (ASSE): 1005 . Performance Requirements
13、for Water Heater Drain Valves, 20 mm (3/4 inch) size C. American National Standard Institute (ANSI): Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22 34 00 - 3 Z21.10.1-06 Gas Water Heaters Volume 1, Storage Water Heaters with Input Ratings o
14、f 75000 Btu per hour or less. Z21.10.3-04 Gas Water Heaters, Volume III, Storage Water Heaters with Input Ratings above 75000 Btu per hour, circulating and instantaneous. Z21.15A-01 . Manually Operated Gas Valves for Appliances, Appliance connector Valves, and Hose End Valves Z21.18-07 Gas appliance
15、 Pressure Regulators Z21.20-05 Automatic Gas Ignition Systems and Components Z21.21-05 Automatic Valves for Gas Appliance Z21.22B-01 . Relief Valves for Hot Water Supply systems D. American Society of Mechanical Engineers (ASME): B1.20.1-83(R 2006) . Pipe Threads, General Purpose(Inch) B16.5-03 . St
16、andard for Pipe Flanges and Flanged Fittings: NPS through NPS 24. B16.24-06 Cast Copper Alloy Pipe Flanges and Flanged Fittings: classes 150, 300, 400, 600, 900, 1500, and 2500. PTC 25.3-02 Pressure Relief Devices Section IV-07 Boiler and Pressure Vessel Code; Section IV, Recommended Rules for the C
17、are and Operation of Heating Boilers Section VIII D1-07 . Boiler and Pressure Vessel Code, Section VIII, Pressure Vessels Division 1 Basic Coverage E. National Fire Protection Association (NFPA) 54-09 National Fuel Gas Code F. Underwriters Laboratories, Inc. (UL): SPEC WRITER NOTE: Delete between /_
18、/ if not applicable to project. Also delete any other item or paragraph not applicable in the section and renumber the paragraphs. 1.6 AS-BUILT DOCUMENTATION A. The electronic documentation and copies of the Operations and Maintenance Manual, approved submittals, shop drawings, and other closeout do
19、cumentation shall be prepared by a computer software program complying with Section 508 of the Rehabilitation Act of 1973, as amended (29 U.S.C 794d). The manufacturer or vendor of the software Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-02-10 22
20、 34 00 - 4 used to prepare the electronic documentation shall have a Voluntary Product Accessibility Template made available for review and included as part of the Operations and Maintenance Manual or closeout documentation. All available accessibility functions listed in the Voluntary Accessibility
21、 Template shall be enabled in the prepared electronic files. As Adobe Acrobat is a common industry format for such documentation, following the document, “Creating Accessible Adobe PDF files, A Guide for Document Authors“ that is maintained and made available by Adobe free of charge is recommended.”
22、 B. Four sets of manufacturers literature and data updated to include submittal review comments and any equipment substitutions. C. Four sets of operation and maintenance data updated to include submittal review comments shall be inserted into a three ring binder. All aspects of system operation and
23、 maintenance procedures, including piping isometrics, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall include troubleshooting techn
24、iques and procedures for emergency situations. Notes on all special systems or devices such as damper and door closure interlocks shall be included. A List of recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- VA2234002010FUELFIREDDOMESTICWATERHEATERSPDF

链接地址:http://www.mydoc123.com/p-1074885.html