UL SUBJECT 693-2006 Outline of Investigation for Excess Pressure Pumps for Wet Pipe Sprinkler Systems (Issue 3)《湿管喷淋系统用超压泵调查大纲 发布编号 3》.pdf
《UL SUBJECT 693-2006 Outline of Investigation for Excess Pressure Pumps for Wet Pipe Sprinkler Systems (Issue 3)《湿管喷淋系统用超压泵调查大纲 发布编号 3》.pdf》由会员分享,可在线阅读,更多相关《UL SUBJECT 693-2006 Outline of Investigation for Excess Pressure Pumps for Wet Pipe Sprinkler Systems (Issue 3)《湿管喷淋系统用超压泵调查大纲 发布编号 3》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDecember 5, 20061SUBJECT 693OUTLINE OF INVESTIGATIONFOREXCESS PRESSURE PUMPS FOR WET PIPE SPRINKLER SYSTEMSIssue Number: 3DECEMBER 5, 2006Summary of TopicsThis new issue of SU 693 is being issued
2、 through ULs electronicpublishing system to ensure format uniformity between the PDF andHTML versions of the document. No substantive changes have beenincorporated in the document.The UL Foreword is no longer located within the UL Standard. For informationconcerning the use and application of the re
3、quirements contained in thisStandard, the current version of the UL Foreword is located onULStandardsInfoNet at: http:/ 2006 UNDERWRITERS LABORATORIES INC.UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULDECEMBER 5, 2006SUBJECT 6932No Text on T
4、his PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULCONTENTSGENERAL1 General 4PERFORMANCE2 General 43 Installation Test .54 Operational Test 55 Endurance Test .56 Hydrostatic Pressure Strength Test .6MARKING7 General 6DECEMBER 5, 2006 SUBJ
5、ECT 693 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULGENERAL1 General1.1 Excess pressure pumps are intended for installation on wet pipe sprinkler systems as a means ofestablishing excess pressure for suppression of false alarms due to wat
6、er surges (water hammer).1.2 The purpose of the investigation of the excess pressure pump is to determine that it is designed forinstallation on alarm check valve equipped, wet pipe sprinkler systems to provide an automaticallycontrolled means of maintaining excess pressure in the systems, substanti
7、ally in excess of the maximumpressure likely to be present in the supply lines.1.3 Maintenance of excess pressure in systems at all times is intended to prevent movement of the alarmvalve clapper during surges of the water supply line pressure thus eliminating false alarms due to flowthrough the val
8、ve occasioned by surges. The pump assembly and the required control pressure switchesare to be securely installed on a heavy gauge metal panel which in turn is intended for installation on asprinkler riser immediately above the alarm valve.1.4 The panel is generally fastened to a wall or the sprinkl
9、er riser close to the alarm check valve. Thepanel incorporates a control circuit, armor cable, electric motor, mounting plate, differential pressureswitch, low pressure supervisory switch, pump, and low pressure alarm switch. The electrical componentsare to be covered by the UL Recognized Component
10、Program and each part is clearly identified as such.1.5 All the electrical components are to be reviewed and tested by ULs Burglary Protection and SignalingDepartment and the following tests conducted:a) Input Test,b) Temperature Test,c) Dielectric Strength Test.PERFORMANCE2 General2.1 In addition,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便